Voltmaster Engine-Driven Generators C-Series D-Series S-Series LN-Series SG-Series T-Series Owner’s Manual July 2011
Voltmaster Engine-Driven Generators Table of Contents 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.1 1.2 1.3 1.4 2 1 2 2 2 3 3 3 4 4 4 Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2.1 2.2 2.3 3 Read before using . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Generator models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Specifications. . . . . . . . . . . . . . .
Voltmaster Engine-Driven Generators 3.2 3.3 Operating the generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.1 Models LR50EL and LR60EL. . . . . . . . . . . . . . . . 3.2.2 SG-Series (SafeGen/RoofPro) models . . . . . . 3.2.3 Air in fuel line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.4 Electrical loads. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.5 First-time use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.6 Starting the generator . .
Voltmaster Engine-Driven Generators List of Figures Figure 3-1 Figure 3-2 Figure A-1 Typical standby installation. . . . . . . . . . . . . . . . Fuel mixture adjustment screw . . . . . . . . . . . . Formula for calculating wattage . . . . . . . . . . . 19 26 33 List of Tables Table 3-1 Table 3-2 Table A-1 Table A-2 Table A-3 Owner’s Manual Recommended oil grade . . . . . . . . . . . . . . . . . . Battery type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Voltmaster Engine-Driven Generators iv Owner’s Manual
Voltmaster Engine-Driven Generators 1 Introduction 1.1 Read before using WARNING Improper use of equipment could cause serious injury or death. Prior to using this equipment, carefully read, understand, and observe all instructions in this manual and the engine manual. This is an industrial-type electric generator. This equipment is potentially hazardous and could cause physical injury or even death if improperly used.
Voltmaster Engine-Driven Generators 1.
Voltmaster Engine-Driven Generators 1.3.2 D-Series Model Max. watts Rated watts LR50 LR60 LR130 5000 6000 13,000 4000 120/240 5500 120/240 12,000 120/240 1.3.3 S-Series Model Max. watts Rated watts A25 A30 A50 A55 A60 LA50 LA55 LA60 LR70 LR80 LR105 3000 3000 5000 5500 6000 5000 5500 6000 7000 8000 10,000 2400 2400 4000 4500 5000 4000 4500 5000 6500 7500 9500 Rated amps Run time Fuel capacity 1/2 load (hrs.) (gal.) Run time full load (hrs.) 33.3/16.7 45.8/22.9 100/50 5 5 8 10.5 10.
Voltmaster Engine-Driven Generators 1.3.5 SG-Series Model Max. watts Rated watts LR70 LR105 LR150 7000 10,000 15,000 6500 120/240 9500 120/240 12,000 120/240 Rated voltage Rated amps Run time Fuel capacity 1/2 load (hrs.)* (gal.) Run time full load (hrs.)* 54.1/27 79.2/39.6 100/50 8 8 8 10.3 5.8–6 5–6 Rated amps Fuel Run time capacity 1/2 load (gal.) (hrs.)* Run time full load (hrs.)* 17.4 7.5 27.8 12 41.6 18 52 23 5 5 8 8 8 8 18 18 7.6–10.5 7.6–10.5 6 6 6–8 6–8 7.2 7.2 13.4 8.5–9 5.
Voltmaster Engine-Driven Generators 2 Safety Information 2.1 Operating safety DANGER Explosion hazard. Owner’s Manual ■ NEVER operate generator in an explosive atmosphere or near combustible materials. ■ Keep generator, engine, fuel, and other combustibles away from sparks, open flame, and burning objects. ■ Do not smoke near engine. ■ Never use generator to jump-start a vehicle. ■ Before filling or draining fuel, stop engine and allow it to cool. ■ Use correct fuel.
Voltmaster Engine-Driven Generators DANGER Asphyxiation hazard. Engine exhaust contains carbon monoxide, a poison gas you cannot see or smell. ■ NEVER operate engine indoors, EVEN IF doors and windows are open. ■ Operate the engine OUTSIDE, far away from doors, windows, and vents. ■ Refill and drain fuel tank only in a well ventilated area. ■ Perform maintenance in a well ventilated area. WARNING Shock hazard. 6 ■ Use extreme caution when working on or with electrical components.
Voltmaster Engine-Driven Generators WARNING Fire hazard. ■ Before transporting generator, drain fuel and close fuel shutoff valve. ■ A hot muffler can ignite flammable materials. Keep area around muffler free of debris such as leaves, paper, and cartons. ■ Remove all unnecessary grease and oil from generator surfaces. ■ Do not leave any flammable material on generator while it is running. CAUTION Risk of severe burn. Do not touch the engine, exhaust pipes, or any engine component until cool.
