In This Section… Rigid and Intermediate Metal Conduit Fittings...................A-4–A-34 Conduit Outlet Bodies .....................................................A-35–A-46 Mogul Conduit Outlet Bodies...........................................A-47–A-48 Aluminum Mogul Conduit Outlet Bodies..........................A-49–A-50 FS/FD Cast Device Boxes and Covers .............................A-51–A-54 FS/FD Aluminum Device Boxes and Covers.....................
Overview The Complete Product Line Since the turn of the century, Thomas & Betts has been a recognized leader in electrical fittings. Industry standards such as Chase® Nipples and Erickson® Couplings were introduced by Thomas & Betts and are still registered trademarks. This leadership continues. Here’s why... High-Performance Products Quality and performance result when engineering design skills are combined with the manufacturing technologies required to produce them.
Overview DURA-PLATE® Finish — Corrosion-Resistant Finish Protects Fittings in Harsh Environments DURA-PLATE® Corrosion-Resistant Fittings have a T&B plating process that provides excellent corrosion resistance on threaded steel and malleable iron fittings for use in harsh environments. DURA-PLATE® Corrosion-Resistant Fittings utilize an electro-plating process that ensures a uniform thickness of protective material over the entire part.
Rigid and Intermediate Metal Conduit Fittings Locknuts 140 Series 141AL Series 106 Series Application • To connect externally threaded conduit or connector to a threadless opening in a box or enclosure Standard Material 140 Series & 106 Series ⁄8" thru 2" steel (hardened) 21⁄2" thru 6" Malleable Iron All screws steel 3 • To effectively bond conduit or connector to box or enclosure Features • Hardened steel/malleable iron/copper-free aluminum construction 141AL Series • Tightens without deformation
Rigid and Intermediate Metal Conduit Fittings Available in your choice of steel/malleable iron, aluminum or stainless steel. Ensures positive bonding of conduit to box and prevents loosening due to vibration! Locknuts Bonding Locknuts A (B) Thickness (B) Thickness • Steel from 1⁄4" to 2", malleable iron from 21⁄2" to 6" • Aluminum 624 or Type 304 stainless steel all sizes CAT. NO. STL./M.I. ALUM. ST. STL. SIZE (IN.
Rigid and Intermediate Metal Conduit Fittings Perfect for grounding old work or new! Bonding & Grounding Wedges • Provides grounding without a jumper except in concentric knockouts • When jumper is required, it fits under set screw in grounding wedge • Update existing installations to meet code requirements for bonding (NEC Sect.
Rigid and Intermediate Metal Conduit Fittings Threaded Insulated Grounding Bushing Application • For quick installation of bonding jumper to multiple metal conduits (Rigid and IMC) • Designed to bush conductors and prevent insulation damage Features • Ease of installation, lay in lug design • Cast malleable iron body designed to lock insulator in place within body, reducing common assembly problem resulting in dislodging of insulator • Insulator rated for 150° C/302° F application • Look for the unique T&B
Rigid and Intermediate Metal Conduit Fittings Blackjack® — Grounding Bushing Innovative design makes installation quicker, easier. The Blackjack® Grounding Bushing never has to be threaded onto a conduit. It is simply placed in position on either a threaded or non-threaded rigid or IMC conduit, with the grounding lug in perfect position to accept the grounding wire — even in tight installations.
Rigid and Intermediate Metal Conduit Fittings Blackjack® — Grounding Bushing Mounting Screw Nylon Insulator (150º C) Lug Screw 14-4: Slotted 14-2/0: Slotted 6-4/0: Internal hex drive ØB Throat I.D. C E ØA D For Threaded and Threadless Rigid and IMC Conduit CAT. NO.
Rigid and Intermediate Metal Conduit Fittings Meets and surpasses NEC® requirements! Insulated Throat Fittings Locknut-type base improves bonding and resists loosening under vibration.
Rigid and Intermediate Metal Conduit Fittings For threadless rigid conduit and intermediate metal conduit.
Rigid and Intermediate Metal Conduit Fittings Knockout Bushing Application • To bush knockout openings in metal boxes or enclosures Listings/Compliances Features • One-piece construction designed to snap in place UL 514B UL (UL File No. E-3803) CSA (LR-589,LR-4484) CSA C22.2 No.
Rigid and Intermediate Metal Conduit Fittings Made from flame-retardant, non-dripping thermoplastic, UL rated 105° C! Knockout Plugs 1451 Series Application • To plug unused knockout openings in a box or enclosure Features • One-piece construction designed to snap in place 105° C rated by UL Made from flame retardant, non-dripping thermoplastic.
Rigid and Intermediate Metal Conduit Fittings Bush holes in metal boxes or enclosures! CHASE® Nipples CAT. NO. STL. OR M.I. 841TB 842TB 843TB 844 845 846 847 848 849 850 851 853 854 • 3⁄8" and 1⁄2" sizes in steel • 3⁄4" to 6" sizes in malleable iron DIMENSIONS (IN.) B ALUM.
Rigid and Intermediate Metal Conduit Fittings For Threaded Rigid Metal Conduit/IMC/PVC Coated Rigid Metal Conduit. Copper-Free Aluminum Threaded Hubs (Bullet® Hubs) Copper free aluminum castings for fittings have a maximum of 0.4% copper. The most detrimental effect of higher percentage of copper on aluminum base alloy is its decrease in corrosion resistance.
Rigid and Intermediate Metal Conduit Fittings UL Listed raintight and CSA Certified watertight and dusttight.
Rigid and Intermediate Metal Conduit Fittings T&B Hub A Never before has a single hub fit like this one. Designed for unequalled performance. The innovative engineering of the T&B® Hub will, quite simply, raise your performance expectations for threaded hubs. Look for the distinctive blue color to ensure the quality of a Thomas & Betts fitting. Sealing Ring and Groove with innovative profile outperforms standard O-ring design.
Rigid and Intermediate Metal Conduit Fittings T&B Grounding Hub A CAT. NO. TRADE SIZE DIA. ⁄2 3 ⁄4 1 11⁄4 11⁄2 2 21⁄2 3 31⁄2 4 5 6 17⁄16 17⁄16 2 23⁄8 23⁄4 31⁄4 33⁄4 43⁄8 5 51⁄2 67⁄8 711⁄16 H050GR-TB H075GR-TB H100GR-TB H125GR-TB H150GR-TB H200GR-TB H250GR-TB H300GR-TB H350GR-TB H400GR-TB H500GR-TB H600GR-TB 1 Material – Hub and Locknut: zinc or copper-free aluminum Insulating Throat: thermoplastic temp.
