User Guide

– 18 –
*
4 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
RAV-SM1103AT-E1
Pressure
Pipe surface temp.
Temp
*
Comp.
*
Comp.
(MPa) (kg/cm
2
G)
Pd Ps Pd Ps TD TS TC
TL
TE Hz Fan In Out
Cooling
Standard
3.44 0.92 35.1 9.4 82 8 10 56 39 47 HIGH
27/19
35/–
Overload 3.73 1.18 38.1 12.0 82 15 17 59 48 42 HIGH 32/24 43/–
Low load
1.49
0.70 15.2 7.1 39 8 3 23 22 30 LOW 18/15.5 –5/–
Heating
Standard
2.80
0.61
28.6 6.2 80 0 46 7 1 48 HIGH 20/– 7/6
Overload 3.43 1.08 35.0 11.0 82 14 55 12 13 24 LOW 30/– 24/18
Low load 2.20 0.25 22.4 2.6 76 -19 36 -16 -16 55 HIGH 15/–
–10/(70%)
3.52 0.85 35.9 8.7 87 8 9 57 39 54 HIGH 27/19 35/–
3.78
1.12
38.6
11.4
84 15 17 59 47 45 HIGH 32/24 43/–
1.51 0.71
15.4
7.2 40 7 3 23 23
30
LOW
18/15.5
–5/–
2.88
0.60
29.4
6.1
85
1
47
6
161
HIGH
20/–
7/6
3.41
1.08
34.8
11.0 81
14
54
13
13
24
LOW
30/–
24/18
2.35 0.24
24.0
2.4
80
-19
40
-16
-16 73 HIGH 15/–
–10/(70%)
RAV-SM1403AT-E1
Pressure
Pipe surface temp.
Temp
(MPa) (kg/cm
2
G)
Pd Ps Pd Ps TD TS TC
TL
TE Hz Fan In Out
Cooling
Standard
Overload
Low load
Heating
Standard
Overload
Low load