Voltmaster Engine-Driven Generators 8 ■ NEVER operate this equipment under the influence or drugs or alcohol. ■ When fueling electric-start engines, do not touch battery cables or posts to a gasoline supply can. ■ Before operating, know the location of the nearest fire extinguisher, first aid kit, and emergency telephone. ■ Keep a fire extinguisher nearby and know its proper use. Extinguishers rated ABC by the NFPA are appropriate for all applications.
Voltmaster Engine-Driven Generators 2.2 Engine safety 2.2.1 Operator safety Before using the generator, refer to engine manufacturer’s documentation for additional engine safety and operating information. 2.2.2 California Proposition 65 WARNING Health hazard. Engine exhaust and some of its constituents are known to the State of California to cause cancer, birth defects, and other reproductive harm. 2.2.
Voltmaster Engine-Driven Generators 2.3 Maintenance and storage safety DANGER Explosion hazard. Do not use gasoline, other fuels, or flammable solvents to clean parts. DANGER Corrosive material. Battery acid will cause severe burns and blindness. ■ Use extreme care when handling or servicing batteries. ■ Never service batteries while generator is operating. ■ Wear appropriate eye and hand protection. ■ Upon contact with skin or eyes, immediately flush with water and seek medical help.
Voltmaster Engine-Driven Generators ■ Before servicing, ensure power cannot be started inadvertently during service. ■ ALWAYS keep the generator in proper running condition. ■ ALWAYS fix damage to the generator immediately. Repair or replace broken or worn parts. Only use parts from original manufacturer. ■ Replace operation and safety decals when they become difficult to read. ■ When not in use, store equipment in a clean, dry location out of the reach of children. ■ Before storing, drain fuel.
Voltmaster Engine-Driven Generators 12 Owner’s Manual
Voltmaster Engine-Driven Generators 3 Operation 3.1 Before starting 3.1.1 Safety Before operating the Voltmaster generator: ■ Read and be familiar with this instruction manual. ■ Read and follow all safety instructions (see Section 2, page 5). ■ Read and follow instructions in the engine manufacturer’s documentation. 3.1.2 Fuel ■ For gasoline-powered models, use unleaded gasoline, 87 octane or higher ■ For diesel-powered models: ❑ In normal ambient temperatures, use diesel fuel No.
Voltmaster Engine-Driven Generators 3.1.3 Oil To avoid engine damage, always check oil level and refill oil if necessary before starting engine: ■ Crankcase pressure can blow hot engine oil out the fill tube, causing severe burns. Always stop the engine before removing the oil cap, and remove the cap with caution. ■ Fill the oil sump to the full mark on the dipstick. Check oil level while filling and DO NOT overfill. If accidentally overfilled, drain extra oil.
Voltmaster Engine-Driven Generators 3.1.4 Battery for electric-start models For electric-start models the starter battery is user-supplied. Battery cables and a battery tray are installed on the generator at the factory. DANGER Explosion hazard. When connecting battery cables, first connect the positive (red) cable and then connect the negative (green) cable. Use only a 12-volt DC battery. Other battery requirements are listed in Table 3-2. Table 3-2. Battery type 3.1.
Voltmaster Engine-Driven Generators 3.1.6 LN-Series (propane/natural gas) models LN-Series generators feature a special vapor fuel carburetor with a vacuum safety shutdown and an electric solenoid fuel shutdown. LN-Series generators are derated, because the liquid propane (LP) and natural gas (NG) fuel reduces engine output slightly versus gasoline. Safety ■ Only a qualified LP or NG installer should work with LP and NG fuel lines, connections, and components.
Voltmaster Engine-Driven Generators Fuel line The incoming fuel line should be a 1-inch line. Fuel connections on the generator are 3/4-inch NPT. To protect the flexible fuel line against rupture, route the fuel line away from the engine muffler and manifold. Do not remove the cover from the solenoid valve until you are ready to make pipe connections. Before the flexible fuel connection is connected to the hard fuel pipe connections, and after all other fuel line connections have been made: 1.
Voltmaster Engine-Driven Generators 3.1.7 Standby installations Safety concerns WARNING Shock hazard. Failure to isolate generator from power utility can result in death or serious injury. When using the generator for backup power: ■ Never connect the generator output to any live home or commercial electric circuits. ■ Use a suitable power-transfer device to isolate the generator from the power utility. ■ Use a licensed electrician or electrical contractor to install the power-transfer device.