Rigid and Intermediate Metal Conduit Fittings Raintight for Rigid or Intermediate Metal Conduit (IMC) CHASE Threaded Conduit Hubs ® Applications • A fitting for connecting junction box to junction box, or junction box to the conduit system. The resulting connection maintaining ground continuity is raintight. • Suitable for use where the system is normally hosed down (NEMA 4) for cleaning. HT, HTZ Features • Plastic insulated throat, precision cast and machined surfaces permit safer wire pulling.
Rigid and Intermediate Metal Conduit Fittings CHASE® Hub with Insulated Throat CAT. NO. HUB SIZE STD. PKG. WT. LBS. APP. PER 100 HTZ1 HTZ2 HTZ3 HTZ4 HTZ5 HTZ6 HTZ7 HTZ8 HTZ9* HTZ10* ⁄2" ⁄4" 1" 11⁄4" 11⁄2" 2" 21⁄2" 3" 31⁄2" 4" 25 25 25 10 10 10 5 2 2 2 26 32 45 58 74 93 202 250 300 360 1 3 HTZ *Made to order item. Consult factory for lead time and minimum quantities. CHASE® Hub with Insulated Throat and Ground Screw CAT. NO. HUB SIZE STD. PKG. WT. LBS. APP.
Rigid and Intermediate Metal Conduit Fittings T&B Bulkhead Fittings CAT. NO. Bulkhead Fitting Across Flats Diameter Thru Bulkhead Fitting Thread Nipple Nut Not Included Thru Bulkhead Hub Height TRADE SIZE (IN.
Rigid and Intermediate Metal Conduit Fittings Offset Reducers C TRADE SIZE CAT. NO. B Height A H150-TB075ORGR 11⁄2"–3⁄4" H150-TB100ORGR 19⁄32"–1" H150-TB125ORGR 19⁄32"–11⁄4" H250-TB200ORGR 21⁄2"–2" Material — Dia. (Ø) HEIGHT DIA. (Ø) 121⁄32" 125⁄32" 125⁄32" 21⁄8" Offset Reducer and Locknut: Insulating Throat: 23⁄4 23⁄4 23⁄4 33⁄4 A DIA. B (IN.
Rigid and Intermediate Metal Conduit Fittings Watertight, flexible connections support movement and thermal expansion! XD Expansion/Deflection Coupling Use the T&B XD Expansion/Deflection Coupling to join two conduit runs in applications where movement in any direction is required. The coupling provides a flexible, watertight connection, accommodating axial or parallel movement of up to 3⁄4" and angular movement of up to 30° from normal.
Rigid and Intermediate Metal Conduit Fittings No disassembly required! XJG Conduit Expansion Coupling Suggested Specifications for Expansion Fittings for Rigid Steel or Intermediate Metal Conduit Where raceways require expansion fittings to compensate for thermal expansion and contraction and where expansion fittings and telescoping sections of metal raceway shall be made electrically continuous by bonding jumpers or other means: 8" Movement • The fitting will be constructed from malleable or ductile iron
Rigid and Intermediate Metal Conduit Fittings A B XJG24-EMT Features • Fast and easy installation — no disassembly required • No external grounding strap needed — internal bonding jumper is protected from tampering and the environment • Exceeds code requirements for long conduit runs to permit linear movement Standard Materials/Finish Body . . . . . . . . . . . . . . . . . . . . . . . . .Ductile Iron, available PVC Coated Internal Bonding Jumper . . . . . . . . . . .
Rigid and Intermediate Metal Conduit Fittings Split steel ring with diagonal serrations grips conduit and bites in for positive ground! Threadless Connectors — Nylon Insulated • Makes a permanent connection • Eliminates need for cutting a thread on conduit CAT. NO. • Insulation helps ensure continuity of service by protecting the conductor at the critical point — the connector bushing • Malleable iron construction • Look for the unique T&B blue color, ensuring the highest quality fitting NYLON INSUL.
Rigid and Intermediate Metal Conduit Fittings Set-Screw Connector/Coupling (For Threadless Rigid Metal Conduit and Intermediate Metal Conduit) Application • To connect and effectively bond threadless rigid metal conduit or intermediate metal conduit to a box or enclosure or to couple ends of threadless conduit 8124 Series 8125 Series • Coupling provided with positive center stop Standard Finish • Suitable for concrete-tight application Electro Zinc Plated & Chromate Coated Features • Thickwall steel
Rigid and Intermediate Metal Conduit Fittings Smoothly rounded shoulders protect conductor insulation! Bushed Elbows CAT. NO. SIZE A DIMENSION (IN.) B • Non-insulated 460-TB 461TB 462 463 ⁄2" 3 ⁄4" 1" 11⁄4" 11⁄8 11⁄2 113⁄16 21⁄4 113⁄16 21⁄4 211⁄16 31⁄8 • Malleable iron construction 1 Available with DURA-PLATE® Finish. UL File No. E 23018. C ⁄8 ⁄8 3 ⁄4 3 ⁄4 5 5 CSA File No.
Rigid and Intermediate Metal Conduit Fittings Threaded Erickson® 3-Piece Coupling (For Threaded Rigid Metal Conduit and Intermediate Metal Conduit) 674 Series 675AL Series Standard Material 674 Series Bushing & Case . . . . . . . . . . . Malleable Iron With an ERICKSON® coupling, a conduit run may be completed when neither conduit can be turned. A conduit run may also be broken without taking down the whole run.
Rigid and Intermediate Metal Conduit Fittings The ideal solution for applications requiring longer thread length! Panel Connector Extensions • Will combine with any fitting with a male thread • Male thread of panel connector extension is 1" long • Malleable iron construction CAT. NO. SIZE A DIMENSIONS (IN.) B C 1440 1441 1442 1443 ⁄2" 3 ⁄4" 1" 11⁄4" 11⁄4 13⁄8 11⁄4 11⁄4 13⁄32 111⁄32 119⁄32 115⁄16 17⁄8 2 115⁄16 15⁄16 1 UL File No. E-23018 CSA File No.
