TEMPERATURE SETBACK DELAY - COOL
00-120 (20*) Select the time delay (in minutes) before the thermostat
will initiate the temperature setback and allow the room
temperature to raise to the setback temperature after the
room becomes unoccupied
This feature prevents initiating temperature setback
prematurely while the guest is still in the room but in an area
where occupancy cannot be detected by the occupancy sensor.
Setting the “Temperature Setback Delay - Cool” to “00”, disables
the setback in the cool mode. Set to “00” to disable EMS.
Thermostat Settings
MAXIMUM SETBACK TEMPERATURE
72-92 (78°F) Select the “Maximum Setback Temperature” in °F.
Setback temperature is calculated by measuring PTAC
unit’s ability to attain “Recovery Temperature - Cool” within
“Temperature Recovery Time”.
If recovery is disabled (“Temperature Recovery Time” is set to
“0”) or if setback temperatures have not yet been calculated,
the “Maximum Setback Temperature” value will be used as the
setback temperature for cooling.
If calculated setback temperature for air conditioning is higher
than “Maximum Setback Temperature”, then the “Maximum
Setback Temperature” will be used as setback temperature for
air conditioning.
This feature allows defining the maximum temperature in a
room when room is unoccupied and the thermostat is in the
setback mode.
Thermostat Settings