Installation Guide

14
Each and every Warmup loose heating cable is subjected
to careful testing before it is shipped from the factory.
However, damage does sometimes occur in storage or
transit, and sometimes during installation. We strongly
recommend you test your heaters:
After unpacking them but before you install them,
and
After you have installed them but before you install the
floor covering (i.e. while the cables are still exposed),
and
After installation of the final floor covering.
Complete a simple visual inspection of the heating cable to make sure there is no visible damage.
A simple electrical inspection can be done with a digital ohmmeter to ensure the ohms
resistance is what it should be. The ohm resistance should be measured between the two
conductors without touching the yellow-green wire, which is the ground connection.
Checking for resistance between the two conductor wires ensures there is no break in the cold
lead conductor and the heat resistance wire. It does not assure you that there is no electrical
short in the circuit.
Place one probe on the black wire. Place the other probe on the yellow (red wire for 240V).
Resistance can vary significantly depending on the ambient temperature and an allowance of
+/- 5% from the norm is acceptable.
Ensure cable is fully insulated :
Test across the yellow-green wire (ground). Place the other probe on the yellow (red wire
for 240V).
Confirm the reading is infinity (open circuit).
Repeat these steps to check the reading between the yellow-green wire (ground) and the
black wire.
There should be no continuity between these wires and the ohms reading should be infinity
(not zero). If your meter shows a number of ohms between these wires, your heating cable
has an electrical short. Take note of the resistance and contact Warmup.
In order to conduct a more thorough test for insulation verification, Warmup recommends the
use of a megohmeter. Connect the instrument’s black cable to the system’s ground and the
red to the either one of the heating cable leads.
Note that depending on your meter model, you may read “kilo-Ohms” probably due to your
fingers touching the probes (it’s your body’s conductivity). If the readings are not satisfactory,
do not commence installation contact Warmup for further advice.
Testing the System