Internet www.weidmueller.com
PUSH IN connector design:
Handling:
Recommended tool:
• Screwdriver blade 0.4 x 2.5
• Screwdriver blade standard DIN 5264
Solid conductors:
1. A stripped solid conductor is simply plugged into the contact point up to the end stop.
Conductors with wire-end ferrule:
1. Stranded conductors with crimped-on wire-end ferrules, with and without plastic collars, are
simply plugged into the contact point up to the end stop.
When plugging-in, an initial resistance (spring clamp) has to be overcome
Flexible conductors:
1. Open the contact point by activating the slider / push-button / pusher
2. Insert stranded conductors, without crimped-on wire-end ferrules.
3. Remove tool from slider / push-button / pusher
• When connecting or disconnecting the conductors, the actuating force
of the slider / push-button / pusher must be max. 40 N
• After connection, the strand/cable has to be checked,
whether the strand is tight and cannot be pulled out again.
slider / push-button / pusher
conductor entry
spring clamp
end stop
max. 40 N