Voltmaster Engine-Driven Generators Emergency circuit isolation To address the possibility of overloading the generator, the building may be wired so emergency circuits are grouped together, rewired to a separate junction box, and connected to the generator through a manual transfer switch. The emergency circuit should be configured so it does not exceed the ampere rating of the generator. The transfer switch must have an ampere rating equal to that of the emergency circuit.
Voltmaster Engine-Driven Generators 3.1.8 Preparing for use 1. Ensure the generator is in proper working order: ■ Check the generator for damage and wear. ■ Secure all fuel and wiring connections. ■ Tighten loose screws, nuts, and bolts. ■ If applicable, ensure the starter battery is fully charged (see Section 3.3.3, page 29). If a trickle charger was used when the generator was not in use, disconnect the charger. 2. Read tags and labels, and follow all directions.
Voltmaster Engine-Driven Generators 3.2 Operating the generator 3.2.1 Models LR50EL and LR60EL Model LR50EL and LR60EL generators feature electric-start engines with auxiliary recoil starters. To start the engine on these models if a battery is not available, move the red or black lever near the fuel pump to the up position. If a 12-volt battery is installed, the lever must be in the down position at all times. 3.2.
Voltmaster Engine-Driven Generators 3.2.3 Air in fuel line For diesel models, air pockets in the fuel line will cause difficulty in starting and operating the generator. ■ Before starting, pump the fuel lever 20 times or more. ■ Do not allow the generator to run out of fuel or to the bottom of the fuel tank. 3.2.4 Electrical loads Ratings Complete ratings for the generator are listed on the generator serial number tag, which is attached to the generator housing.
Voltmaster Engine-Driven Generators D-Series diesel models CAUTION Operating a diesel generator without the proper load will permanently damage the engine. Always operate the diesel engine under load, using at least 25% of its rated capacity. Diesel models require a load of at least 25% of the generator’s rated output. Operating a diesel generator with insufficient load (referred to as “wet stacking”) will irreparably damage the engine and void the warranty.
Voltmaster Engine-Driven Generators Plugs and connected equipment Use only 3-prong grounded plugs, 3-wire extension cords, and 3-wire or double-insulated power tools with the generator. Full-power switch Some models are equipped with a switch that allows selection of 120-volt power only or both 120- and 240-volt power. ■ ■ ■ When using the generator to power only 120-volt equipment, put the full-power switch in the 120V position.
Voltmaster Engine-Driven Generators 3.2.5 First-time use Break-in period Controlled break-in helps to ensure satisfactory service from the generator. D-Series diesel models During the first 5 to 10 hours of operation, operate the generator with electrical loads from 25 to 50 percent of the generator’s rated capacity (indicated on the generator serial number tag). This will ensure the valves are properly seated. After the first 10 hours of operation, change the oil and oil filter.
Voltmaster Engine-Driven Generators Figure 3-2. Fuel mixture adjustment screw Fuel mixture adjustment screw Fuel mixture nut 3.2.6 Starting the generator CAUTION Load on generator at startup or shutdown can damage equipment. Remove all electric loads from the generator before starting or stopping the engine. 26 1. Before operating the generator, follow all instructions in Section 3.1 and Section 3.1.9. 2. Start the generator: a. Disconnect all loads. b.
Voltmaster Engine-Driven Generators 3. 3.2.7 e. Start the engine using the electric starter or recoil cord, referring to engine manufacturer’s instructions if necessary. f. When the engine starts, close the choke. g. For SG-Series models, ensure the green light is lit on the ground-fault sensing module on the control panel. Apply loads: a. Before connecting any load to the generator, run the engine for 2 to 3 minutes, allowing it to reach normal operating temperature. b.
Voltmaster Engine-Driven Generators 3.3 General maintenance The generator should be run at least once a month for a few minutes to keep all components in proper operating condition. For engine maintenance requirements, see the engine manual. For troubleshooting, see the Voltmaster troubleshooting manual, available at www.voltmaster.com. 3.3.1 Storage Store the generator in a warm, dry location. If the generator is used infrequently, the engine could become difficult to start.
Voltmaster Engine-Driven Generators 3.3.3 Changing the oil Change the engine oil as specified in the engine manual. Oil should be drained while the engine is slightly warm. 3.3.4 Battery For generator models that have a battery, regular maintenance is necessary for the battery to function properly and for long battery life. Safety DANGER Explosive gases can cause blindness and severe injury. When working on or near batteries: ■ Wear eye protection. ■ Prevent sparks and open flames.
