Installation and Operation Manual

46
G8000 Series Installation and Operation Manual
FIGURE 11.16 - GROUNDING CONFIGURATION WITH INPUT NEUTRAL GROUNDED
A 2 AWG (or 38 mm
2
) jumper cable is provided between the neutral terminal and ground bus in the UPS
cabinet. The qualied personnel should remove the jumper cable in this conguration. The jumper cable
location is illustrated below.