Technical data

TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
ESFR PRE-PRIMED SINGLE
INTERLOCK PREACTION
COLD STORAGE SYSTEM
Page 51
March 7, 2008
Table 12 - Input
Descriptions
Input Description
1 “Man” position of Hand-
Off- Auto Switch
2 “Auto” position of Hand-
Off- Auto Switch
3 Pressure Switch of
Pumping Unit
4 Tank Level Switch
5 System 1 Inputs
6 System 2 Inputs
7 System 3 Inputs
8 System 4 Inputs
9 System 5 Inputs
10 System 6 Inputs
11 Switch A – Down Position
12 Switch A – Up Position
13 Switch B – Down Position
14 Switch B – Up Position
Table 13 - Output Descriptions
Output Description Control Logic
1 “Power On” light Output 1 on when: Input 1 or Input 2 are on.
2 Pump Motor
Starter Coil and
“Pump” light
Output 2 on when:
(Manual Mode System and Tank Filling) Input 1 on + Input 3 on. OR
(Automatic Mode) Input 2 on + Input 3 on + Input 4 on and Internal Timer times
to 10 minutes. The timer begins when Manual or Automatic mode is started and is
reset when pump turns off in Automatic Mode.
3 System 1
Solenoid Valve
Output 3 on when:
(Manual Mode) Input 1 on and Input 5 on and Input 12 on and Input 13 off and Input
14 off. OR
(Automatic Mode) Input 2 on and Input 5 on.
4 System 2
Solenoid Valve
Output 4 on when:
(Manual Mode) Input 1 on and Input 6 on and Input 11 on and Input 13 off and Input
14 off. OR
(Automatic Mode) Input 2 on and Input 6 on.
5 System 3
Solenoid Valve
Output 5 on when:
(Manual Mode) Input 1 on and Input 7 on and Input 11 off and Input 12 off and Input
14 on. OR
(Automatic Mode) Input 2 on and Input 7 on.
6 System 4
Solenoid Valve
Output 6 on when:
(Manual Mode) Input 1 on and Input 8 on and Input 11 off and Input 12 off and Input
13 on. OR
(Automatic Mode) Input 2 on and Input 8 on.
7 System 5
Solenoid Valve
Output 7 on when:
(Manual Mode) Input 1 on and Input 9 on and Input 12 on and Input 14 on. OR
(Automatic Mode) Input 2 on and Input 9 on.
8 System 6
Solenoid Valve
Output 8 on when:
(Manual Mode) Input 1 on and Input 10 on and Input 11 on and Input 13 on. OR
(Automatic Mode) Input 2 on and Input 10 on.
9 Level Switch
Relay Coil
Output 9 on when: Input 4 on.
Follow the steps below:
Turn off and isolate the electrical supply to the unit.
Close the liquid supply valve and Tank Fill isolation valves.
If not already connected to fill the storage tank, connect the antifreeze supply container
to the liquid supply valve. A flexible hose may be used, but must not restrict the flow from
the supply container to the valve. An additional isolation valve must be installed in the
line between the supply container and unit’s liquid supply valve. A slight downward slope
from the supply container to the unit’s valve connection is required to prime the pump and
maintain positive head on pump inlet. Always use a backup wrench when making piping
connections to avoid damage to the unit’s piping.
Open the shut-off valve on the supply container and liquid supply valve on the CS-1.
Open high-point vent/bleed valves on the system.
Select system to be filled using switches “A” and “B”. Use Table 14 or the table on the
CS-1 Panel to determine switch “A” and “B” position.
With the CS-1’s “OFF-ON” switch in the “OFF” position, turn on the power supply to the
unit.
Switch the “Man-O-AUTO” switch on the unit control panel to “Man”. Turn the “Off-On”
switch to “ON”. Liquid will begin to fill the selected system.
As the system fills, monitor the system vent/bleed valves. Close each valve when liquid
leaks from it.
When the liquid leaks from the uppermost vent/bleed valve, close the vent valve. The
system pressure switch will close that system’s solenoid valve when set pressure is
established. The pump pressure switch will turn the pump off when set pressure is es-
tablished.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.