User manual
MENU SYSTEM
2001 Xantrex Technology, Inc.
5916 - 195th Street N. E.
Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
SW Series Inverter/Charger
Part No. 2031-5
Rev. C: February 2001
Page
55
In either mode, the SET START BULK TIME menu item setting under the BULK CHARGE TRIGGER
TIMER (15) menu heading can be used to increase the battery charging regulation voltage to the BULK
VOLTS DC setting.
Note: By setting the beginning time equal to the ending time, the grid usage timer feature is defeated.
INFORMATION DISPLAY
The following information is displayed as additional Menu Items.
After Start Charge time: SELL mode charges battery. FLT mode charges battery.
After End Charge time: SELL mode sells battery to AC1. FLT mode drops AC1 and inverts.
Timer on when start <> end. Timer off when start = end;
Sell and float modes use timer. SLT and LBX mode ignore timer.
INFORMATION FILE BATTERY (19) MENU HEADING
This Menu Heading provides additional information about the battery charging system. It has no user
adjustable settings.
INFORMATION DISPLAY
The following information is displayed as Menu Items.
Batt temp comp changes battery voltage reading away from actual.
HBCO resets at: 6v/48, 3v/24 and 1.5v12 under HBCO.
LowBatt Transfer used in LBX, FLT modes only.
Goes back to battery at LowBattCutIn (aka LBCI).
For LBX mode set below LBCI so charger won’t cycle batteries up and down set LBCO below.