Rigid and Intermediate Metal Conduit Fittings Stainless Steel Pipe Straps • Higher degree of corrosion resistance than traditional zinc-plated or hot-dipped galvanized straps • One and two-hole straps for EMT sizes 1⁄2" through 2" • One and two-hole straps for Rigid and IMC size 1⁄2" through 4" • 303 stainless steel TRADE WT. PER SIZE 100 HOLE DIA. STD. PKG. 1 TS101-SS ⁄2" 2.21 3 TS102-SS ⁄4" 2.49 TS103-SS 1" 3.31 TS104-SS 11⁄4" 3.64 TS105-SS 11⁄2" 3.87 TS106-SS 2" 4.
Rigid and Intermediate Metal Conduit Fittings 1275 Series 1276AL Series For Rigid Metal Conduit and Intermediate Metal Conduit Standard Material Range 1275 Series . . . . . . 1976AL Series 1275 Series . . . . . . 1276AL Series Conduit Straps Malleable Iron . . . . . All copper-free 3 Application • To support and securely fasten rigid metal conduit and intermediate metal to the supporting surface Standard Finish 1275 Series . . . . . . 1276AL Series Listings/Compliances Hot Dipped . . .
Rigid and Intermediate Metal Conduit Fittings Conduit Spacers (For Rigid Metal Conduit, Intermediate Metal Conduit and Electrical Metallic Tubing) A 1350 1351–1354 Application • Provides mounting surface for conduit where installation requires air space between conduit and supporting surface Standard Material Features • Prevents conduit rusting from wall condensation 1350 Series. . . . . . . . . . . . . . . . 1350AL Series 1350 Series. . . . . . . . . . . . . . . . 1350AL Series Malleable Iron . . .
Rigid and Intermediate Metal Conduit Fittings One-piece fitting couples armored cable or flexible conduit to threaded rigid conduit! TITE-BITE® Combination Couplings — Armored Cable for Threaded Rigid • Tite-Bite® wedge holds conduit securely with a double grip • When used with a Chase® nipple, this fitting will connect flexible conduit to outlet boxes, enabling more wiring space in the box than the usual connector CAT. NO.
Conduit Outlet Bodies T&B Conduit Fittings for Ordinary and Hazardous Locations Thomas & Betts offers a broad range of conduit bodies, conduit boxes, conduit fittings, unions, sealing fittings, drains and cable fittings for both ordinary and hazardous locations. Complete information on applications, features, materials, finishes, size range and certifications is provided in the following pages.
Conduit Outlet Bodies Conduit Outlet Bodies Application Conduit Bodies are installed in conduit systems to: • Connect conduit sections Materials Form 7, Form 8 and Series 35 Conduit Bodies . . . . . . . . Sand-cast class 30 gray iron alloy Red•Dot® Conduit Bodies . . . . . . . . . . . . . . Die-cast aluminum, copper-free • Act as pull outlets when conductors are being installed • Provide easy access for splices in branch conductors Covers . . . . . . . . . . . . . .
Conduit Outlet Bodies Conduit Bodies Quick Reference SHAPE TYPE ⁄2 1 ⁄4 3 1 LB BlueKote® Form 7 LB17 LB27 LB37 BlueKote® Form 8** LB18 LB28 LB38 Series 35 LB50M LB75M-TB LB100M Threaded Aluminum* ALB1 ALB2 ALB3 EMT Aluminum* BLB1 BLB2 BLB3 LU BlueKote® Form 7 HUB SIZE (IN.
Conduit Outlet Bodies Replacement Covers and Gaskets HUB SIZE (IN.
Conduit Outlet Bodies Form 7 Body, Gasket and Cover — One Number! NEW! Pre-Assembled Form 7 BlueKote® Conduit Bodies, Gaskets and Covers T&B® Pre-Assembled Bodies, Gaskets and Covers CAT. NO. Now you can order a conduit body, gasket and cover, pre-assembled, using one catalog number. T&B’s pre-assembled cast conduit bodies help reduce transactions, eliminate the need for additional stocking bins and provide an easy inventory reduction.
Conduit Outlet Bodies LB Form 7 BlueKote® Conduit Bodies HUB CAT. NO. SIZE BlueKote internal finish reduces the amount of force necessary to pull wires through T&B Form 7 and Form 8 conduit bodies. LB17 LB27 LB37 LB47 LB57 LB67 LB77 LB87 LB97 LB107 LB Form 7 and Form 8 CAT. NO. LB50M LB75M-TB LB100M LB125M LB150M LB200M LB250M LB300M LB350M LB400M ⁄2" ⁄4" 1" 11⁄4" 11⁄2" 2" 21⁄2" 3" 31⁄2" 4" 1 3 B 4.60 5.25 6.00 6.45 7.25 8.30 10.55 10.55 12.85 12.85 2.20 2.40 2.65 3.20 3.90 4.45 5.20 5.95 6.70 7.
Conduit Outlet Bodies D B E C A T Series 35 LU Form 7 T Series 35 Conduit Bodies LU Form 7 BlueKote® Conduit Bodies CAT. NO. HUB SIZE A LU17 T27 LU37 LU47 LU57 LU67 ⁄2" 3 ⁄4" 1" 11⁄4" 11⁄2" 2" 5.54 6.22 7.34 8.40 8.95 10.61 1 DIMENSIONS (IN.) B C D 1.45 1.70 1.97 2.47 2.72 3.43 2.72 3.07 3.52 4.21 4.44 5.43 0.95 1.15 1.35 1.80 2.05 2.45 E CU. IN. 3.20 3.80 4.55 5.00 5.45 6.40 4.8 7.6 13.4 23.0 28.3 56.0 CAT. NO. HUB SIZE A DIMENSIONS (IN.) B C CU. IN.
Conduit Outlet Bodies A C B C Form 7 and Form 8 C Series 35 C Series 35 Conduit Bodies C Form 7 BlueKote® Conduit Bodies CAT. NO. HUB SIZE A B C17 C27 C37 C47 C57 C67 C77-TB C87 ⁄2" 3 ⁄4" 1" 11⁄4" 11⁄2" 2" 21⁄2" 3" 5.45 6.05 6.75 7.30 8.60 9.50 12.10 12.10 1.40 1.60 1.90 2.30 2.60 3.20 3.65 4.40 1 DIMENSIONS (IN.) C D 1.45 1.65 1.80 2.20 2.45 3.05 4.25 4.25 .95 1.15 1.35 1.80 2.05 2.45 3.60 3.60 E CU. IN. CAT. NO. HUB SIZE A DIMENSIONS (IN.) B C CU. IN. 3.20 3.80 4.55 5.00 5.45 6.
