Instructions / Assembly

BLUE = QUICK-GUIDE
to frequently asked questions
Programmable
Water Feeder for
Steam Boilers
120 VAC Operating Voltage
U.S. Patent No. 6,688,329; 7,093,611;
6,926,028
Model VXT-120
LIMITED MANUFACTURER’S WARRANTY
We warrant products manufactured by Hydrolevel Company to be free from defects
in material and workmanship for a period of two years from the date of manufac-
ture or one year from the date of installation, whichever occurs first. In the event
of any claim under this warranty or otherwise with respect to our products which
is made within such period, we will, at our option, repair or replace such products
or refund the purchase price paid to us by you for such products. In no event shall
Hydrolevel Company be liable for any other loss or damage, whether direct, indi-
rect, incidental or consequential. This warranty is your EXCLUSIVE remedy and
shall be IN PLACE OF any other warranty or guarantee, express or implied, includ-
ing, without limitation, any warranty of MERCHANTABILITY or fitness for a partic-
ular purpose. This warranty may not be assigned or transferred and any unautho-
rized transfer or assignment thereof shall be void and of no force or effect.
SPECIFICATIONS
MAX AMBIENT
TEMPERATURE: 100°F
FLOW RATE: 1 GPM
MAXIMUM FEED: 10 Gallons (2 Cycles)
ELECTRICAL: 120 VAC, 60 HZ
126 Bailey Road North Haven, CT 06473 Phone: (203) 776-0473 FAX: (203) 764-1711 www.hydrolevel.com
UNIVERSAL COMPATIBILITY page 2
PROGRAMMABLE FEED DELAY SETTINGS page 3
PROGRAMMABLE FEED AMOUNT SETTINGS page 3
FEED COUNTER page 4
UNDERFEED PROTECTION page 4
LOCKOUT FLOOD PROTECTION page 4
INSTALLATION
WARNING To
prevent electri-
cal shock or
equipment dam-
age, power must
be off during
installation or
servicing of the
control. To prevent serious burns, the boiler
should be thoroughly cooled before
installing or servicing control. Only qualified
personnel may install or service the control
in accordance with local codes and ordi-
nances. Read instructions completely before
proceeding.
Step 1 Warning Step 2 Plumbing
The feeder can be mounted on a horizontal or vertical cold water
supply line. It must be installed with a manual by-pass valve and
unions (as shown above) for future serviceability. Arrows on the
valve indicate direction of water flow. Do not install feeder on hot
water supply.
IMPORTANT: It is important to prevent any contaminants from enter-
ing the feed valve during or any time after installation. The feeder
should be installed with non-ferrous plumbing materials only to pre-
vent rust from contaminating the valve. Apply pipe compound spar-
ingly. Remove and clean the feed valve strainer after the first feed
cycle to remove any contaminants that could have been introduced
during installation. See Service / Maintenance on page 4 for addition-
al information.