Installation Guide
Table Of Contents
- Installation Manual
- Legal Provisions
- Table of Contents
- 1 Information on this Document
- 2 Safety
- 3 Scope of Delivery
- 4 Product Overview
- 5 Mounting
- 6 Electrical Connection
- 7 Commissioning
- 8 Disconnecting the Inverter from Voltage Sources
- 9 Decommissioning the Inverter
- 10 Technical Data
- 11 Compliance Information
- 12 Contact
- Instrucciones de instalación
- Disposiciones legales
- Índice
- 1 Indicaciones sobre este documento
- 2 Seguridad
- 3 Contenido de la entrega
- 4 Vista general del producto
- 5 Montaje
- 6 Conexión eléctrica
- 7 Puesta en marcha
- 8 Desconexión del inversor de la tensión
- 9 Puesta fuera de servicio del inversor
- 10 Datos técnicos
- 11 Información de cumplimiento
- 12 Contacto
- Instructions d’installation
- Dispositions légales
- Table des matières
- 1 Remarques relatives à ce document
- 2 Sécurité
- 3 Contenu de la livraison
- 4 Vue d’ensemble des produits
- 5 Montage
- 6 Raccordement électrique
- 7 Mise en service
- 8 Mise hors tension de l’onduleur
- 9 Mise hors service de l’onduleur
- 10 Caractéristiques techniques
- 11 Informations sur le respect des spécifications
- 12 Contact
6 Electrical Connection
SMA Solar Technology AG
Installation Manual SBxx-1SP-US-41-IA-xx-10 31
Position Designation
M
Network ports A and B for connecting a router or network switch
N
USB port for connecting a USB flash drive (for service purposes)
O
MFR slot for connection to the multifunction relay
P
Pin connector BAT is not used
Q Equipment grounding terminals for the equipment grounding conductors
of the PV array
R Communication assembly
S
Jack DISPLAY for the LED assembly connection in the enclosure lid of the
Connection Unit
6.2 AC Connection
6.2.1 Requirements for the AC Connection
Additionally required material (not included in the scope of delivery):
☐ Conduits (trade size: 21mm (0.75in) or smaller with suitable reducer bushing)
☐ UL-listed raintight or liquidtight conduit fittings (trade size: 21mm (0.75in) or smaller with
suitable reducer bushing)
Requirements on the AC conductors:
☐ The maximum permitted temperature of the terminal block for AC connection of 105°C
(221°F) must be observed.
☐ The conductors with regards to its ampacity, rated temperatures, operating conditions and its
power loss must be made in accordance with the local standards and the National Electrical
Code
®
ANSI/NFPA 70 or the Canadian Electrical Code
®
CSA C22.1.
☐ Conductor type: copper wire
☐ Maximum permissible temperature at SB3.0-1SP-US-41, SB3.8-1SP-US-41, SB5.0-1SP-US-41
and SB6.0-1SP-US-41: 75°C (+167°F)
☐ The conductors must be made of solid wire, stranded wire or fine stranded wire. When using
fine stranded wire, bootlace ferrules must be used.
☐ Conductor cross-section: 4mm² to 16mm² (12AWG to 6AWG)