Instruction Manual COMMERCIAL ELECTRIC WATER HEATERS MODELS LTE 66D, LTE 80D & LTE 120D, Series 200 INSTALLATION - OPERATION - SERVICE - MAINTENANCE - LIMITED WARRANTY 500 Tennessee Waltz Parkway Ashland City, TN 37015 ® Thank you for buying this energy efficient water heater. We appreciate your confidence in our products. PLACE THESE INSTRUCTIONS ADJACENT TO HEATER AND NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE.
SAFE INSTALLATION, USE, AND SERVICE The proper installation, use and servicing of this water heater is extremely important to your safety and the safety of others. Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual.
GENERAL SAFETY INFORMATION PRECAUTIONS HYDROGEN GAS (FLAMMABLE) DO NOT USE THIS WATER HEATER IF ANY PART HAS BEEN EXPOSED TO FLOODING OR WATER DAMAGE. Immediately call a qualified service technician to inspect the water heater and to replace any part of the control system which has been under water. If the unit is exposed to the following, do not operate heater until all corrective steps have been made by a qualified service technician. 1. External fire. 2. Damage. 3. Firing without water.
TABLE OF CONTENTS ELECTRICAL.......................................................................................11 General.........................................................................................11 Branch Circuit...............................................................................11 Calculating Amperage/Overcurrent Protection.............................11 WIRING DIAGRAMS........................................................................... 12 OPERATION.....................
DIMENSIONS AND CAPACITIES DATA ANODE ROD HOT CONNECTION COLD CONNECTION 8" C A B Figure 1 TABLE 1 - ROUGH-IN DIMENSIONS Capacity A B Approx. Shipping Weight C US Gals. Litres Inches cm Inches cm Inches cm Lbs. Kg. 66 250 60.13 153 52.75 134 22 56 146 66.22 80 303 60.50 154 52.25 133 24 61 174 78.93 119 450 61.38 156 54.38 138 28 71 268 121.56 TABLE 2 - RECOVERY CAPACITIES Element INPUT Wattage KW (Upper/Lower) NON-SIMULATANEOUS 3000/3000 3.0 4000/4000 4.
APPROVALS ® All models are listed by Underwriters Laboratories Inc.
FEATURES AND COMPONENTS ANODE COLD ELECTRICAL JUNCTION BOX (ACCESS PANEL) ACCESS PANELS DRAIN VALVE INSTALL SUITABLE DRAIN PANS UNDER WATER HEATERS TO PREVENT DAMAGE DUE TO LEAKAGE. REFER TO WATER HEATER LOCATION ON PAGE 8. I N S TA L L T H E R M A L E X PA N S I O N TA N K IF CHECK VALVE OR PRESSURE REDUCING VA LV E I S U S E D I N SUPPLY LINE. INSTALL VACUUM RELIEF IN COLD WATER INLET LINE AS REQUIRED BY LOCAL CODES.
LOCATING THE NEW WATER HEATER FACTS TO CONSIDER ABOUT THE LOCATION Water heater life depends upon water quality, water pressure and the environment in which the water heater is installed. Water heaters are sometimes installed in locations where leakage may result in property damage, even with the use of a drain pan piped to a drain. However, unanticipated damage can be reduced or prevented by a leak detector or water shut-off device used in conjunction with a piped drain pan.
INSTALLATION REQUIRED ABILITY CONTAMINATED WATER Installation and service of this water heater requires ability equivalent to that of a qualified installer or service agency (page 2) in the field involved. Plumbing and electrical work is required. This water heater shall not be connected to any heating system(s) or component(s) used with a non-potable water heating appliance. Toxic chemicals, such as those used for boiler treatment shall not be introduced into this system.
paragraph. The new valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 psi = 1,035 kPa) and a discharge capacity not less than the water heater Btu/hr or KW input rate as shown on the water heater’s model rating plate. For safe operation of the water heater, the temperature and pressure relief valve must not be removed from its designated opening nor plugged.
