Specification

800-757-6996
48
AC CABLES
Armor & Jacket
Interlocked Galvanized Steel Strip (Green Striped)
Conductors
Solid Copper
Conductor Insulation
THHN
Conductor Insulation Covering
Moisture Resistant Fire Retardant Paper Wrap
Maximum Temperature Rating
90°C (Dry) Type ACTHH
Grounding
16 AWG Integral Bond Wire/Armor Combination per 250.118(8) and Green Insulated
Copper Grounding Conductor per 250.118(1)
Neutral Conductor
White 120/208V
Gray 277/480V
Maximum Voltage Rating
600V
References & Ratings
UL 4, 83, 1479, 1581, 2556, File Reference E7330
NEC
®
250.118(8), 300.22(C), 392, 320, 517.13, 518, 645
Federal Specification A-A-59544 (formerly J-C-30B)
Meets all applicable OSHA and HUD Requirements
Cable Tray Rated, install per NEC
®
UL Classified 1, 2, and 3 hour through (Fire) penetration product, R14141
Environmental Air-Handling Space Installation per NEC
®
300.22(C)
U.S. Patent No. 8,278,554 B2
Made in USA of US and/or imported materials
Type AC HCF-90® Steel Healthcare Facilities Cable
(120/208V Colors & 277/480V Colors) Technical Specifications
Product Code Stock Items
Trade Size
Grounding
Conductor AWG
Length (ft)
Approx. Weight/
1,000ft (lbs)
Approx. Armor O.D.
(in)
Coil Reel Coil Reel
120/208V Solid
1504G42-00 1504G60-00 12-2 Solid (Black, White) 12 Solid (Green) 250 1000 235 0.535
1505G42-00 1505G60-00 12-3 Solid (Black, Red, White) 12 Solid (Green) 250 1000 279 0.582
1506G42-00 1506G60-00 12-4 Solid (Black, Red, Blue, White 12 Solid (Green) 250 1000 320 0.621
1507G42-00 1507G60-00 10-2 Solid (Black, White) 10 Solid (Green) 250 1000 309 0.610
1508G42-00 1508G60-00 10-3 Solid (Black, Red, White) 10 Solid (Green) 250 1000 383 0.696
1509G42-00 1509G60-00 10-4 Solid (Black, Red, Blue, White) 10 Solid (Green) 250 1000 426 0.752
120/208V Specialty Colors
1504G42-04 1504G60-04 12-2 Solid (Red, White) 12 Solid (Green) 250 1000 235 0.535
1504G42-05 1504G60-05 12-2 Solid (Blue, White) 12 Solid (Green) 250 1000 235 0.535
277/480V Solid
1504G42-01 1504G60-01 12-2 Solid (Brown, Gray) 12 Solid (Green) 250 1000 235 0.535
1504G42-02 1504G60-02 12-2 Solid (Orange, Gray) 12 Solid (Green) 250 1000 235 0.535
1504G42-03 1504G60-03 12-2 Solid (Yellow, Gray) 12 Solid (Green) 250 1000 235 0.535
1505G42-01 1505G60-01 12-3 Solid (Brown, Orange, Gray) 12 Solid (Green) 250 1000 279 0.582
1506G42-01 1506G60-01 12-4 Solid (Brown, Orange, Yellow, Gray) 12 Solid (Green) 250 1000 320 0.621
1507G42-01 1507G60-01 10-2 Solid (Brown, Gray) 10 Solid (Green) 250 1000 300 0.545
1508G42-01 1508G60-01 10-3 Solid (Brown, Orange, Gray) 10 Solid (Green) 250 1000 309 0.610
1509G42-01 1509G60-01 10-4 Solid (Brown, Orange, Yellow, Gray) 10 Solid (Green) 250 1000 426 0.752
NOTE: All dimensions and weights are subject to normal manufacturing tolerances. Sizes 14 AWG, 8 AWG and larger are available by special order and subject to lead time and minimum quantities.
See page 61 for bond wire termination details.
Emergency circuits require special consideration in healthcare settings.
Review NEC® 517.30 (C)(3)(3) for guidance on the use of HCF cables on emergency circuits.
Green Insulated
Copper Ground
Nylon Thermoplastic
THHN Insulation
Interlocked Galvanized Steel Armor
(Color-Coded Green)
Bare Aluminum
Bonding Strip
Insulated Bushing
Paper Wrap on
Each Conductor
48
www.afcweb.com
AFC Cable Catalog

Summary of content (1 pages)