User Guide

No.
13
14
Item
Frequency fixed
operation (Test run)
Outline of specifications
<In case of wireless remote controller>
1) Push [ON/OFF]
button.
2) Using [SELECT]
MODE
button, set [COOL] or [HEAT] to
the operation mode to drive the air conditioner.
3) Set [HIGH
] to the fan speed.
4) To change the temperature setting, repeat it 6 times
to COOL and HEAT operations each.
COOL:
17°C 18°C
17°C 18°C 17°C
18°C 17°C 18°C
17°C (test run) ON/OFF
HEAT:
30°C 29°C
30°C 29°C 30°C
29°C 30°C 29°C
30°C (test run) ON/OFF
Change an operation setting within 3 seconds.
The error detection is performed as usual.
The frequency-fixed operation is performed.
5) To finish a test run, push [ON/OFF]
button.
Remarks
FILTER [ ] goes on.
Filter sign display
(Except wireless type)
It is provided on the
separately sold type
TCB-AX21
E2
1)
The operation time of the indoor fan is calculated, the
filter reset signal is sent to the remote controller when
the specified time (150H) has passed, and it is displayed
on LCD.
2) When the filter reset signal has been received from
the remote controller, time of the calculation timer is
cleared.
In this case, the measurement time is reset if the
specified time has passed, and display on LCD
disappears.
(No display)
[CENTER] goes on.
[CENTER] goes on.
In a case of wireless
type, the display lamp
does not change.
However, contents which
can be operated are same.
The status set in
[CENTER]/[Operation
Prohibited] mode is
notified with the
receiving sound
“Pi, Pi, Pi, Pi, Pi” (5 times).
1) Setting at the central controller side enables to select
the contents which can be operated on the remote
controller at indoor unit side.
2)
RBC-AMT32
E2
[Last push priority] :
The operation contents can be selected from both
remote controller and central controller of the indoor
unit side, and the operation is performed with the
contents selected at the last.
[Center] :
Start/Stop operation only can be handled on the
remote controller at indoor unit side.
[Operation Prohibited] :
It cannot be operated on the remote controller at
indoor unit side. (Stop status is held.)
Central control mode
selection
15
FILE NO. SVM-12004
TCB-AX32E2
34