Brochure/Catalogue
D
Cable entries
D.332712630000
Klippon
®
cable glands – Nickel–plated Brass – Ex e, Ex d, IP66 / IP68 for non-armoured cables
/
6:
/
7KUHDG
Cable gland exclusively for non-armoured cables and lines.
Technical data
Material Brass, nickel-plated
O-ring / Seal insert CR / CR
Temperature range -35 °C...90 °C
Degree of protection IP66, IP68 - 2.5 bar
Water depth 25 m (30 Min.)
Marking ATEX: II 2GD, Ex db IIC Gb, Ex ta IIIC Da and/or II 2 GD, Ex eb IIC Gb, Ex ta IIIC Da, IECEx: Ex db IIC Gb, Ex eb IIC Gb, Ex ta IIIC Da
Certificate no. (ATEX / IECEx / EAC) SIRA 05ATEX1287X / IECEx SIR 05.0067X / RUC-DE.IT08.B.00594
Note
Length "L" depends on the cable diameter used.
Cable glands made of brass with natural surface are available in the online catalogue (catalog.weidmueller.com).
Ordering data
Type Thread KB L/L1 SW SUHB Qty. Order No.
metric, nickel-plated brass
KSG M20 BN O NI 2 G16 M 20 4-8.4 33 / 16 25 L24 20 1911510000
KSG M20 BN O NI 2 G20S M 20 7.2-11.7 33 / 16 25 L24 20 1911540000
KSG M20 BN O NI 2 G20 M 20 9.6-14 33 / 16 30 L30 20 1911560000
KSG M25 BN O NI 2 G25 M 25 13.5-20 33 / 16 38 L38 20 1911570000
KSG M32 BN O NI 2 G32 M 32 19.5-26.3 33 / 16 46 L46 10 1911580000
KSG M40 BN O NI 2 G40 M 40 23-32.2 37 / 16 55 L55 10 1911590000
KSG M50 BN O NI 2 G50S M 50 28.1-38.2 37 / 16 65 L65 1 1911600000
KSG M50 BN O NI 2 G50 M 50 33.1-44.1 37 / 16 65 L65 1 1911610000
KSG M63 BN O NI 2 G63S M 63 39.2-50.1 37 / 19 80 L80 1 1911620000
KSG M63 BN O NI 2 G63 M 63 46.7-56 37 / 19 80 L80 1 1911630000
KSG M75 BN O NI 2 G75 M 75 58-68 37 / 19 90 L90 1 1075360000
KSG M75 BN O NI 2 G75S M 75 52.1-62 37 / 19 90 L90 1 1075350000
Note
• All cable glands have a thread pitch of 1.5mm.
• In the case of Ex d applications, the inner threads used for cable glands must meet the requirements of section 5.3 of EN/IEC 60079-1. In the screwed in position, at least 5 threads must be engaged.
• If the cable glands are installed in non-metallic Ex e connection equipment, these must be connected to the protective earth of the system.
• The connection cable must be laid securely and inflexibly to rule out tensile stress.
• Installation specifications and tightening torques can be found in the installation instructions. For further information please use our online catalogue: catalog.weidmueller.com.
Ex-cable glands – Brass