ELECTRICAL This is an example of calculating heater amperage for both types of element operation. From this, the branch circuit conductor and overcurrent protection sizing can be established. The example (T-4) is of a single-phase 240 volt unit with two, 3 kw elements. Check the water heater model and rating plate for actual specifications and substitute those values in the following. TABLE 3 Non-simultaneous: Simultaneous: (T6 - Circuit) (T4 - Circuit) 3000 ÷ 240 = 12.
WIRING DIAGRAMS T-4 T-6 208 or 240 VOLT SIMULTANEOUS OPERATION SINGLE PHASE OPERATION 208 or 240 VOLT NON-SIMULTANEOUS SINGLE PHASE OPERATION SUPPLY LEADS L2 L1 SUPPLY LEADS L2 L1 Figure 3 12 RED RED RED RED BLACK BLACK RED BLACK BLACK BLACK BLACK RED GND GREEN BLUE YELLOW BLACK GND GREEN
OPERATION GENERAL INITIAL START UP Refer to the Features and Components section of this manual (page 7) for the location of components mentioned in the instructions that follow. The following checks should be made by the installer when the heater is placed into operation for the first time. NEVER turn on power to the water heater without being certain the water heater is filled with water and a temperature and pressure relief valve is installed in the relief valve opening. 2.
TEMPERATURE REGULATION T-4 THERMOSTAT (UPPER & LOWER) NOTE: It is not necessary to adjust the upper thermostat for a dual element unit. However, if it is adjusted above the factory set point 140°F (60°C) it is recommended that it not be set higher than the lower thermostat setting. To change the temperature setting: It is recommended that lower water temperatures be used to avoid the risk of scalding.
MAINTENANCE GENERAL ANODE ROD INSPECTION The anode rod is used to protect the tank from corrosion. Most hot water tanks are equipped with an anode rod. The submerged rod sacrifices itself to protect the tank. Instead of corroding tank, water ions attack and eat away the anode rod. This does not affect water’s taste or color. The rod must be maintained to keep tank in operating condition. Periodically the drain valve should be opened and the water allowed to run until it flows clean.
TROUBLESHOOTING CHECKLIST CHECKLIST ABNORMAL SOUNDS Before calling for service, check the following points to see if the cause of trouble can be identified and corrected. 1. Sediment or lime scale accumulations on the elements causes sizzling and hissing noises when the heater is operating. • Reviewing this checklist may eliminate the need of a service call and quickly restore hot water service. See Figure 2 on page 7 in this manual to identify and locate water heater components.
LEAKAGE CHECKPOINTS Instructions: Use this illustration as a guide when checking for sources of water leakage. You or your dealer may be able to correct what appears to be a problem. NOTE: Cover and Insulation shown removed to reveal tank top. Where possible remove or lift top cover to examine threads of fittings installed into tank for evidence of leakage. Correct fitting leaks as necessary. Relief Valve Condensation and dripping may appear on pipes when cold water temperature is low.
WARRANTY COMMERCIAL WATER HEATER LIMITED WARRANTY EFFECTIVE WHAT'S NOT COVERED For 3 Years, in the event of a tank leak, we will repair or, at our • Problems caused by improper: gas supply line sizing, gas type, venting, connections, combustion air, voltage, wiring, or fusing For 1 Year, in the event of part failure, we will repair or, at our discretion, replace the defective part.
REPAIR PARTS LIST Now that you have purchased this water heater, should a need ever exist for repair parts or service, simply contact the company it was purchased from or direct from the manufacturer listed on the rating plate on the water heater. Be sure to provide all pertinent facts when you call or visit.
Figure 8 TABLE 6 - COPPER SHEATH ELEMENT AND WATTAGE CHART 208V 240V K.W. ELEMENT WATTAGE PART NO. PART NO. 3.0 3000 9003956115 9001879005 3.5 3500 9000092015 9003948115 4.0 4000 9003951115 9003956115 4.5 4500 9002645005 9000092015 5.0 5000 9004688105 9003957005 5.