Brochure/Catalogue
Klippon
®
POK – Polyester enclosures
Technical Overview
Technical data
Ex Standard
Enclosure material Glass bre-reinforced polyester to DIN 16913 with added graphite Glass bre-reinforced polyester to DIN 16913
Surface Black, similar to RAL 9011 Grey, similar to RAL7001
IP Rating IP 66 to DIN EN 60529 IP 66 to DIN EN 60529
NEMA Rating 4, 4x 4, 4x
Equipment mounting M4 to M6 threaded bushes M4 to M6 threaded bushes
Enclosure mounting 4 holes for M4 to M6 screw 4 holes for M4 to M6 screw
Lid xing M4/M6 slothead / crosshead screws from stainless steel M4/M6 slothead / crosshead screws from stainless steel
Impact Resistance 7J to IEC 60029-0 IK08 (5J) to DIN EN 50102
Gasket material Silicone (VMQ) Chloroprene
Temperature range -55 °C...+100 °C -40 °C...+100 °C
Torque screws of lid M4 2.0 – 2.5 Nm 2.0 – 2.5 Nm
Torque screws of lid M6 2.5 – 3.0 Nm 2.5 – 3.0 Nm
Surface resistance (in ohms) < 10
9
Ohm 10
12
Ohm
Flammability UL 94 V0, self extinguishing UL 94 V0, self extinguishing
Toxicity Halogen and cadmium-free Halogen and cadmium-free
Note
Approvals for empty enclosures
Ex Standard
ATEX certicate IBExU13ATEX1003 U
ATEX marking
T II 2G Ex e IIC Gb or T II 2G Ex eb IIC
T II 2D Ex tb IIIC Db or T II 2D Ex tb IIIC
IECEx certicate IECEx IBE 13.0003U
IECEx marking Ex e IIC Gb or Ex eb IIC
Ex tb IIIC Db or Ex tb IIIC
EAC RUC-DE.08.B.00472 RUC-DE.08.B.00472
cULus E 256877 E 256877
Lloyd‘s Register 14/20001 14/20001
Russian Maritime Register 19.00109.272
DNV GL TAE00002R2 TAE00002R2
AEx E223792
Note
Approvals terminal enclosures
ATEX certicate IBExU13ATEX1004 X
ATEX marking
T II 2G Ex e IIC T6...T5 Gb or T II 2G Ex eb IIC T6...T5
T II 1G Ex ia IIC T6...T5 Ga or T II 1G Ex ia IIC T6...T5
T II 2(1)G Ex e ia IIC T6...T5 Gb or T II 2(1)G Ex eb ia IIC T6...T5
T
II 2D Ex tb IIIC T 85 °C...100 °C Db
or
T
II 2D Ex tb IIIC T 85 °C...100 °C
IECEx certicate IECEx IBE 13.0004X
IECEx marking Ex e IIC T6...T5 Gb or Ex eb IIC T6...T5
Ex ia IIC T6...T5 Ga or Ex ia IIC T6...T5
Ex e ia IIC T6...T5 Gb or Ex eb ia IIC T6...T5
Ex tb IIIC T 85 °C...100 °C Db or Ex tb IIIC T 85 °C...100 °C
EAC certicate RUC-DE.08.B.01328 AEx certicate E223792
EAC marking II 2 G Ex eb IIC T6/T5
II 2 G Ex e IIC T6/T5 Gb
II 1 G Ex ia IIC T6/T5
II 1 G Ex ia IIC T6/T5 Ga
II 2(1) G Ex eb ia IIC T6/T5
II 2(1) G Ex e ia IIC T6/T5 Gb
II 2 D Ex tb IIIC T 85 °C...100 °C
II 2 D Ex tb IIIC T 85 °C...100 °C Db
AEx marking Class I, Zone 1, AEx e IIC Gb T6..T4
Class I, Zone 2, AEx e IIC Gc T6..T4
Class I Div.2 Group A,B,C,D T6…T4
Class II Div.2 Group F,G
Zone 21, AEx tb IIIC Db
KOSHA certicate 16-AV4BO-246X
KOSHA marking Ex e IIC T6...T5 Gb or Ex eb IIC T6...T5
Ex ia IIC T6...T5 Ga or Ex ia IIC T6...T5
Ex e ia IIC T6...T5 Gb or Ex eb ia IIC T6...T5
Ex tb IIIC T 85 °C...100 °C Db or Ex tb IIIC T 85 °C...100 °C
Note If you have specic requirements for installations within potentially explosive atmospheres, please contact Weidmüller for a copy of the approval
certicates. For details of power dissipation, please contact your Weidmüller representative.
C
C.1312712630000
Enclosures