6. Extended parameters
Extended parameters are provided for sophisticated operation, fine adjustment and other special purposes. Modify pa-
rameter settings as required. See Section 11, Table of extended parameters.
6.1 Input/output parameters
6.1.1 Low-speed signal
: Low-speed signal output frequency
• Function
When the output frequency exceeds the setting of this parameter, an ON signal will be generated. This
signal can be used as an electromagnetic brake excitation/release signal.
★ Relay output (250Vac-2A (cos φ = 1), 30Vdc-1A, 250Vac -1A (cos φ = 0.4) at RY-RC or FLA-FLC-
FLB terminals (Default setting: RY-RC).
★ Open-collector output (24Vdc-50mA [maximum]) can also be set at OUT terminal.
[Parameter setting]
Title Function Adjustment range Default setting
Low-speed signal output frequency
0.0 ∼ (Hz)
0.0
Set frequency
Low-speed signal output
RY-RC terminals (Default setting)
P24-OUT terminals
FLA-FLC-FLB terminals
Low-speed signal output: Inverted
Time [sec]
Output frequency
[Hz]