Table of Contents Table of Contents 1 2 IM-PP 724607 0320 ProPress About this Document_______________________________________ 6 1.1 Disclaimer_ ____________________________________________ 6 1.2 Symbols Used__________________________________________ 6 Product Information ________________________________________ 7 2.1 ProPress Systems_______________________________________ 7 2.2 Safety_________________________________________________ 7 2.2.1 Drinking Water Installation_________________________ 7 2.
Table of Contents Table of Contents, continued 3 4 5 4 of 44 Handling Instructions______________________________________ 19 3.1 Transport_____________________________________________ 19 3.2 Storage_______________________________________________ 19 Installation Instructions____________________________________ 20 4.1 Check System Components_____________________________ 20 4.1.1 Changing the Sealing Element____________________ 20 4.1.1.1 ½" to 2" Fittings________________________ 20 4.1.1.
Table of Contents List of Tables Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Table 7 Table 8 Table 9 Table 10 Table 11 Table 12 Table 13 Table 14 Table 15 Table 16 Table 17 Table 18 Table 19 Table 20 Table 21 Table 22 IM-PP 724607 0320 ProPress ProPress approved applications___________________________ 8 Minimum distance between press fittings__________________ 24 ProPress standard jaws clearance requirements____________ 25 ProPress standard jaws clearance requirements between tube, wall, and floor__
About this Document 1 About this Document 1.1 Disclaimer Viega products are designed to be installed by licensed and trained plumbing and mechanical professionals who are familiar with Viega products and their installation. Installation by non-professionals may void Viega LLC’s warranty. This document is subject to updates. For the most current Viega technical literature please visit www.viega.us. ProPress 2½" to 4" formerly ProPress XL-C. 1.
Product Information 2 Product Information 2.1 ProPress Systems Viega ProPress systems are state-of-the-art press fitting systems that provide economical and reliable installations for the commercial, industrial, and residential markets. Viega ProPress are copper and Zero Lead bronze fittings and valves in copper tube size (CTS) ranging from ½ inch to 4 inches. The fittings require no soldering or brazing and are installed with electro-hydraulic press tools (battery-powered or corded press tools).
Product Information 2.
Product Information 2.3.1 Commercial and Residential ProPress systems are approved for numerous applications in commercial and residential markets including potable water. “Zero Lead” identifies products meeting the lead-free requirements of NSF 61 through testing under NSF/ANSI 372 (0.25% or less maximum weighted average lead content). 2.3.2 Industrial and Plant Operations ProPress systems are also suitable for use in industrial and plant processes.
Product Information 2.4.2 Listings and Certifications The fittings have the following listings and certifications: ■ ABS: American Bureau of Shipping Type Approval ■ ASME B16.51: Copper and Copper Alloy Press-Connect Pressure Fittings ■ ASME B31.1: Power Piping ■ ASME B31.3: Process Piping ■ ASME B31.9: Building Service Piping ■ BV: Bureau Veritas Type Approval ■ Canadian Registration Number (CRN): 0A14541.
Product Information 2.4.4 Copper Tubing Copper tubing must be free of surface imperfections, including metal stamped print lines, before a ProPress fitting is installed. Viega ProPress may only be pressed onto copper tube in accordance with ASTM B88 or B75. When pressing onto B88 copper tube, types K, L, and M may be used. Tempers O60 and O50, known as “soft copper”, are limited to nominal sizes ½" to 1 ¼". Temper H58, known as hard copper, may be used with nominal sizes ½" to 4".
Product Information 2.4.5.3 EPDM Sealing Element Viega ProPress fittings are manufactured with a high-quality, shiny black EPDM (Ethylene Propylene Diene Monomer) sealing element installed at the factory. The molded sealing lips also seal tube surfaces with slightly uneven surfaces. Sealing elements are inserted into the fitting using a H1 food grade lubricant registered with NSF and the USDA, and is approved for use under FDA 21 CFR.
Product Information 2.4.5.6 Cylindrical Guides All Viega fittings are designed with cylindrical guides to keep the tube straight and protect the sealing element during assembly. Fittings that do not have cylindrical guides risk making an unsecured connection. Without the guides, installers may damage the sealing element. Fittings are radially pressed around the sealing element in a single step. 2.4.5.
