Compact Inverter Instruction Manual

E6580757
C-7
3
3.2.1 How to start and stop
(1) Start and stop using the operation panel keys ( )
Use the and keys on the operation panel to start and stop the motor.
RUN: Motor starts.
STOP: Motor stops (slowdown stop).
(2) Start and stop using external signals to the terminal board ( )
Use external signals to the inverter terminal board to start and stop the motor. (Set JP301 to sink logic)
Short F and CC terminals:
run forward
Open F
and CC terminals:
slow down and stop
* Coast stop
The standard default setting is for slowdown stop. To
make a coast stop, assign an ST terminal function to
an idle terminal using the programmable terminal
function. And set the :ST signal selection.
For coast stop, open the ST-CC when stopping the
motor in the state described at left. The monitor on
the inverter at this time will display .
3.2.2 How to set the frequency
(1) Setting the frequency using the potentiometer on the inverter main unit
(
)
Set the frequency with the notches on the potentiometer.
Move clockwise through the higher
notches for the higher frequencies.
Motor speed
Coast stop
ST-CC
F-CC
Frequency
F-CC
Slowdown stop
ON
OFF