Conduit Outlet Bodies A C B LL Form 7 and Form 8 LL Series 35 LL Series 35 Conduit Bodies LL Form 7 BlueKote® Conduit Bodies CAT. NO. HUB SIZE A B LL17 LL27 LL37 LL47 LL57 LL67 LL77 LL87 LL97 LL107 ⁄2" 3 ⁄4" 1" 11⁄4" 11⁄2" 2" 21⁄2" 3" 31⁄2" 4" 4.60 5.25 6.00 6.45 7.90 8.30 10.55 10.55 12.85 12.85 1.40 1.60 1.90 2.30 2.60 3.20 3.65 4.40 4.90 5.40 1 DIMENSIONS (IN.) C D 1.45 1.65 2.60 3.05 3.80 4.25 5.80 5.80 7.03 7.03 .95 1.15 1.35 1.80 2.05 2.45 3.60 3.60 4.55 4.55 E CU. IN. CAT. NO.
Conduit Outlet Bodies A B C LR Form 7 and Form 8 LR Series 35 LR Series 35 Conduit Bodies LR Form 7 BlueKote® Conduit Bodies CAT. NO. HUB SIZE A B LR17 LR27 LR37 LR47 LR57 LR67 LR77 LR87 LR97 LR107 ⁄2" 3 ⁄4" 1" 11⁄4" 11⁄2" 2" 21⁄2" 3" 31⁄2" 4" 4.60 5.25 6.00 6.45 7.90 8.30 10.55 10.55 12.85 12.85 1.40 1.60 1.90 2.30 2.60 3.20 3.65 4.40 4.90 5.40 1 E CU. IN. CAT. NO. HUB SIZE A DIMENSIONS (IN.) B C CU. IN. 3.20 3.80 4.55 5.00 5.45 6.40 8.40 8.40 10.25 10.25 4.0 6.6 10.6 18.8 26.4 51.
Conduit Outlet Bodies L Form 7 BlueKote® Conduit Bodies L Form 7 CAT. NO. HUB SIZE A B DIMENSIONS (IN.) C D E L17-TB L27-TB L37-TB L47-TB L57-TB L67-TB ⁄2" 3 ⁄4" 1" 11⁄4" 11⁄2" 2" 4.60 5.25 6.00 6.45 7.90 8.30 1.40 1.60 1.90 2.30 2.60 3.20 1.45 1.65 2.60 3.05 3.80 4.25 .95 1.15 1.35 1.80 2.05 2.45 3.20 3.80 4.55 5.00 5.45 6.40 1 L Threaded Aluminum Conduit Bodies CAT. NO. HUB SIZE A B C ALRL1 ALRL2 ALRL3 ALRL4 ALRL5 ALRL6 ⁄2" 3 ⁄4" 1" 11⁄4" 11⁄2" 2" 3.88 4.63 5.38 7.25 7.25 9.50 3.
Conduit Outlet Bodies X Form 7 BlueKote® Conduit Bodies CAT. NO. HUB SIZE A B DIMENSIONS (IN.) C D E CU. IN. X17 X27 X37 X47 X57 X67 ⁄2" ⁄4" 1" 11⁄4" 11⁄2" 2" 5.60 6.20 7.35 7.30 8.60 9.50 1.80 2.00 2.30 2.30 2.60 3.20 3.05 3.30 3.80 3.85 5.05 5.45 .95 1.15 1.35 1.80 2.05 2.45 3.20 3.80 4.55 5.00 5.45 6.40 6.0 9.1 16.9 19.3 27.5 52.8 1 3 X Form 8 BlueKote® Conduit Bodies X Form 7 and Form 8 CAT. NO. HUB SIZE A B DIMENSIONS (IN.) C D E CU. IN.
Mogul Conduit Outlet Bodies Application • Act as pull outlets for conductors that are stiff, due to large size or type of insulation • Provide the longer openings needed when pulling large conductors • Prevent sharp bends and kinks in large conductors (protects insulation during installation) • Provide ample openings for splices and taps • Provide access to wiring for maintenance, and future system changes Features • Long openings • Provision for easy bends • Tapered tapped hubs with integral bushings • St
Mogul Conduit Outlet Bodies BUB Mogul Series (Cover and Gasket Included) C E A B SECTION A-A CAT. NO. HUB SIZE A B DIMENSIONS (IN.) C D BUB3-TB BUB4-TB BUB5-TB BUB6-TB BUB7-TB BUB8-TB BUB9-TB BUB10-TB 1" 11⁄4" 11⁄2" 2" 21⁄2" 3" 31⁄2" 4" 9.49 9.55 16.68 13.68 18.30 18.30 23.74 23.74 2.75 3.21 6.67 4.28 5.03 5.67 6.72 7.22 CAT. NO. HUB SIZE A B BT3-TB BT4-TB BT5-TB BT6-TB BT7-TB BT8-TB BT9-TB BT10-TB 1" 11⁄4" 11⁄2" 2" 21⁄2" 3" 31⁄2" 4" 9.56 9.56 13.75 13.75 18.38 18.38 23.75 23.75 1.88 2.
Aluminum Mogul Conduit Outlet Bodies Application • Raintight junction for bringing electrical service into a location • Spacious, accessible wiring chamber provides a convenient location to pull conductors and make splices Features • Copper-free* aluminum provides increased corrosion resistance • Precision cast and machined surfaces permit safer wire pulling • Clean cover edges provide good gasket sealing MALB • Precision NPT threaded hubs enable trouble-free field installation for rigid and IMC conduit •
Aluminum Mogul Conduit Outlet Bodies Aluminum Mogul Conduit Outlet Bodies with Covers and Gaskets MALB-3 through -6 CAT. NO. HUB SIZE UNIT QTY. STD. PKG. WT. LBS. PER 100 MALB-3 MALB-4 MALB-5 MALB-6 MALB-7 MALB-8 MALB-9 MALB-10 1" 11⁄4" 11⁄2" 2" 21⁄2" 3" 31⁄2" 4" 1 2 1 1 1 1 1 1 10 10 1 1 1 1 1 1 174 160 400 375 1100 1060 1900 1800 COVER CAT. NO. GASKET CAT. NO. HUB SIZE UNIT QTY. STD. PKG. WT. LBS.