Product Information 2.4.5.8 Viega Smart Connect Technology 1 Identify an unpressed connection during pressure testing when water or air flows past the sealing element. 2 Upon identification, use the press tool to press the fitting, making a secure leakproof connection. Viega Smart Connect technology provides the installer quick and easy identification of an unpressed fitting during a leak test. When the fitting is pressed, a secure, non-detachable, mechanical connection is created.
Product Information 2.5.2 Expansion Thermal expansion in installed systems generates stress on tubing and appliance connectors. Compensation must be allowed for expansion and contraction that may occur within the tubing. Expansion joints or mechanical expansion compensators may be used to alleviate these stresses. ProPress systems do not require any additional protection as compared to a soldered system.
Product Information 2.5.5 Underground Installations Viega ProPress fitting systems with copper tubing are approved for underground installations. However, installations must meet all state and local codes, including those for underground. Proper authorization must be obtained prior to installation from the Authority Having Jurisdiction. 2.5.6 Concealed Spaces The Viega ProPress fitting system has been approved for use in concealed spaces.
Product Information 2.5.8 Pressure Surges ■ ProPress fittings should be isolated or separated by sufficient distance from pumps, fast-acting valves, and other sources of pressure transients. ■ The maximum operating pressure in a ProPress system is 200 psi, which applies to general operation as well as pressure transients. ■ Good engineering practices should be used to design the system in a way that minimizes sharp pressure surges.
Product Information 2.5.10.1 Controlling Deflection Deflection while pressing can be minimized by utilizing the following installation practices. Alternate Press Directions ▶ Press one end of fitting. ▶ Make second press on other end of fitting from the opposite side. Site conditions permitting. Push-Pull Method ▶ Rings = Push on press tool. ▶ Jaws = Pull on press tool. The press tool can be feathered using the trigger as needed to apply pulling or pushing force to control deflection.
Handling Instructions 3 Handling Instructions All Viega ProPress components and associated tubing shall be free from dirt, debris, or items that may interfere with the sealing element and the press connection. Viega ProPress sealing elements, separator rings, and grip rings are to be visually inspected prior to installation to ensure the seal is intact and properly located within the fitting. 3.
Installation Instructions 4 Installation Instructions 4.1 Check System Components System components may, in some cases, become damaged through transportation and storage. ■ Check all parts. ■ Replace damaged components. ■ Do not repair damaged components. ■ Contaminated components may not be installed. 4.1.1 Changing the Sealing Element Damage to the Sealing Element If damage to the sealing element, separator ring, or grip ring is discovered, contact a Viega District Manager for assistance.
Installation Instructions ▶ Insert new, undamaged sealing element into the bead. ▶ Check to make sure that the whole sealing element is in the bead. 4.1.1.2 2½" to 4" Fittings ▶ Insert o-ring pick between sealing element and separator ring. ▶ Use o-ring pick to push the sealing element into the fitting below the grip ring.
Installation Instructions ▶ Carefully reach past the grip ring, pinch and remove the sealing element from the fitting. WARNING! Grip ring is extremely sharp, use gloves or extreme caution when reaching into fitting. CAUTION! If reusing the sealing element ensure the sealing element does not make contact with grip ring as this can cause damage. ▶ Visually inspect replacement sealing element. Ensure there are no defects, scratches, or burrs, is free of debris, and is coated with lubricant.
Installation Instructions 4.2 Installing and Mounting the Tube Observe the general rules of hanging and mounting: ■ Fixed tubing should not be used as support for other tubing and components. ■ Do not use pipe hooks. ■ Observe distance between fittings and mounting points. ■ Observe the expansion direction – plan fixed and sliding mounts. 4.2.1 Pipe Hangers and Supports Tubing supports perform two functions: ■ To provide support for the tubing. ■ To guide the tube during thermal expansion and contraction.
