Brochure/Catalogue
A
A.78 2690170000
Universal solutions for PLC input/
output cards
RSM – Isolated interfaces
for 16 digital output signals
Digital output relay interface for transmitting electrical
signals between the PLC and the field via pre-wired cables
of Weidmüller’s universal system.
• Input/output reinforced insulation (basic between
contacts)
• Positive switching
Technical data
Connection data and functionality
Connection on control side
Number of poles (control side)
Relay type
LED status display per relay
LED status of the supply voltage
Fuse per relay
Power supply fuse
Nominal input data
Input voltage
Input current
Operating voltage (supply)
Operating current (supply)
Nominal output data
Contact material
Operating voltage
Max. AC continuous current
Minimum contact current
Minimum contact voltage
Mechanical service life
General data
Ambient temperature (operational)
Storage temperature
Approvals
Insulation coordination (EN 50178)
Rated input insulation voltage
Rated output insulation voltage
Overvoltage category input/output
Overvoltage category output/output
Pollution severity level
Pulse voltage test (1,2/50μs)
Insulation test voltage
Clearance input/output
Dimensions
Clamping range, min./max. (field)
Clamping range, min./max. (supply)
Mounting rail
Length x width
Note
Ordering data
Screw connection without switch
Screw connection with switch
Tension-clamp connection without switch
Tension-clamp connection with switch
Note
Accessories
Note
RSM-16 FOR 1CO
RCL relays, 1 CO contact and switch
Connector according IEC60603-13/DIN41651
20-pole plug
RCL
green
yellow
No
3.15 A
24 V DC ± 10%
17 mA
24 V DC ± 10%
2 A
AgNi 90/10
250 V AC
2 A
0.01 A
10 V
3 x 10
7
switching cycles
-25...40°C
-40...60 °C
CE; EAC
< 50 V AC
< 250 V AC
III
II
2
6 kV
1.2 kVAC
≥ 5.5 mm
Screw connection
0.13 mm² / 6 mm²
0.13 mm² / 6 mm²
TS 35, TS 32
263 mm / 109 mm
Type Height Order No.
RSM-16 FOR 1CO S 75 mm 9445140000
Relay 8693260000 RCL314024 24VDC 1CO
RSM – Isolated interfaces for digital output signals