Power Supply User Manual

28
G8000 Series with Isolated Output Installation and Operation Manual
10.3 Anchor Bolts
Install the anchor bolts to secure the UPS on the oor. See Figure 10.2 for anchor bolt installation detail.
Use 12mm (1/2”) diameter anchor bolts. There are 16mm (5/8”) diameter holes provided in the UPS base.
See Figure 10.3 for the hole locations and dimensions for the specied UPS models.
FIGURE 10.2
ANCHOR BOLT INSTALLATION DETAIL
FIGURE 10.3
HOLE LOCATIONS/DIMENSIONS
ON BOTTOM OF UPS
100 kVA
Back
Front
4 X 1/2 in. Dia. (12 mm)
29 11/16 in. (754 mm)
21 11/16 in.
(551 mm)
150 kVA
46 1/16 in. (1170 mm)
21 11/16 in.
(551 mm)
Back
Front
4 X 1/2 in. Dia. (12 mm)
4 x 5/16 in. (16 mm)
diameter screw holes
4 screw holes
(Side View)
Anchor Bolt