Power Supply User Manual
28
G8000 Series with Isolated Output Installation and Operation Manual
10.3 Anchor Bolts
Install the anchor bolts to secure the UPS on the oor. See Figure 10.2 for anchor bolt installation detail.
Use 12mm (1/2”) diameter anchor bolts. There are 16mm (5/8”) diameter holes provided in the UPS base.
See Figure 10.3 for the hole locations and dimensions for the specied UPS models.
FIGURE 10.2
ANCHOR BOLT INSTALLATION DETAIL
FIGURE 10.3
HOLE LOCATIONS/DIMENSIONS
ON BOTTOM OF UPS
100 kVA
Back
Front
4 X 1/2 in. Dia. (12 mm)
29 11/16 in. (754 mm)
21 11/16 in.
(551 mm)
150 kVA
46 1/16 in. (1170 mm)
21 11/16 in.
(551 mm)
Back
Front
4 X 1/2 in. Dia. (12 mm)
4 x 5/16 in. (16 mm)
diameter screw holes
4 screw holes
(Side View)
Anchor Bolt