Adjustable Speed Drive Installation and Operation Manual

H9 ASD Installation and Operation Manual 197
FM Bias Adjustment
Program Terminal Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the FM terminal.
Set the function of F005 to zero and then set this parameter to zero for proper
operation.
See F005 for more information on this setting.
Direct Access Number — F683
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Ye s
Minimum — -10.0
Maximum — +100.0
Units — %
AM Output Gradient Characteristic
Program Terminal Analog Output Terminals
This parameter sets the output response polarity of the AM output terminal.
The AM output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See F670 for more information on this setting.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number — F685
Parameter Type — Selection List
Factory Default Plus
Changeable During Run — Ye s
AM Bias Adjustment
Program Terminal Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the AM terminal.
Set the function set at F670 to zero and then set this parameter to zero for
proper operation.
See F670 for more information on this setting.
Direct Access Number — F686
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Ye s
Minimum — -10.0
Maximum — +100.0
Units — %
MON 1 Voltage/Current Output Switching
Program Terminal Analog Output Terminals
This parameter is used to set the output signal type of the MON1 output
terminal.
Settings
0 — -10V – +10V
1 — 0 – 10V
2 — 0 – 20 mA
Direct Access Number — F688
Parameter Type — Selection List
Factory Default 0 – 10V
Changeable During Run — Ye s
MON 1 Output Gradient Characteristic
Program Terminal Analog Output Terminals
This parameter sets the output response polarity of the MON1 output terminal.
The MON1 output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See parameter F672 for more information on this setting.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number — F689
Parameter Type — Selection List
Factory Default Plus
Changeable During Run — Ye s
F683 F689