Voltmaster Engine-Driven Generators ■ Even when batteries are not in operation, self-discharge generates hydrogen gas that can explode. Always store and work on batteries in a well ventilated area. ■ Always wear proper eye, face, and hand protection when working on or near batteries. Battery acid will cause severe eye damage and skin burns. If contact with battery acid occurs, immediately flush with water and seek medical help.
Voltmaster Engine-Driven Generators ■ Charge the battery and keep it fully charged if any of the following conditions exist: ❑ If the generator will be run infrequently ❑ If the battery will be stored for a long period of time ❑ If the battery will be located in an unheated room Cleaning ■ Observe battery safety precautions (see “Safety” on page 29). ■ Keep batteries clean and dry, avoiding accumulation of dust, dirt, grime, and moisture.
Voltmaster Engine-Driven Generators 32 Owner’s Manual
Voltmaster Engine-Driven Generators Appendix A Power requirements The information provided in this appendix is for reference only. Values presented here are not necessarily representative of all such equipment. A.1 Sizing the generator In most applications, the generator will provide power to devices that use a total wattage rating up to the rated wattage output of the generator.
Voltmaster Engine-Driven Generators Table A-1 Approximate current requirements for electric motors Horsepower Running watts Universal motor* Starting watts Induction Capacitor motor motor Split-phase motor 1/6 275 400 600 850 1200 1/4 400 500 850 1050 1700 1/3 450 600 950 1350 1950 1/2 600 750 1300 1800 2600 3/4 850 1000 1900 2600 — 1 1000 1250 2300 3000 — 1 1/2 1600 1750 3200 4200 — 2 2000 2350 3900 5100 — 3 3000 — 5200 6800 — 5 4800 — 7500 980
Voltmaster Engine-Driven Generators Table A-2 Minimum extension cord gauge Amps 2 3 4 5 6 8 10 12 14 16 18 20 22 25 30 35 40 50 60 Continuous load Watts Minimum gauge @ 120 volts @ 240 volts 0–50 foot length 50–100 foot length 100–150 foot length 240 360 480 600 720 960 1200 1440 1680 1920 2160 2400 2640 3000 3600 4200 4800 6000 7200 480 720 960 1200 1440 1920 2400 2880 3360 3840 4320 4800 5280 6000 7200 8400 9600 12,000 14,400 22 22 20 18 18 16 16 16 14 14 14 12 12 12 10 10 8 6 4 20 18 16 16 1
Voltmaster Engine-Driven Generators Table A-3 Approximate equipment power requirements* Household and RV equipment Central air conditioner 10,000 BTU Clothes dryer, electric Clothes dryer, gas Running watts Starting watts 1500 2200 5200 5750 700 1800 Clothes washing machine 1150 2300 Coffee maker 1750 — Computer, desktop 600–800 Computer, laptop 200–250 — — Computer monitor 200–250 — Computer printer 400–600 — Dishwasher, cool dry 700 1400 Dishwasher, hot dry 1450 1400 Fry
Voltmaster Engine-Driven Generators Table A-3 Approximate equipment power requirements* (continued) Contractor equipment Running watts Air compressor (see Table A-1) 1/2 HP 975 Starting watts 1600 1 HP 1600 4500 1 1/2 HP 2200 6000 7700 2 HP 2800 Bench grinder 8 inch 1400 2500 Circular saw 6 inch 950 2200 7 1/4 inch 1200 2600 8 1/2 inch 1500 3000 10 inch 2000 3900 1/4 inch 300 400 3/8 inch 475 650 Drill Impact wrench 1/2 inch 750 900 1 inch 1000 1250 1/2 inch 60
Voltmaster Engine-Driven Generators Table A-3 Approximate equipment power requirements* (continued) Farm equipment Running watts Battery charger 4 amp 90 15 amp 380 Starting watts — — 60 amp with 240-amp boost 1500/5750 — 100 amp with 300-amp boost 2400/7800 — Electric fence 25 mile 250 Grain cleaner 1/4 HP 650 1000 Grain conveyor, portable 1/2 HP 1000 2400 50,000 BTU 400 675 100,000 BTU 500 1260 625 1875 Heater, portable liquid-fuel type 150,000 BTU — Heater, portable r
WANCO INC. 5870 Tennyson Street Arvada, Colorado 80003 800-972-0755 303-427-5700 303-427-5725 fax www.voltmaster.com ©2011 Wanco Inc. All rights reserved. Printed in the USA. | 205994 Rev.