FS/FD Cast Device Boxes and Covers Cast Device Boxes Application • Accommodate wiring devices Size Range • Hubs: 1⁄2" to 1" NPT • Act as pull boxes for conductors in a threaded rigid conduit system, including an internal ground screw Materials • Boxes: Class 30 gray iron alloy • Provide openings to make splices and taps in conductors • Covers: Sand cast aluminum alloy and sheet steel • Gaskets: Neoprene • Provide access to conductors for maintenance and future system changes Finish • Zinc-plated with
FS/FD Cast Device Boxes and Covers Single-Gang Cast Device Boxes Fig. A Dead-End Fig. C Thru-Feed Fig. B Dead-End Shallow Single-Gang Cast Device Boxes CAT. NO. FIG. HUB SIZE A B C DIMENSIONS (IN.) D E F G Dead-End FS019-TB FS1-TB FS2-TB FS3-TB A B B B Blank 1 ⁄2" 3 ⁄4" 1" 2.00 2.00 2.00 2.00 2.75 2.75 2.75 2.75 4.28 4.28 4.28 4.28 — .88 .88 .88 3.38 2.19 2.19 2.19 4.72 — — — .88 — — — N/A 0.570 0.755 0.935 N/A 0.610 0.810 1.
FS/FD Cast Device Boxes and Covers Shallow Double-Gang Cast Device Boxes CAT. NO. Fig. A Dead-End Dead-End FS062-TB FS12-TB FS22-TB FS32-TB Thru-Feed FSC12-TB FSC222-TB FSC32-TB FIG. HUB SIZE A B A B B B Blank 1 ⁄2" 3 ⁄4" 1" 2.00 2.00 2.00 2.00 4.63 4.63 4.63 4.63 4.28 4.28 4.28 4.28 ⁄2" ⁄4" 1" 2.00 2.00 2.00 4.63 4.63 4.63 4.28 4.28 4.28 C C C 1 3 DIMENSIONS (IN.) C D THROAT DIA. MIN. MAX. E F — .88 .88 .88 4.13 2.19 2.19 2.19 5.50 — — — N/A 0.570 0.755 0.935 N/A 0.610 0.810 1.
FS/FD Cast Device Boxes and Covers 1.405 dia. hole Single Gang Covers DSS100-TB CAT. NO. DESCRIPTION DSS100-TB DS21-TB DS23-TB DS32-TB DS100G-TB Blank, Sheet Steel Round Receptacle, Sheet Steel Duplex Receptacle, Sheet Steel Single Switch, Sheet Steel Blank, Cast Aluminum DS21-TB Double Gang Covers DS23-TB CAT. NO.
FS/FD Aluminum Device Boxes and Covers Application • Industrial grade FS/FD device boxes and raintight covers protect wiring devices, switches, electronic components, and terminal blocks in dry, damp and wet locations.
FS/FD Aluminum Device Boxes and Covers Single Gang Boxes Raintight* CAT. NO. HUB SIZE UNIT QTY. STD. PKG. WT. LBS.
FS/FD Aluminum Device Boxes and Covers Dimensions and Cubic Inches (CI) Single Gang Boxes AFS AFS, AFSC, AFSS, AFSCC CAT. NO. HUB SIZE A B AFS-1 AFS-2 AFS-3 AFSC-1 AFSC-2 AFSC-3 AFSS-1 AFSS-2 AFSCC-1 AFSCC-2 ⁄2" 3 ⁄4" 1” 1 ⁄2" 3 ⁄4" 1" 11⁄2" 3 ⁄4" 1 ⁄2" 3 ⁄4" 49⁄16 49⁄16 49⁄16 49⁄16 49⁄16 49⁄16 49⁄16 49⁄16 49⁄16 49⁄16 213⁄16 213⁄16 213⁄16 213⁄16 213⁄16 213⁄16 213⁄16 213⁄16 213⁄16 213⁄16 1 AFSS AFSCC C D DIMENSIONS (IN.) E F G H J CU. IN.
FS/FD Aluminum Device Boxes and Covers Dimensions and Cubic Inches (CI) Double Gang Boxes 2AFS 2AFSC 2AFS, 2AFSC CAT. NO. 2AFS-1 2AFS-2 2AFS-3 2AFSC-1 2AFSC-2 HUB SIZE A B ⁄2" 3 ⁄4" 1" 1 ⁄2" 3 ⁄4" 49⁄16 49⁄16 49⁄16 49⁄16 49⁄16 45⁄8 45⁄8 45⁄8 45⁄8 45⁄8 1 C D DIMENSIONS (IN.) E F G H CU. IN. ⁄16 13 ⁄16 7 ⁄8 13 ⁄16 13 ⁄16 21⁄16 21⁄16 21⁄16 21⁄16 21⁄16 13⁄8 13⁄8 111⁄16 13⁄8 13⁄8 27⁄8 27⁄8 27⁄8 27⁄8 27⁄8 43⁄8 43⁄8 43⁄8 43⁄8 43⁄8 115⁄16 115⁄16 115⁄16 115⁄16 115⁄16 36.0 36.0 36.0 36.0 36.
FS/FD Aluminum Device Boxes and Covers Special new aluminum alloy offers the ultimate in corrosion resistance! T&B® FS/FD CorroStall™ Aluminum Boxes • Special aluminum alloy provides corrosion resistance as cast • No protective coating required to prevent corrosion Material • Aluminum alloy • Ideal for use in food and beverage or pharmaceutical washdown areas, chemical processing and other corrosive environments Finish • As cast • Available in single- and double-gang sizes • Use with standard T&B FS/FD
FS/FD Aluminum Device Boxes and Covers Special new aluminum alloy offers the ultimate in corrosion resistance! T&B® FS/FD CorroStall™ Aluminum Boxes 4.63" .63" 4.56" 2.00" 1.50" .63" Double-Gang CorroStall™ Boxes CAT. NO. LT11-3-FP LT14-3-FP LT11-2-FP LT14-2-FP NO. OF OUTLET HOLES HUB SIZE (IN.) STD. PKG. 5 5 4 4 1 ⁄2 ⁄4 1 ⁄2 3 ⁄4 10 10 10 10 3 Material • Aluminum alloy Finish • As cast LT11-2-FP LT14-2-FP A-60 www.tnb.com United States Tel: 901.252.8000 800.816.7809 Fax: 901.252.