Installation Instructions 4.3.1 Transition Fittings 4.3.1.1 Threaded Connections The Viega ProPress systems can be joined with off-the-shelf threaded fittings made of non-ferrous metals. In this regard: ■ The threaded connection is made first. ■ The press connection is made second. This process avoids unnecessary torsion on the press fitting. 4.3.1.2 Flange Connections When using Viega flanges, bolt the flange end in place prior to pressing the fitting to the tube. 4.3.
Installation Instructions Tube Diameter (inches) A minimum (inches) A minimum (mm) B minimum (inches) B minimum (mm) ½ ¾ 19 1⅝ 41 ¾ ⅞ 22 2⅛ 54 1 1 26 2½ 64 1¼ 1⅛ 29 2⅞ 73 1½ 1¾ 45 3½ 89 2 2 51 4⅜ 111 B A Table 3: ProPress standard jaws clearance requirements C 20° B A Tube Diameter (inches) A minimum (inches) A minimum (mm) B minimum (inches) B minimum (mm) C minimum (inches) C minimum (mm) ½ ⅞ 23 1⅜ 35 2½ 64 ¾ 1 26 1½ 38 2½ 64 1 1⅛ 29 1¾ 45
Installation Instructions 4.3.4 ProPress Rings Clearance Requirements Ensure that the space required for system pressing tools is available if Viega ProPress fittings will be installed immediately upstream or downstream from ceiling penetrations.
Installation Instructions Tube Diameter (inches) A minimum (inches) A minimum (mm) B minimum (inches) B minimum (mm) C minimum (inches) C minimum (mm) 1½ 2⅜ 60 5 127 2 3/16 56 2 2 9/16 121 3 9/16 65 65 4¾ Table 11: ProPress rings with V2 Actuator clearance requirements between tube, wall, and floor Tube Diameter (inches) A minimum (inches) A minimum (mm) ½ 1⅝ 41 ¾ 1¾ 45 1 2 51 1¼ 2 3/16 55 B minimum (inches) B minimum (mm) 3¼ C minimum (inches) C minimum (mm) 2 51
Installation Instructions 4.4 Soldering or Brazing 4.4.1 Using ProPress In Line with Existing Fittings ■ The minimum clearance requirement when pressing connections near an existing brazed connection is two tube diameters. ■ To ensure proper sealing of both the soldered and press connections, a minimum distance when pressing connections near an existing soldered fitting must be maintained. Refer to the table below.
Installation Instructions Tube Soldering Diameter minimum (inches) distance (inches) Soldering minimum distance (mm) Brazing minimum Brazing minimum distance (inches) distance (mm) ½ 1½ 38 4½ 114 ¾ 2¼ 57 6¾ 172 1 3 76 9 229 1¼ 3¾ 95 11¼ 286 1½ 4½ 114 13½ 343 2 6 153 18 457 2½ 7½ 191 22½ 572 3 9 229 27 686 4 12 305 36 915 Table 17: Minimum distance between existing ProPress fitting and soldered or brazed fitting The installer should take precautions to keep t
Installation Instructions 4.6 Cutting the Tube Damaged tube and/or sealing element Press fittings can form improper connections as the result of damaged tube and/or sealing elements. ■ Do not use flame cutters when cutting the tube. ■ Do not use grease or oils when cutting the tube. ▶ Cut the tube square using a displacement-type cutter or fine toothed saw. Note: Cut tubing a minimum of four inches away from the contact area of the vise to prevent possible damage to the tubing in the press area.
Installation Instructions 4.8 Pressing the Fitting WARNING! Read and understand all instructions for installing Viega ProPress fittings. Failure to follow all instructions may result in extensive property damage, serious injury, or death. 4.8.1 Viega ProPress ½" to 2" Installation For hard copper tubing in ½" to 2" and soft copper tubing in ½" to 1¼". ▶ Check the sealing element for correct fit: ■ The tube end is not bent or damaged. ■ The tube is deburred. ■ The correct sealing element is in the fitting.
Installation Instructions No-stop couplings and extended no-stop couplings are often used to conduct repairs. Without a stop, these couplings can slide completely onto a tube and allow a connection to be made in tighter spaces. Unlike fittings with an integrated stop that have a minimum insertion depth, nostop couplings have minimum and maximum allowable insertion depths. Both the minimum and the maximum insertion depths must be marked with a line connecting the two marks.
