User Documentation
User Manual Managed Switches
128
The data map addresses of Weidmüller switches shown in the following table start from MODBUS
address 30001 for Function Code 4. For example, the address offset 0x0000 (hex) equals MODBUS
address 30001, and the address offset 0x0010 (hex) equals MODBUS address 30017. Note that all
the information read from Weidmüller switches are in hex mode. To interpret the information, refer to
the ASCII table for the translation (e.g. 0x4D = ‘M’, 0x6F = ‘o’).
Address Offset
Data Type
Interpretation
Description
System Information
0x0001
1 word
Unit ID (Ethernet = 1)
0x0002
1 word
HEX
Product Code = 0x0003
0x0010
20 words
ASCII
Vendor Name = "Weidmueller"
Word 0 Hi byte = 'W'
Word 0 Lo byte = 'e'
Word 1 Hi byte = 'i'
Word 1 Lo byte = 'd'
Word 2 Hi byte = 'm'
Word 2 Lo byte = 'u'
Word 3 Hi byte = 'e'
Word 3 Lo byte = 'l'
Word 4 Hi byte = 'l'
Word 4 Lo byte = 'e'
Word 5 Hi byte = 'r'
Word 5 Lo byte = ' '
Word 6 Hi byte = '\0'
Word 6 Lo byte = '\0'
0x0030
20 words
ASCII
Product Name = “IE-SW-VL08M”
Word 0 Hi byte = ‘I’
Word 0 Lo byte = ‘E’
Word 1 Hi byte = ‘-’
Word 1 Lo byte = ‘V’
Word 2 Hi byte = ‘L’
Word 2 Lo byte = ‘0’
Word 3 Hi byte = ‘8’
Word 3 Lo byte = ‘M’
Word 4 Hi byte = ‘\0’
Word 4 Lo byte = ‘\0’
0x0050
1 word
Product Serial Number
0x0051
2 words
Firmware Version
Word 0 Hi byte = major (A)
Word 0 Lo byte = minor (B)
Word 1 Hi byte = release (C)
Word 1 Lo byte = build (D)
0x0053
2 words
HEX
Firmware Release Date
For example:
Word 0 = 0 x 0609
Word 1 = 0 x 0705
Firmware was released on 2007-05-06 at 09
o’clock
0x0055
3 words
HEX
Ethernet MAC Address
Ex: MAC = 00-01-02-03-04-05
Word 0 Hi byte = 0 x 00
Word 0 Lo byte = 0 x 01