User's Manual

Yingkou Tiancheng Fire Protection Equipment Co., LTD
1. Points for on-site installation
The wireless performance indicators of this product will vary according to the actual use environment. The
construction personnel should strictly follow the communication requirements of the wireless product and set
the working network segment of the wireless fire alarm system in accordance with the actual working
environment of the installation site.
VI. Test
Warning: Please make sure that the polarity of the battery is correct before proceeding.
1. The detector must be tested after installation or after each regular maintenance.
2. Simulated fire alarm: After successfully connecting to the network, choose a detector to make it meet the fire
alarm conditions artificially (please turn off the fire alarm linkage function to avoid unnecessary alarm linkage),
and verify whether the detector reports the fire alarm normally. After the test is over, pass The control panel
sends a communication command to reset the detector and informs the relevant management department to
restore the system to normal.
3. During the test, the unqualified detector shall be dealt with according to "general failure and repair" and
"maintenance", and then be tested. If it still fails to pass the test, it should be returned to the factory for repair.
VII. Use and Operation
1. Network segment setting: Before the detector connects to the network, you should first set the device
network segment. Select the network setting on the menu interface of the control panel . After entering the
network setting, first set the local address number, and then set the detector to the network according to the
actual situation on site Segments (29 options).
2. The device enters and exits the network: After the detector is powered on, press the "Indicators" button once,
the green light flashes once, the detector sends an online command to the control panel , and the control panel
displays the detector loop address number, indicating that the detector has successfully connected to the
network , Otherwise the detector is not connected to the network. The detector sends online commands for 3s,
during which other functions of the keys are disabled.
A) Network access operation: When the control panel is in the "wireless registration interface" and the
detector is not connected to the network, quickly press the "Indicators" button three times, the green light
flashes three times, the detector sends a network access application to the control panel , and the application is
successful After that, the total number of network access displayed by the control panel is +1, and the detector
sends a network access request for 3 seconds. During this period, other functions of the button are disabled.
B) Network exit operation: When the control panel is in the "wireless registration interface" and the detector is
in the network connection state, quickly press the "Indicators" button three times, the green light flashes three
times, and the detector sends an exit request to the control panel . After the application is successful, the total
number of logout displayed by the control panel is +1, and the detector sends a logout request for 3s. During
this period, other functions of the button are disabled.
3. Equipment alarm: When the temperature in the environment reaches or exceeds the alarm temperature set
by the detector, the red light of the detector will be on, and an alarm signal will be sent to the control panel
wirelessly. After the control panel responds to the alarm signal, the control panel will display a fire alarm. ,
The detector is in the state of waiting for the control panel to reset. After confirming that the fire alarm is
released, the control panel can send a signal to reset the detector.