2. Power supply cabling
As Power Supplies used are the Mean Well Enterprises Co., Ltd fanless HLG-185/480 series.
Ordering Code
Type
Specification
AC12009/4
Power supply v3-68/100 (HLG-185H-24TE10)
27V / 6.9A (185W) TE10 (US-JunctionBox)
AC12009/5
Power supply v3-68/100 (HLG-185H-24TE11)
27V / 6.9A (185W) TE11 (C14)
AC12011/4
Power supply v3-160/256 (HLG-480H-30TE10)
27V / 16A (432W) TE10 (US-JunctionBox)
AC12011/5
Power supply v3-160/256 (HLG-480H-30TE11)
27V / 16A (432W) TE11 (C14)
AC12035/0
Meanwell HEP-185-24A
27.0V / 6.9A
AC12033/0
Meanwell HEP-240-24A
25.6V / 9.4A
AC12034/0
Meanwell HEP-320-24A
26.0V / 12.3A
HLG-Series:
The 24 and 30 in the type number of the HLG power supplies indicate the normal output voltage, and are internally
adjusted to 27 V. The TE10 and TE11 in the type number indicate custom made power supplies. The input mains side
consists of either the C14 connector or a Junction Box.
The output consists either of 1 or 2 cables (HLG-480 series) The black and red cables of the 480 series shall be
connected to the Power Connection Box, so don’t connect everything to 1 cable. That way 1 cable will have a max
load of 8A.
One side marked with INPUT will always need to be connected to the main wall outlet (100-240VAC or 277 VAC).
HEP Series
The HEP series is an alternative power supply. They all have an C14 connector as input, so in the US, they can never
be used at a Fixed locker bank. Default these PSU’s are 24v, but these are adjusted to its maximum voltage.
Connecting the INPUT:
The side marked with INPUT shall be connected to the mains wall outlet (90-305 VAC 50-60 Hz).
The TE10 versions are provide with a JunctionBox and are for the USA & Canadian market, where the locker bank is
at a Fixed location, for example in a Wall. These TE10 Power supplies shall be installed by a qualified and
experienced technician.. An all-pole mains switch in accordance with UL62368-1 Annex L shall be incorporated in the
electrical installation of the building.
The TE11 and the HEP versions are provided with a C14 connector and are for all other cases, e.g. lockers put in
front of a wall or at the end of desks. Those lockers are also often replaced by customers.
TE10 - JunctionBox TE11 - C14
If the input is connected to a UPS, you can connect 1 large PSU or 2 small PSU to 1 UPS of 650VA.