Split System Cooling Product Data XL15i 4TTX5018A-060A, 049E, 61E 1½ – 5 Tons PUB. NO.
Features and Benefits • Climatuff® compressor • Efficiency up to 16.0 SEER and 9.
Contents Features and Benefits 2 General Data 4 Model Nomenclature 6 Electrical Data 7 Product Specifications A-weighted Sound Power Level [dB(A)] Accessory Description and Usage AHRI Standard Capacity Rating Conditions 22-1817-10 4 4 5 5 Dimensions 10 Mechanical Specification Options 11 3
General Data Product Specifications Model No. 1 4TTX5018A1 4TTX5024A1 4TTX5030A1 4TTX5036A1 Electrical Data V/Ph/Hz 2 200/230/1/60 200/230/1/60 200/230/1/60 208/230/1/60 Min Cir Ampacity 8 11 15 22 Max Fuse Size (Amps) 15 20 25 35 Compressor CLIMATUFF® CLIMATUFF® CLIMATUFF® CLIMATUFF® - SCROLL No. Used - No Stages 1-1 1-1 1-1 1-1 RL Amps - LR Amps 6.2 - 38.6 8.6 - 57.8 11.1 - 63 16.7 - 79 Outdoor Fan FL Amps 0.74 0.74 0.74 0.93 Fan HP 1/8 1/8 1/8 1/5 Fan Dia (inches) 27.6 27.6 27.6 26.
General Data Product Specifications Model No. 1 4TTX5042A1 4TTX5048A1 4TTX5049E1 Electrical Data V/Ph/Hz 2 208/230/1/60 208/230/1/60 208/230/1/60 Min Cir Ampacity 26 28 28 Max Fuse Size (Amps) 45 50 45 Compressor CLIMATUFF® - SCROLL CLIMATUFF® - SCROLL CLIMATUFF® - SCROLL No. Used - No. Stages 1-1 1-1 1-1 RL Amps - LR Amps 19.9 - 109 21.8 - 117 19.9 - 109 Outdoor Fan FL Amps 0.93 0.93 2.8 Fan HP 1/5 1/5 1/3 Fan Dia (inches) 27.6 27.6 27.
General Data Accessory Description and Usage AHRI Standard Capacity Rating Conditions Anti-Short Cycle Timer — Solid state timing device that prevents compressor recycling until 5 minutes have elapsed after satisfying call or power interruptions. Use in area with questionable power delivery, commercial applications, long lineset, etc. AHRI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F WB air entering indoor coil, 95°F DB air entering outdoor coil.
Model Nomenclature Outdoor Units 4 T T X 5 0 3 6 A 1 0 0 0 A A G as F urnaces T Refrigerant Type 2 = R-22 4 = R-410A Furnace Configuration TU = Upflow/Horizontal TD = Downflow/Horizontal TRANE Type C = Condensing D = Induced Draft E = Electronic Ignition X = Direct Vent Condensing Y = Direct Vent Condensing Variable Speed Product Type W = Split Heat Pump T = Split Cooling Product Family Z = Leadership – Two Stage X = Leadership R = Replacement/Retail B = Basic A = Light Commercial Family SEER 0 = 1
Electrical Data Schematic Diagrams (SEE LEGEND) 4TTX5018A Printed from D156722P01 © 2010 Trane 8 22-1817-10
Electrical Data Schematic Diagrams (SEE LEGEND) 4TTX5024A Printed from D156722P01 22-1817-10 9
Electrical Data Schematic Diagrams (SEE LEGEND) 4TTX5030A Printed from D156722P01 10 22-1817-10
Electrical Data Schematic Diagrams (SEE LEGEND) 4TTX5036A Printed from D156910P01 22-1817-10 11
Electrical Data Schematic Diagrams 4TTX5042A Printed from D156552P01 12 22-1817-10
Electrical Data Schematic Diagrams 4TTX5048A Printed from D156578P01v 22-1817-10 13
Electrical Data Schematic Diagrams 4TTX5060A Printed from D156060P03 14 22-1817-10
Electrical Data Schematic Diagrams 4TTX5049E Printed from D156677P01 22-1817-10 15
Electrical Data Schematic Diagrams 4TTX5061E Printed from D156678P02 16 22-1817-10
Electrical Data Schematic Diagrams LEGEND 22-1817-10 17
Dimensions 4TTX5 Outline Drawing MODELS BASE FIG.
Mechanical Specification Options General The 4TTX5 is fully charged from the factory for up to 15 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit is certified to UL 1995. Exterior is designed for outdoor application. Condenser Coil The outdoor coil provides low airflow resistance and efficient heat transfer.
Literature Order Number 05/11 File Number Supersedes Stocking Location Trane A business of American Standard Companies www.trane.com Trane has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.