Installation Instructions ▶ Pull retaining pin out of press tool. ▶ Insert appropriate jaw. ▶ Push in retaining pin until it locks the jaw in place. ▶ Open the jaw and place at right angle on the fitting. ▶ Look at insertion depth mark on the tube to make sure that the tube is properly inserted into the fitting. ▶ Hold trigger on press tool until press jaws have fully engaged the fitting. Jaws will automatically release after a full press is made.
Installation Instructions 4.8.2 Viega ProPress 2½" to 4" Installation For hard copper tubing in 2½" to 4". WARNING! Read and understand all instructions for installing Viega ProPress 2½" to 4" fittings. Failure to follow all instructions may result in extensive property damage, serious injury, or death. Use only rings that are compatible with ProPress 2½" to 4" fittings. ■ Use of incompatible rings will result in an improper connection. ■ Do not mix actuators and rings from different manufacturers.
Installation Instructions ▶ Measure insertion depth (see table below). ▶ Mark the proper insertion depth on the outside of the tube. Improper insertion depth Improper insertion depth may result in an improper seal. ■ Be sure to mark the correct insertion depth on the tube before pressing the fitting.
Installation Instructions ▶ Open XL-C ring and place at right angles on the fitting. ▶ Ensure that the XL-C ring is engaged on the fitting bead. ▶ Open the V2 Actuator and connect the V2 Actuator to the XL-C ring. ▶ Look at insertion depth mark on the tube to make sure that the tube is properly inserted into the fitting. ▶ Hold the trigger until the Actuator has engaged the XL-C ring.
Installation Instructions 4.9 Pressure Testing Viega Smart Connect technology provides a quick and easy way for installers to identify connections that need to be pressed. Unpressed connections are located by pressurizing the system with air or water. Pressure test all installed tube in accordance with local codes. Smart Connect Testing ■ Testing for unpressed connections using Smart Connect is not a replacement for pressure testing requirements of local codes and standards.
Limited Warranty 5 Limited Warranty 5.
Limited Warranty warranty shall be the reimbursement for repair and/or replacement of the part. VIEGA SHALL NOT BE LIABLE FOR ANY CONSEQUENTIAL OR OTHER DAMAGE (FOR EXAMPLE, WATER OR PROPERTY OR MOLD REMEDIATION) UNDER ANY LEGAL THEORY AND WHETHER ASSERTED BY DIRECT ACTION, FOR CONTRIBUTION OR INDEMNITY OR OTHERWISE. THE ABOVE WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
Limited Warranty In the event of a leak or other failure in the Viega product covered by this warranty, it is the responsibility of the end user to take appropriate measures to diminish any damage, to include making timely repairs. Only if the warranty applies will Viega be responsible for the remedy under this warranty.
Limited Warranty 5.3 Limited Warranty for Viega Marine Applications Marine applications are defined as mobile structures used to navigate water or stationary structures in water.
Limited Warranty under this warranty shall be the reimbursement for reasonable charges for repair or replacement of the Viega Product itself. VIEGA SHALL NOT BE LIABLE FOR CONSEQUENTIAL OR OTHER DAMAGE (FOR EXAMPLE, ECONOMIC LOSS, WATER OR PROPERTY OR MOLD REMEDIATION) UNDER ANY LEGAL THEORY AND WHETHER ASSERTED BY DIRECT ACTION, FOR CONTRIBUTION OR INDEMNITY OR OTHERWISE.
Limited Warranty IM-PP 724607 0320 ProPress 43 of 44
Viega LLC 585 Interlocken Blvd. Broomfield, CO 80021 Phone (800) 976-9819 www.viega.us IM-PP 724607 0320 ProPress ©2020, Viega®, FostaPEX®, GeoFusion®, ManaBloc®, MegaPress®, ProPress®, SeaPress®, Smart Connect®, Climate Mat®, Climate Panel®, Climate Trak®, PureFlow®, XL®, XL-C®, Visign®, Visign for Style®, Visign for More®, Visign for Care®, Visign for Public®, Viega Eco Plus®, and Viega: Connected in quality® are trademarks of Viega Holding GmbH & Co. KG.