FS/FD Aluminum Device Boxes and Covers Single Gang Covers — Raintight* UNIT QTY. STD. PKG. WT. LBS. PER 100 For Duplex Receptacles, Horizontal CWPDR* Duplex receptacle cover with 2 spring doors, Device Mount CWPDR-FS* Box Mount 1 1 25 25 40 40 For Duplex Receptacles, Vertical CFSDR* Box Mount 1 25 38 For GFCI Receptacles Horizontal CFSH-G* Box Mount 1 25 40 1 25 40 1 25 40 CAT. NO.
FS/FD Aluminum Device Boxes and Covers Single Gang Covers UNIT QTY. STD. PKG. WT. LBS. PER 100 For Duplex Receptacles CDR Duplex receptacle Cover, Box Mount 20 100 11 For Switches CTS 20 100 14 CAT. NO. DESCRIPTION Switch Cover, Box Mount CTS CDR CAT. NO. NOMINAL SIZE MAX. DEVICE FACE DIA. UNIT QTY. STD. PKG. WT. LBS. PER 100 1.600" 1.395" 20 20 100 100 12 12 For Single Receptacles (Box Mount Only) CRL 19⁄16" CRS 13⁄8" FS-GKV CR Series CAT. NO. DESCRIPTION STD. PKG. WT. LBS.
FS/FD Aluminum Device Boxes and Covers Dimensions — Single Gang Covers CWPDR CWPDR-FS CFSDR CDR CFSH-G CWPV-G CFSR-G CFST CFSR Series CTS CR Series CFSTF United States Tel: 901.252.8000 800.816.7809 Fax: 901.252.1354 CFSB Technical Services Tel: 888.862.3289 www.tnb.
Conduit Outlet Boxes Explosion-Proof, Dust-Ignition-Proof Dimensions — Double Gang Covers 113⁄16" 113⁄16" 45⁄8" 45⁄8" 45⁄8" 49⁄16" 311⁄16" 49⁄16" 49⁄16" 2CDR 2CWPDR 2CTDR 45⁄8" 45⁄8" 21⁄4" Dia. 21⁄4" Dia. 311⁄16" 49⁄16" 49⁄16" 23⁄8" 113⁄16" 33⁄4" 2CFSR-M 2CWPR-M 45⁄8" 45⁄8" 49⁄16" A-64 311⁄16" 49⁄16" 45⁄8" 311⁄16" 311⁄16" 49⁄16" 33⁄4" 33⁄4" 33⁄4" 2CTS 2CFST 2CFSB www.tnb.com United States Tel: 901.252.8000 800.816.7809 Fax: 901.252.1354 Technical Services Tel: 888.862.
Conduit Outlet Boxes Explosion-Proof, Dust-Ignition-Proof GUA Conduit Outlet Boxes Application GUA boxes can be used for hazardous location conduit runs for the following: GUA • Allows for mounting of fixture outlets (when used with appropriate covers) • Provides easy access to wiring • Provides junction in conduit for wire pulling and splices • Changes direction in rigid conduit systems GUA • Attaches two or more pieces of conduit in long runs Features • All hubs have a minimum of five full threads an
Conduit Outlet Boxes Explosion-Proof, Dust-Ignition-Proof GUA Conduit Outlet Boxes GUAW GUAT GUAL GUAN GUAX GUAM GUAL CAT. NO. GUAL14-TB GUAL16-TB GUAL24-TB GUAL26-TB GUAL36-TB GUAL47-TB GUAL49-TB GUAL59-TB GUAL69-TB GUAT HUB SIZE ⁄2" ⁄2" 3 ⁄4" 3 ⁄4" 1" 11⁄4" 11⁄4" 11⁄2" 2" 1 1 DIMENSIONS (IN.) A B C 2.25 2.00 2.00 2.00 2.31 2.69 3.81 3.81 4.06 2.50 3.50 2.50 3.50 3.50 4.38 5.75 5.75 5.75 .88 .88 .88 .88 .88 1.00 1.00 1.06 1.06 THROAT DIA. MIN. MAX. .570 .570 .755 .755 .935 1.260 1.260 1.
Aluminum Conduit Outlet Boxes Explosion-Proof, Dust-Ignition-Proof Application • Junction for branch conduits in hazardous locations • Accessible wiring chamber provides a convenient location to maintain or change a system, pull conductors and make splices GAX • Unique mounting pads and external hub designideal for installations of OEM devices or instruments Features • Copper-free* aluminum provides increased corrosion resistance Listings/Compliances • UL Listed • CSA Certified • Suitable for hazardous l
Aluminum Conduit Outlet Boxes Explosion-Proof, Dust-Ignition-Proof External Hubs with Installed Green Ground Screw Through Feed with Surface Cover CAT. NO. GAC • • • GAC-1 GAC-2 GAC-3 HUB SIZE UNIT QTY. STD. PKG. WT. LBS. PER 100 ⁄2" ⁄4" 1" 1 1 1 5 5 5 115 115 115 HUB SIZE UNIT QTY. STD. PKG. WT. LBS. PER 100 ⁄4" 1 5 110 HUB SIZE UNIT QTY. STD. PKG. WT. LBS. PER 100 ⁄2" ⁄4" 1" 11⁄4" 11⁄2" 2" 1 1 1 1 1 1 5 5 5 5 4 4 115 115 115 175 247 253 HUB SIZE UNIT QTY. STD. PKG. WT. LBS.
Aluminum Conduit Outlet Boxes Explosion-Proof, Dust-Ignition-Proof External Hubs with Installed Green Ground Screw X Style with Surface Cover GAX CAT. NO. HUB SIZE UNIT QTY. STD. PKG. WT. LBS. PER 100 †• † †• †• ⁄2" ⁄4" 1" 11⁄2" 1 1 1 1 5 5 5 1 125 125 125 257 GAX-1 GAX-2 GAX-3 GAX-5 1 3 X Style with Flange and Surface Cover CAT. NO. GAFX † † HUB SIZE UNIT QTY. STD. PKG. WT. LBS. PER 100 ⁄2" ⁄4" 1 1 4 4 135 135 FITS BOXES STD. PKG. WT. LBS.
