Installation and Operation Manual

24 G9000 Installation and Operation Manual
no sidecars used.
Rated Output kVA
80
100
160
225
300
500
750
Enclosure
NEMA 1
Audible Noise
70 dB @ 1 m
72 dB @ 1 m
73 dB @ 1 m
Listings/Standards
UL 1778; cUL; FCC Class A-Article 47 Part 15 B;
ISO 9001; ISO14001; ANSI C62.41 (IEEE 587 Cat. B)
UL 1778; cUL; IEC 62040-2 Cat. C3;
ISO 9001; ISO14001; ANSI C62.41 (IEEE 587 Cat. B)
Warranty
3 Years Parts and Labor
Emergency Power Off
Included
MONITORING
Dry Contacts Included
Yes, for Input and Output Signals
RS232 Port
Included
Intelligent Monitoring
(Optional)
SNMP; MODBus RTU; MODBus TCP; BACNET; METASYS
Display
LCD Touch Panel for Local Monitoring, Operation, and Control
TABLE 1.5.b Typical UPS Efficiencies at Various Loads
UNIT
% Full Load
20%
40%
60%
80%
100%
80 kVA
92.5%
94.3%
95.0%
95.2%
95.8%
100 kVA
92.5%
94.3%
95.0%
95.2%
95.8%
160 kVA
94.7%
95.7%
96.2%
96.5%
96.5%
225 kVA
94.9%
96.2%
96.5%
96.5%
96.5%
300 kVA
94.4%
96.3%
96.9%
97.0%
97.0%
500 kVA
94.8%
96.7%
97.0%
97.0%
97.0%
750 kVA
95.5%
96.6%
97.0%
97.0%
97.0%
TABLE 1.5.c MTBF and MTTR
Parameter
Phase I 80-225kVA
Phase II 300-750kVA
MTBF (Mean Time Between Failures): System (With Bypass)
Inverter (Without Bypass)
3,081,946 hr.
140,406 hr.
2,633,910 hr.
101,687 hr.
MTTR (Mean Time to Repair)Excluding Travel and Shipping Time)
4 hr.
1.5 hr.