Installation Manual

1
Revenue grade inverter P/N: SExxxxH-US000NNC2
2
For power de-rating information refer to: https://www.solaredge.com/sites/default/files/se-temperature-derating-note-na.pdf
3
-40 version P/N: SExxxxH-US000NNU4
Single Phase Inverter with HD-Wave Technology Specifications (North America) MAN-01-00308-1.3
80
Technical Specifications - Single Phase Inverters with HD-Wave Technology (North America)
Unit
Revenue Grade Data, ANSI
C12.20
Rapid Shutdown - NEC 2014 and
2017 690.12
SE3000H-US SE3800H-US SE5000H-US SE6000H-US SE7600H-US SE10000H-US SE11400H-US
Optional
1
Automatic Rapid Shutdown upon AC Grid Disconnect
STANDARD COMPLIANCE
Safety
Grid Connection Standards
UL1741, UL1741 SA, UL1699B, CSA C22.2, Canadian AFCI according to T.I.L. M-07
IEEE1547, Rule 21, Rule14 (HI)
FCC part15 class B
Yes
Emissions
RoHS
INSTALLATION SPECIFICATIONS
AC output conduit size / AWG
range
3/4” minimum / 14 - 6 AWG
DC input conduit size / # of strings
/ AWG range
3/4” minimum / 1-2 strings / 14-6 AWG
3/4” minimum / 1-3 strings /
14-6 AWG
Dimensions with Safety Switch
(HxWxD)
17.7 x 14.6 x 6.8 / 450 x 370 x 174 21.3 x 14.6 x 7.3 / 540 x 370 x 185 in/mm
Weight with Safety Switch 22 / 10 25.1 / 11.4 26.2 / 11.9 38.8 / 17.6 lb / kg
Noise < 50 dBA
Cooling
< 25
Natural Convection Natural convection and internal fan (user replaceable)
Operating Temperature Range °F/ °C
Protection Rating
-13 to +140 / -25 to +60
2
(-40°F / -40°C option)
3
IP65/ NEMA 3R (Inverter with Safety Switch)
3/4” minimum / 14-4 AWG