XDC 6000 Watt and 12000 Watt Series DigitalProgrammable DC Power Supply Operating Manual
Output Performance Specifications
TM-XDOP-01XN A–11
Transient Response Time
1
Time to recover within 0.75% of rated output of previous level after step change
in load current between 50% and 100%.
Mode Crossover
Maximum deviation as a percentage of rated output voltage.
Peak–Peak and RMS Noise Bandwidth Limits
The frequency range for Peak to Peak measurements is 10 Hz–20 MHz.
The frequency range for RMS measurements is 10 Hz–100 kHz.
Maximum Remote Sense Line Drop Compensation
Minimum 3.8 V for each line, 5 V typical
Isolation
1. Time for the output voltage to recover within 0.75% of rated output of its previous level after a step change
in load current of up to 50% - 100% and 100% to 50% of rated output
Mode Time
Voltage Mode 3 ms (6000 W models)
Voltage Mode 30 ms (12000 W models)
CV – CC Overshoot 1%
AC Input to Output 1350 V
ac
AC Input to Chassis 1350 V
ac
Output to Chassis 600 V
ac
TM-XDOP-01XN.book Page 11 Monday, July 17, 2006 11:19 AM