Datasheet

1
78
Sockets with Solid State Relay
Solid state relay
Input: 24 V DC
Output: 0 V ... 24 V DC / 3.5 A
Solid state relay
Input: 24 V DC
Output: 0 V ... 24 V DC / 5 A
Description
Item No.
Pack.
unit
Item No.
Pack.
unit
Relay socket with solid state relay, for DIN 35 rail 788-700 1 788-701 1
Technical Data
Accessories see pages 80 ... 81 Accessories see pages 80 ... 81
Control circuit:
Nominal input voltage (V
N
) 24 V DC 24 V DC
Input voltage range 18 V ... 30 V DC 15 V ... 30 V DC
Control current U
N
(20°C) 7 mA ±10 % 9.3 mA ±10 %
Release voltage 8 V DC 2.5 V DC
Control circuit resistance 3.2 kΩ 2.1 kΩ
Load circuit:
Load switching voltage range 0 ... 24 V DC 0 ... 30 V DC
Peak reverse voltage 33 V 36 V
Max. switching current 3.5 A DC DC12/DC13 (5 A DC)
Min. switching current 1 mA DC
Pull-in time 50 μs
Drop-out time 600 μs
Switching frequency (max.) 100 Hz at 5 A
Forward voltage at max. switching current < 0.1 V DC 0.3 V DC
Nominal operating mode continuous duty continuous duty
Dielectric strength control/switching circuit 2.5 kV 2.5 kV
Nominal voltage acc. to VDE 0110 Part 1/4.97,
IEC 60664-1
250 V / 2.5 kV / 2 250 V / 2.5 kV / 2
Degree of protection IP 20 IP 20
Ambient operating temperature -20 °C ... +60°C -40 °C ... +60°C
Storage temperature -40 °C ... +70 °C -40 °C ... +70 °C
Dimensions (mm) W x H x L 15 x 53 x 86 15 x 63 x 86
Height from upper-edge of DIN 35 rail Height from upper-edge of DIN 35 rail
Wire connection CAGE CLAMP
®
SCAGE CLAMP
®
S
Cross sections 0.34 mm² ... 2.5 mm² / AWG 22 ... 12 0.34 mm² ... 2.5 mm² / AWG 22 ... 12
Stripped lengths 9 ... 10 mm / 0.37 in 9 ... 10 mm / 0.37 in
Approvals DIN VDE 0140 part 1, DIN EN 61140; DIN VDE 0160,
EN 50178; degree of protection II
DIN VDE 0140 part 1, DIN EN 61140; DIN VDE 0160,
EN 50178; degree of protection II
13 +
A1
+
A2
-
14 -
13 +
A1
+
A2
-
14 -

Summary of content (1 pages)