2) Heating fan control
The outdoor fan is controlled by TE sensor, TO sensor and the operation frequency.
(From Min. W1 to Max. are controlled according to the following table.)
During 3 minutes after start-up, the fan is fixed
with the maximum fan tap corresponding to zone
in the following table.
After then the fan is controlled by temperature of
TE sensor.
If status, TE > 24°C continues for 5 minutes, the
operation stops.
This status is same to the usual Thermo-OFF
which has no alarm display, and the fan restarts
after 2 minutes and 30 seconds.
This intermittent operation is not abnormal.
When the above status
occurs frequently, it is
considered that the filter of suction part of the
indoor unit is stain.
Clean the filter and then restart the operation.
5. Coil heating control
1) This control function heats the compressor by turning on the stopped compressor instead of a case heater.
It purposes to prevent slackness of the refrigerant inside of the compressor.
2) As usual, turn on power of the compressor for the specified time before a test run after installation,
otherwise a trouble of the compressor may be caused.
As same as a test run, it is recommended to turn on power of the compressor beforehand when starting
operation after power of the compressor has been interrupted for a long time.
3) Coil heating is controlled by TD and TE sensor.
4) The power is turned off when TD is 30°C or more.