Compact Inverter Instruction Manual

E6580757
E-10
5
[Example of how to adjustment the FM terminal frequency meter]
* Use the meter's adjustment screw to pre-adjust zero-point.
Key operated LED display Operation
-
Displays the operation frequency. (When standard monitor display selec-
tion is set to [operation frequency]
Press the MON key to display the first basic parameter (automatic
acceleration/deceleration) .
Press either the key or the key to select " ."
Press the ENTER key to display the operation frequency.
Press the key or the key to adjust the meter. The meter reading will
change at this time but be careful because there will be no change in the
inverter's digital LED (monitor) indication.
The adjustment is complete. and the frequency are displayed alter-
nately.
The display returns to its original indications (displaying the operation
frequency). (When standard monitor display selection
is set to [operation frequency].
Adjusting the meter in inverter stop state
If, when adjusting the meter for output current, there are large fluctuations in data during adjustment, making
adjustment difficult, the meter can be adjusted in inverter stop state.
When setting to for adjustment (100% fixed current), a signal of absolute values will be output
(inverter's rated current = 100%). In this state, adjust the meter with the
(Meter adjustment) parameter.
After meter adjustment is ended, set to (output current).
5.7 Standard default setting
: Default setting
Function
Allows setting of all parameters to the standard default setting, etc. at one time.
Title Function Adjustment range Default setting
Standard setting mode selection
0 2 : - (invalid)
3: Default setting
4: Trip clear
5: Cumulative operation time clear
6: Initialize inverter type information
0
[Hint]
It's easier to make the adjustment if
you push and hold for several seconds.