Installation and Operation Manual
66
G8000 Series Installation and Operation Manual
14.5 Stop
The procedure to stop the UPS is shown in Steps 1-3.
STEP 1
Transfer to Bypass supply as described in
Switch Power Supply.
UPS LED is “OFF”.
BYPASS LED is “ON”.
STEP 2
Turn off the DC Input Breaker (72B) on
the external battery cabinet, and, press
the G8000 “STOP” button for at least 0.5
seconds.
BATTERIES LED is “OFF”.
INVERTER LED ashes then “OFF”.
FLOAT CHARGE LED and CONVERTER
LED are “OFF”.
STEP 3
Wait until procedure is completed.
CONVERTER
INVERTER
UPS
AC OUTPUT
BATTERIES
BYPASS INPUT
DISCHARGE
EQUAL CHARGE
FLOAT CHARGE
BYPASS
AC INPUT
AC
SWITCH
BYPASS
AC - Vo 480 V
AC - Io 50%
PRESS ‘UPS’ SWITCH
CONVERTER
INVERTER
UPS
AC OUTPUT
BATTERIES
BYPASS INPUT
DISCHARGE
EQUAL CHARGE
FLOAT CHARGE
BYPASS
AC INPUT
AC
SWITCH
BYPASS
MOVE #72B TO ‘OFF’ POSITION
CONVERTER
INVERTER
UPS
AC OUTPUT
BATTERIES
BYPASS INPUT
DISCHARGE
EQUAL CHARGE
FLOAT CHARGE
BYPASS
AC INPUT
AC
SWITCH
BYPASS
PRESS ‘RUN’ SWITCH
LED Key
- LED Off
- LED On
- LED Flash