Compact Inverter Instruction Manual

E6580757
F-1
6
6. Extended parameters
Extended parameters are provided for sophisticated operation, fine adjustment and other special purposes. Modify pa-
rameter settings as required. See Section 11, Table of extended parameters.
6.1 Input/output parameters
6.1.1 Low-speed signal
: Low-speed signal output frequency
Function
When the output frequency exceeds the setting of this parameter, an ON signal will be generated. This
signal can be used as an electromagnetic brake excitation/release signal.
Relay output (250Vac-2A (cos φ = 1), 30Vdc-1A, 250Vac -1A (cos φ = 0.4) at RY-RC or FLA-FLC-
FLB terminals (Default setting: RY-RC).
Open-collector output (24Vdc-50mA [maximum]) can also be set at OUT terminal.
[Parameter setting]
Title Function Adjustment range Default setting
Low-speed signal output frequency
0.0 (Hz)
0.0
Set frequency
Low-speed signal output
RY-RC terminals (Default setting)
P24-OUT terminals
FLA-FLC-FLB terminals
Low-speed signal output: Inverted
Time [sec]
Output frequency
[Hz]