Aluminum Conduit Outlet Boxes Explosion-Proof, Dust-Ignition-Proof Dimensions and Cubic Inches (CI) EXUN & EXUNL HUB SIZE A B C D ⁄2" 3 ⁄4" 1" 331⁄32" 331⁄32" 331⁄32" 31⁄8" 31⁄8" 35⁄16" 221⁄32" 221⁄32" 3 ⁄4" 21⁄16" 21⁄16" 21⁄4" 1 DIMENSIONS (IN.) E F 4 4 4 33⁄8" 33⁄8" 39⁄16" G H J 41⁄4" 41⁄4" 41⁄4" 11⁄4" 11⁄4" 11⁄16" 19⁄16" 19⁄16" 19⁄16" K CI ⁄64" 17 ⁄64" 17 ⁄64" 20.3 20.3 20.
Aluminum Conduit Outlet Boxes Explosion-Proof, Dust-Ignition-Proof Dimensions and Cubic Inches (CI) ⁄16" 3 GAFX COVER OPENING 311⁄16" 311⁄16" 311⁄16" HUB SIZE A B C D ⁄2" 3 ⁄4" 1" 4" 4" 4" 21⁄4" 21⁄4" 21⁄4" 215⁄16" 215⁄16" 215⁄16" 59⁄16" 59⁄16" 59⁄16" 1 DIMENSIONS (IN.) E F ⁄16" 11 ⁄16" 13 ⁄16" 41⁄2" 41⁄2" 43⁄4" 11 G H ⁄4" 1 ⁄4" 5 ⁄16" 13⁄8" 13⁄8" 15⁄8" 1 L M CI ⁄16" 9 ⁄16" 9 ⁄16" 53⁄16" 53⁄16" 51⁄2" 20.0 20.0 19.
Aluminum Conduit Outlet Boxes Explosion-Proof, Dust-Ignition-Proof Application • Junction for branch conduits in hazardous locations Listings/Compliances • UL Listed • Accessible wiring chamber provides a convenient location to maintain or change a system, pull conductors and make splices • CSA Certified • Internal hub design ideal for installation where space is limited • Federal Spec W-C-586 • Suitable for hazardous locations • CI.I, Div. 1 & 2, Groups C, D CI.II, Div. 1, Groups E, F, G CI.
Aluminum Conduit Outlet Boxes Explosion-Proof, Dust-Ignition-Proof 5-Hole Box CAT. NO. EXUN-1 EXUN-2 EXUN-3 HUB SIZE DESCRIPTION UNIT QTY. STD. PKG. WT. LBS. PER 100 ⁄2" ⁄4" 1" 5 outlets with 3 close-up plugs with 3 close-up plugs 1 1 1 5 5 5 140 140 140 HUB SIZE DESCRIPTION UNIT QTY. STD. PKG. WT. LBS. PER 100 ⁄2" ⁄4" 4 outlets with 2 close-up plugs 1 1 5 5 140 — 1 3 EXUN-1 4-Hole Box CAT. NO. EXUN-11 EXUN-22 1 3 EXUN-11 United States Tel: 901.252.8000 800.816.7809 Fax: 901.252.
Aluminum Conduit Outlet Boxes Explosion-Proof, Dust-Ignition-Proof Application • Junction for branch conduits in hazardous locations • Accessible wiring chamber provides a convenient location to maintain or change a system, pull conductors and make splices Features • Copper-free* aluminum alloy provides increased corrosion resistance GASS Clean cover edges • Precision cast and machined surfaces permit safer wire pulling • Large capacity 31 cu. in.
Aluminum Conduit Outlet Bodies Explosion-Proof, Dust-Ignition-Proof Perfect for the petrochemical industry! NEW! GUP Explosion-Proof Enclosure Specifications T&B has developed an innovative new solution ideally suited for gas station contractors and the petrochemical market — the GUP ExplosionProof Enclosure. The compact design makes gas station pumps an ideal application due to space constraints.
Conduit Outlet Bodies Explosion-Proof, Dust-Ignition-Proof Application OE series are installed in conduit systems within hazardous areas to: • Protect conductors in threaded rigid conduit • Act as pulling and splice fittings • Interconnect lengths of conduit • Change direction of conduit • Provide access for maintenance and future system changes Features OE conduit bodies have: • Tapered threaded hubs for ground continuity • Smooth integral hub bushings to protect conductor insulation when pulling • Five
Conduit Outlet Elbows Explosion-Proof, Dust-Ignition-Proof Provides maximum volume for bends within a compact overall size! Capped Iron Elbow — Female to Female Application LBY/GYF elbows are installed in conduit systems within hazardous areas to: • Make 90° bends in conduit systems where space is limited • Act as pull outlets • Provide access to conductors for maintenance and future system changes Features • Maximum volume for bends within a compact overall size LBY • Screw on cover for ease of installat
RE, PLG, REC Reducers, Plugs and Adapters Explosion-Proof, Dust-Ignition-Proof Recessed Plugs Application • RE and REC reducers are used in threaded heavy wall conduit systems Standard Finishes • Cast zinc-plated with aluminum acrylic paint • RE reduces conduit hubs to a smaller size • Machine zinc-plated with clear chromate finish • REC connects two different sizes of conduit together or is used to replace a coupling and reducer in an installation Listings/Compliances • UL: 886 • PLG plugs are used
Three-Piece Couplings Explosion-Proof, Dust-Ignition-Proof UNY Male Unions Application UNY and UNF unions are installed in threaded thickwall conduit systems: • UNY — to connect conduit to a conduit fitting, junction box, or device enclosure • UNF — to connect conduit to conduit, or to provide a means for future modification of the conduit system Standard Finishes • Steel — electrogalvanized with chromate treatment • Iron alloy, malleable iron — electrogalvanized and aluminum acrylic paint UNY TRADE SIZE
Aluminum Three-Piece Couplings Explosion-Proof, Dust-Ignition-Proof EXFU Smooth conduit stops EXMU Precision machined threads Unique concentric ring design Application • Unions are used as connecting elements between enclosures, fittings or boxes that permit future changes to the system in both hazardous and non-hazardous areas Listings/Compliances • UL Listed Features • Copper-free* aluminum provides increased corrosion resistance • CI.I, Div. 1 & 2, Groups C, D CI.II, Div. 1, Groups E, F, G CI.
