Cut Sheet
Table Of Contents
- T&B Fitting
- Product Overview
- Rigid & Intermediate Metal Conduit Fittings
- Form 7, Form 8, Series 35, Conduit Outlet Bodies & Covers
- Mogul Conduit Outlet Bodies
- FS/FD Cast Device Boxes and Covers
- Conduit Outlet Boxes
- Conduit Outlet Elbows, Reducers, Plugs, and Adapters
- Three-Piece Couplings
- Sealing Fittings
- Kopr-Shield Compound
- Jacketed Metal Clad Cable Termination Fittings
- Tray Cable Fittings
- EMT Fittings
- Liquidtight Flexible Metal Conduit Fittings
- Shureflex™ Nylon Conduit System
- XTRA FLEX System
- Flexible Cord and Cable Fittings
- Flexible Cord and Cable Fittings - Non-Metallic
- Service Entrance Cable Fittings
- Metal Clad Cable, Armored Cable and FlexibleMetal Conduit Fittings
- Non-Metallic Sheathed Cable Fittings
- Conduit Dimensional Data
Liquidtight Flexible Metal Conduit Fittings
Series 5331GR
External Bonding Liquidtight Flexible Metal Conduit Connectors
Application
• Used where external bonding jumper
is required around liquidtight flexible
metal conduit
• To positively bond conduit to box
or enclosure
• Used where flexible raceway is
installed in outdoor or indoors
location where exposed to
continuous or intermittent moisture
Features
• Designed with provision to install
bonding jumper in several positions
• Designed to accept mechanical
or compression lug
• Ability to install quickly with low
torque effort
(1) Compressed metallic convolutions;
assures ground contact with low
impedance and high raceway
holding power (A)
(2) Single helical thread on ground cone
is easy to install without cross thread;
accepts variations in raceway diameters
and convolution pitch (B)
(3) Rolled over edge protects conductors (C)
• Sealing ring design has following
exclusive features:
(1) Grips and seals at leading and trailing
edge — will not abrade raceway
jacket (D)
(2) Provided with grooves on inside
diameter for anti-sleeving (E)
(3) Shoulders on both ends for extra
sealing (F)
(4) Symmetrical shape ensures
foolproof assembly
• Can be disconnected and reuse
• Watertight/oil tight installation at
box or enclosure termination is
ensured by:
(1) External taper thread hub on 5331GR
series and use of sealing gasket 5262
series (G)
(2) Taper tapped hole on 5271 series
• Suitable for use in Class I Division 2,
Class II Division 1 & 2 and Class III
Division 1 & 2 Hazardous Locations
per NEC Article 500
• Suitable as a bonding means per
UL 467 and NEC Article 351-9
• Conforms with JIC requirements
Standard Material
52/53GR Series
Lugs: High conductivity copper (for copper
conductor only)
Body, Gland, Locknut & Ground Cones: All steel or
malleable iron
Sealing Ring and Insulator: All thermoplastic
Sealing Gasket: Stainless Steel and Santoprene
Strap: Steel
52ALGR Series
Copper-free aluminum
Standard Finish
52/53GR Series
All Electro Zinc Plated and Chromate Coated
except lugs
Lugs: Bright Dipped
52ALGR Series
Zinc plating with clear chromate ground cones
Range
5331GR Series (straight connectors with male
hub):
3
⁄8" thru 6" conduit
5341GR Series (45°):
3
⁄8" thru 4" conduit
5351GR Series (90°):
3
⁄8" thru 4" conduit
5232ALGR Series:
3
⁄8" thru 1" conduit
All hubs provided with taper pipe threads (NPT)
Listings/Compliances
UL File #E-23018
CSA
UL 467
UL 514B
CSA C22.2 No. 18
CSA22.2 No. 41
NEMA FB-1
NFPA 70
JIC EGP1
JIC EMP1
Federal Specification A-A-50552
Federal Standard H-28 (threads)
1 per C.E. Code, this method is not permissible.
Sleeving
Raceway Jacket pulls off — exposing core and affecting
liquidtight termination. Feature (E) on sealing ring helps
overcome this problem.
A-115