Installation and Operation Manual

22 G9000 Installation and Operation Manual
TABLE 1.5.a Detail of Specifications
Rated Output kVA
80
100
160
225
300
500
750
Rated Output kW
72
90
144
202.5
300
500
750
AC INPUT
Configuration
3 phase, 3 wire
Voltage
480 V (+15% to -20%)
Frequency
60 Hz (+/-10%)
Power Factor
>.99 Lagging at 25% 115% Load
Input kVA
(Max Input kVA)
76 kVA
(86 kVA chg)
95 kVA
(107 kVA chg)
151 kVA
(170 kVA chg)
212 kVA
(238 kVA chg)
312 kVA
(336 kVA chg)
521 kVA
(560 kVA chg)
781 kVA
(840 kVA chg)
Walk-in Function
1 –30 Seconds (in 1 second increments)
Start-up Delay
1 –3600 seconds (selectable in 1 second increments)
Input Current
(Max Input Current)
91 A
(103 A)
114 A
(129 A)
181 A
(204 A)
255 A
(286 A)
376 A
(404 A)
626 A
(673 A)
939 A
(1010 A)
Input Current Limiter
~111% Full Load Input Current
~108% Full Load Input Current
Reflected Current THDi
3% max. at 60% 100% load (no input filter required); 6% max. at 25% 59% load.
No-Load Static Loss
1187 W
1187 W
1470 W
1646 W
2653 W
3905 W
5808 W
STATIC BYPASS INPUT
Configuration
3 phase, 3 wire
Voltage
480 V
±
10%
Frequency
60 Hz
±
5%
Bypass Overload
1000% for 1 cycle
500% for 1 cycle
BATTERY
Type
Lead Acid
Ride Through
Application Specific
Nominal Voltage
480 Vdc
Minimum Voltage
400 Vdc
Float Voltage
Up to 545 Vdc
DC Ripple Current
(w/o batteries)
9 Adc
9 Adc
11 Adc
18 Adc
19 Adc
32 Adc
48 Adc
DC Ripple Current (% of
Full Load DC Current)
4.7%
3.8%
2.9%
3.4%
2.7%
2.7%
2.7%
Max DC Charging Current
20 A
25 A
40 A
56 A
75 A
125 A
187 A
Max. Discharge Current
188 A
235 A
372 A
524 A
776 A
1292 A
1935 A