Adjustable Speed Drive Installation and Operation Manual
202 H9 ASD Installation and Operation Manual
Panel Frequency Lockout
Program ⇒ Special ⇒ Operation Panel Parameters
While operating using the LED Keypad Option this parameter Enables/
Disables the ability to change the frequency command value.
Settings:
0 — Unlocked
1 — Locked
Direct Access Number — F730
Parameter Type — Selection List
Factory Default — Unlocked
Changeable During Run — Ye s
Panel Emergency Off Lockout
Program ⇒ Special ⇒ Operation Panel Parameters
While operating using the LED Keypad Option this parameter Enables/
Disables the ability to provide an Emergency Off command.
Settings:
0 — Unlocked
1 — Locked
Direct Access Number — F734
Parameter Type — Selection List
Factory Default — Unlocked
Changeable During Run — No
Panel Reset Lockout
Program ⇒ Special ⇒ Operation Panel Parameters
While operating using the LED Keypad Option this parameter Enables/
Disables the ability to initiate a Reset.
Settings:
0 — Unlocked
1 — Locked
Direct Access Number — F735
Parameter Type — Selection List
Factory Default — Unlocked
Changeable During Run — Ye s
Command Mode/Frequency Mode Change Lockout
Program ⇒ Utilities ⇒ Prohibition
This parameter Enables/Disables the ability to change the CMOD/FMOD
settings.
Note: Command Mode is abbreviated as CMOD.
Note: Frequency Mode is abbreviated as FMOD.
Settings:
0 — Unlocked
1 — Locked
Direct Access Number — F736
Parameter Type — Selection List
Factory Default — Locked
Changeable During Run — Ye s
Lockout All Keys
Program ⇒ Utilities ⇒ Prohibition
This parameter Enables/Disables EOI keypad operation.
Settings:
0 — Unlocked
1 — Locked
Direct Access Number — F737
Parameter Type — Selection List
Factory Default — Unlocked
Changeable During Run — Ye s
F730 F737