Instruction Manual

Watlow Series PD 111 Chapter 9 Device Config Table
Parameter Name
and Description
Web Page Your
Settings
Range Default Modbus*
(Read/write and
scaling)
Alarm 6 - Send Email EnableSelect to enable an email to be sent on activation of Alarm 6.,Configuration Alarm 6,,No (0)Yes (1),No (0),
(R/W)
Alarm 6 - Email Alert SubjectEnter subject of email for Alarm 6. This message will appear in the subject line of the sent email.,Configura-
tion Alarm 6,,,0, (R/W)
Alarm 6 - Alarm HysteresisSelect hysteresis value. Alarm hysteresis defines how far the process must return into the normal operating
range before the alarm can clear.,Configuration Alarm 6,,0 to 2000000200,3000,609-610 (R/W) (/1000)
Alarm 6 - Latching EnableSelect to enable alarm to be latched. Latched alarms must be manually cleared when the process returns to a
safe value.,Configuration Alarm 6,,No (0)Yes (1),No (0),608 (R/W)
Alarm 6 - Latching ActionSelect to cause an active alarm to clear if latching is enabled and the process returns to a safe value.,Monitor De-
vice,,No (0)Yes (1),No (0),176 (R/W)
Alarm 6 - Silence EnableSelect to enable alarm silencing. Silencing allows the operator to disable alarm while the controller is in an alarm
state.,Configuration Alarm 6,,No (0)Yes (1),No (0),607 (R/W)
Alarm 6 - Silence ActionSelect to cause an active alarm to silence if silencing is enabled.,Monitor Device,,No (0)Yes (1),No (0),175 (R/W)
Alarm 6 - BlockingSelect to prevent a low alarm from triggering when the process temperature is initially lower than the alarm set point
due to Power On or Set point change. Also applies to high alarms.,Configuration Alarm 6,,Off (0)Set Point Change (1)Power On (2)Set
Point Change and Power On (3),Off (0),606 (R/W)
Alarm 6 - Send Email Enable
Select to enable an email to be
sent on activation of Alarm 6.
Configuration Alarm 6 No (0)
Yes (1)
No (0) (R/W)
Alarm 6 - Email Alert Subject
Enter subject of email for
Alarm 6. This message will
appear in the subject line of
the sent email.
Configuration Alarm 6 Up to 30 alpha-numeric
characters
(R/W)
Alarm 6 - Alarm Hysteresis
Select hysteresis value. Alarm
hysteresis defines how far the
process must return into the
normal operating range before
the alarm can clear.
Configuration Alarm 6 0 to 2000000200 degrees or
units
3000 609-610 (R/W)
(/1000)
Alarm 6 - Latching Enable
Select to enable alarm to be
latched. Latched alarms must
be manually cleared when the
process returns to a safe value.
Configuration Alarm 6 No (0)
Yes (1)
No (0) 608 (R/W)
Alarm 6 - Latching Action
Select to cause an active
alarm to clear if latching is
enabled and the process
returns to a safe value.
Monitor Device No (0)
Yes (1)
No (0) 176 (R/W)
Alarm 6 - Silence Enable
Select to enable alarm silencing.
Silencing allows the operator to
disable alarm while the con-
troller is in an alarm state.
Configuration Alarm 6 No (0)
Yes (1)
No (0) 607 (R/W)
Alarm 6 - Silence Action
Select to cause an active
alarm to silence if silencing is
enabled.
Monitor Device No (0)
Yes (1)
No (0) 175 (R/W)
Alarm 6 - Blocking
Select to prevent a low alarm
from triggering when the
process temperature is initial-
ly lower than the alarm set
point due to power on or set
point change. Also applies to
high alarms.
Configuration Alarm 6 Off (0)
Set Point Change (1)
Power On (2)
Set Point Change and
Power On (3)
Off (0) 606 (R/W)