USER’S MANUAL Heat (Energy) Recovery Ventilator Vents Frigate HRV 120 S Vents Frigate ERV 120 S
Frigate HRV(ERV) 120 S CONTENT Introduction ............................................................................................... Application .................................................................................................. Delivery set .................................................................................................. Unit designation key ................................................................................ Technical data ............................
INTRODUCTION This user’s manual combines technical description, operation and service manual, technical data sheet and installation guidelines for the heat (energy) recovery ventilator Vents Frtigate HRV (ERV) 120 S, hereinafter referred to as the unit. APPLICATION The unit with heat (energy) recovery is designed to save thermal energy by means of heat and energy recovery and is one of the energy saving components used in the buildings and premises.
Frigate HRV(ERV) 120 S UNIT DESIGNATION KEY Frigate HRV(ERV) 120 S Mounting design modification S - suspended Air capacity [CFM] Unit type HRV - Heat Recovery Ventilator ERV - Energy Recovery Ventilator (enthalpy) TECHNICAL DATA The heat (energy) recovery ventilator is designed for indoor application with the ambient temperature ranging from +34 °F (1 °С) up to +122 °F (50 °С) and relative humidity up to 80%. Ingress Protection rating: IP44 for the unit motors.
Table 2 -22º F...140º F (-30...+60 º С ) Temperature [º С] Relative humidity [%] 80% Warranty service life is 2 years Service life Operating service life is 5 years 5" 4" 7" 1 1/2" 11/16" Vents Frigate HRV 120 S 10" 1/2" 5 1/16" 20 1/16" 23 1/8" 21" 24 7/8" 5 1/16" 10" 20 1/16" 1/2" 7" 5" 11/16" Vents Frigate ERV 120 S 21" 24 7/8" 23 1/8" Fig.
Frigate HRV(ERV) 120 S Do not! • Do not operate the unit beyond the specified temperature range or in an aggressive and explosive medium. • Do not connect clothes dryers or similar equipment to the ventilation system. • Do not operate the unit in the air and dust mixture environment. STRUCTURE AND OPERATING LOGIC The unit has the following operating logic (fig.
1. Supply fan with backward curved blades and maintenance-free motor with external rotor and integrated thermal protection. 2. Extract fan with backward curved blades and maintenance-free motor with external rotor and integrated thermal protection. 3. Plate cross flow heat recovery core (Vents Frigate ERV 120 S — paper heat recovery core, Vents Frigate HRV 120 S — aluminium heat recovery core). 4. G4 supply air filter. 5. G4 extract air filter. 6. Frost protection thermostat. 7. Control block. 8.
Frigate HRV(ERV) 120 S This installation example is applicable only for Vents Frigate ERV 120 S Fig. 4. Wall unit mounting CONDENSATE DRAINAGE The Vents Frigate HRV 120 S unit is equipped with a condensate drain hose for condensate drainage (fig. 5). Connect the drain hose (1), U-trap (3) and drain system (5) with metal, plastic or rubber pipes (2 and 4). The pipes must be sloped down at least by 3°.
Connection to power mains Cut power supply off before any operations with the unit. The unit shall be connected to power mains by a duly qualified electrician only. Rated values of the electrical parameters are shown on the rating plate. Any modifications of the internal connections are not allowed and will void the warranty. The unit is designed for connection to single-phase ac 120 V / 60 Hz power mains.
Frigate HRV(ERV) 120 S UNIT CONTROL The unit is controlled by a three-position speed switch that enables low-speed modes «Low» and «Med» as well as «Stand by» mode which enables total air quality control (fig. 7). Up to five external control devices may be connected to the terminals 2-11 that turn the unit to high-speed ventilation in case of activation of any of the control devices (fig. 6). Terminals for connection of the remote control panel Three-speed switch Fig. 7.
Fig. 8 Control panel SAS908 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. The control panel has the following buttons: On/off button; Not active; Fan speed control adjustment (auto/high/med/low); Not active; Not active; Not active; Heating power scale; Heating power value; Not active; Temperature measuring unit; Not active; Selected fan speed; Not active; Indoor temperature. To turn the unit on/off press the button (1).
Frigate HRV(ERV) 120 S Fig. 9. CO2 transmitter 3. Humidistat The humidistat (fig. 10) is used for indoor humidity control. If the indoor humidity exceeds the setpoint, the humidistat switches the ventilation to high-speed mode. The unit operates in highspeed mode until humidity drops to setpoint. Adjust the humidity setpoint if required. Check that the humidistat closes contact if indoor humidity exceeds the setpoint and breaks contact if the indoor humidity is below the setpoint.
4. Mechanical timer The remote mechanical timer (fig. 11) is designed for installation in pollutable areas. As the timer is activated the unit is switched to high-speed mode. You can connect up to 5 timers in the premise at 500 feet (152 m) distance to the unit. OFF 60 10 50 20 40 Fig. 11. Mechanical timer 5. Switch The switch (fig. 12) is designed for indoor installation in pollutable areas.
Frigate HRV(ERV) 120 S Connect all the above external controls in compliance with the wiring diagram in fig. 13. The terminals (2) and (11) are designed for connection up to five control devices. 30% 40% 20% 10% off OFF OFF 60 10 50 40 20 ON 1 2 6 9 10 Fig. 13.
SERVICING AND MAINTENANCE Servicing of the unit is required 3-4 times per year. Besides general cleaning, the following operations are required: 1. Filter maintenance (3-4 times per year) Dirty filters increase air resistance in the system and reduce supply air flow to the premises. Clean or replace the filters as often as required, but at least 3-4 times per year. Clean the filter with running water or a vacuum cleaner. After two cleaning replace the filter.
Frigate HRV(ERV) 120 S Troubleshooting Possible malfunctions and fault handling Problem Possible reasons Power supply is off. The fan(s) do(es) not start running. Thermal fuse is melted. The extract filter is clogged. Cold supply air. The heat recovery core is frozen. Too low set rotation speed. The filters, fans or heat recovery core are clogged. Low air capacity. The ventilation system is clogged or damaged. The impeller(s) is (are) clogged. Noise, vibration.
STORAGE AND TRANSPORTATION RULES Store the unit in the manufacturer’s original packing box in a ventilation premise with the temperature range from +14 °F (-10 °С) up to +104 °F (+40 °С) and relative humidity less than 60% (at +68 °F (+20 °С)). Vapors or particles which can cause corrosion or damage the insulation or connection tightness are not allowed in the stock. Use hoist equipment for loading and storage operations to prevent the unit falling or excessive oscillation.
Frigate HRV(ERV) 120 S ACCEPTANCE CERTIFICATE Acceptance certificate The heat (energy) recovery ventilator VENTS Frigate HRV(ERV) 120 S is recognized serviceable and compliant with the technical parameters.