CABLE/WIRE SIZE O.D. 20% FILL 40% FILL
Inches [mm] A B C A B C
UNSHIELDED 4-pair, 24 AWG Cat 5 UTP 0.220 [5.6] 9 9 19 18 19 39
TWISTED PAIR 4-pair, 24 AWG Cat.3 UTP 0.190 [4.8] 12 13 26 24 26 52
TELEPHONE 2-pair, 24 AWG 0.140 [3.6] 22 24 48 45 48 96
3-pair, 24 AWG 0.150 [3.8] 19 20 42 39 41 84
4-pair, 24 AWG 0.190 [4.8] 12 13 26 24 26 52
25-pair, 24 AWG 0.410 [10.4] 2 2 5 5 5 11
COAXIAL RG58/U 0.195 [5.0] 11 12 24 23 24 4
RG59/U 0.242 [6.1] 7 8 16 15 16 32
RG62/U 0.242 [6.1] 7 8 16 15 16 32
RG6/U 0.270 [6.9] 6 6 12 12 12 25
TWINAXIAL 100 Ohm 0.330 [8.4] 4 4 8 8 8 17
SHIELDED TYPE 1 0.390 [9.9] 2 3 6 5 6 12
TWISTED PAIR TYPE 2 0.465 [11.8] 2 2 4 4 4 8
TYPE 3 0.245 [6.2] 7 7 15 14 15 31
FIBER OPTIC Two Strand (Duplex) 0.190 [4.8] 12 13 26 24 26 52
Multimode,62.5/125 µm
* Capacity range is calculated at 20% to 40% of raceway area as stated in a proposed revision to the Commercial Building Standard for
Telecommunication Pathways & Spaces, EIA/TIA-569. Actual wire fill capacity may vary based on applications, cable types, and number,
as well as type of fittings. (Fittings may cause additional variances to the fill capacity.)
5400 RACEWAY WIRE FILL CAPACITIES FOR COMMUNICATION (DIVIDED)*
3.72 sq. in.
[95mm]
3.72 sq. in.
[95mm]
1.85 sq.in.
[46mm]
1.74 sq.in.
[44mm]
3.72 sq. in.
[95mm]
1 3/4"
[44mm]
1 3/4"
[44mm]
AB
C
C
C
D
5 1/4"
[133mm]
D
5 1/4"
[133mm]
Wire Capacity is reduced to allow for proper conductor bend radius and maximum permissible heat rise.
Wire Capacity 5400 Raceway
Note No one compartment may exceed capacity specified in A, B, and C.
Total Raceway wire capacity may not exceed as specified in D
WITHOUT DEVICES
14 12 10 8 6
A4130351313
B4130351313
C7148602626
D7148602626
WITH IN-LINE DEVICES
14 12 10 8 6
A 41 30 35 13 13
B 41 30 35 13 13
C7148602626
D7148602626