Elbows Explosion-Proof, Dust-Ignition-Proof Application EYD drain and inspection sealing fittings: • Restrict the passage of gases, vapors or flames from one portion of the electrical installation to another at atmospheric pressure and normal ambient temperatures • Limit explosions to the sealed-off enclosure • Prevent precompression or “pressure piling” in conduit systems.
Sealing Fittings Explosion-Proof, Dust-Ignition-Proof EYD Drain Seals CAT. NO. HUB SIZE A B TURNING RADIUS EYD11-TB EYD21-TB EYD31-TB EYD41-TB EYD51-TB EYD61-TB EYD71-TB EYD81-TB EYD91-TB EYD101-TB ⁄2" ⁄4" 1" 11⁄4" 11⁄2" 2" 21⁄2" 3" 31⁄2" 4" 3.81 4.08 4.85 5.00 5.44 6.25 7.50 8.50 9.19 9.75 1.50 1.75 2.19 2.25 2.44 3.00 3.50 4.25 4.75 5.25 1.75 1.98 2.19 1.80 2.00 2.32 2.69 3.15 3.38 3.64 1 3 DIMENSIONS (IN.) Cl. I, Div. 1 & 2, Groups A, B, C, D Cl. II, Div. 1, Groups E, F, G Cl. III, Div.
Sealing Fittings Explosion-Proof, Dust-Ignition-Proof EYS Sealing Fittings Application EYS sealing fittings can be installed in either vertical or horizontal applications. • Seals sections of conduit runs from passage of vapors, flame, or gases Materials • Bodies: Ductile Iron Listings/Compliances • UL886 • Plugs: Gray Iron • CSA: C22.2 No. 30 • Nipples: Steel, supplied • EYS seals are approved to be used with Crouse-Hinds® Chico® A compound and Chico® X fiber.
Sealing Fittings Explosion-Proof, Dust-Ignition-Proof Application • Limits flames and/or explosions to area within electrical system where they originate • Limits pressure piling EYVF • CSA Certified • Suitable for hazardous locations • Required by NEC for conduit systems in hazardous locations 18" from an enclosure housing a heat producing or arcing device; on 2" and larger system that enters an enclosure containing splices; wherever conduit leaves a Class I, Division I area and enters a non-hazardous ar
Sealing Fittings Explosion-Proof, Dust-Ignition-Proof Preparation Applications T&B Red•Dot® sealing cement is used for making seals in sealing fittings. The insulation in the conductors sealed in the cement may be approved thermoplastic or rubber, with or without lead covering. The sealing cement should not be used for insulating. Characteristics T&B Red•Dot® sealing cement is not affected by gasoline, alcohol, acetone, ether, naptha, petroleum, benzol or lacquer solvent.
Sealing Fittings Explosion-Proof, Dust-Ignition-Proof Sealing Cement and Fiber for Thomas & Betts Sealing Fittings Explosion-Proof Dust-Ignition-Proof Raintight Wet Locations CI.I, Div. 1 & 2, Groups C, D CI.II, Div. 1, Groups E, F, G CI.III, Div. 1 & 2 Sealing Cement • Can be used on T&B Red•Dot® EYV, EVH series fittings only CAT. NO. QUANTITY VOLUME CUBIC INCHES STD. PKG. WT. LBS PER 100 EXSC-2 EXSC-8 EXSC-16 3.2 oz. 13 oz. 1 lb., 10 oz. 2.75” 11.50” 23.
Flexible Couplings — Explosion-Proof, Dust-Ignition Proof Make flexible connections in hazardous locations! XP Flex Explosion-Proof Flexible Couplings XPLFL16 With their flexible design, T&B® XP Flex Couplings make it easy to achieve tight bends in conduit systems in confined spaces — or to connect stationary equipment to equipment that moves or vibrates. Their explosion-proof and corrosion-resistant construction mean you can use them with confidence in hazardous and wet locations.
Kopr-Shield® Compound The copper colloidal surface treatment that protects, lubricates and enhances conductivity between all electrical connections. Kopr-Shield® Compound Good connections are one of the most important aspects of electrical work. Mechanics know how much downtime is caused when fluids or oils leak into the raceway system or when looking for a weak link in a ground system caused by a high resistance connection.
Jacketed Metal Clad Cable Termination Fittings Jacketed Metal Clad Cable and Teck Cable Metal Clad Cable (Type MC) Ref. NEC Article 334* Teck Cables “Metal Clad Cable Type MC is a factory assembly of one or more conductors, each individually insulated and enclosed in a metallic sheath of interlocking tape, or a smooth or corrugated tube.” Teck cable derived its name from one of its first users, the Teck-Hughes Gold Mines in Kirkland Lake, Ontario. Teck 90 is CSA Type designation.
Jacketed Metal Clad Cable Termination Fittings STAR TECK EXTREME® — STE/STEX Series Cable Fitting The STAR TECK® STE cable fitting series is designed for optimum integrity in ordinary applications. The STEX series is specially designed for classified hazardous areas. Both are designed to stand up to the harshest and most corrosive environment. Application • Provides means for passing jacketed metal clad cables through a bulkhead or enclosure in industrial and hazardous areas.
Jacketed Metal Clad Cable Termination Fittings STEX Series Hazardous Locations STE Series Ordinary STAR TECK EXTREME®Jacketed Metal-Clad Cable Fittings CAT. NO. HUB SIZE NPT STRIP LENGTH (IN.) Ordinary Locations ST050-462# 1⁄2 STE050DATA**# 1⁄2 1 STE050* ⁄2 3 STE075* ⁄4 STE100* 1 STE125* 11⁄4 STE150* 11⁄2 STE200* 2 STE250 21⁄2 STE300 3 STE350 31⁄2 STE400 4 GLAND TORQUE (IN.-LB.) CABLE RANGE OVER JACKET (IN.) MIN. MAX. CABLE RANGE OVER ARMOR (IN.) MIN. MAX. A1: THROAT DIA. MIN.
Jacketed Metal Clad Cable Termination Fittings STAR TECK® Jacketed Metal-Clad Cable Fittings Dependable Grounding. Power-Grip grounding ring is non-magnetic stainless steel. Provides 360° long-term dependable grounding. It makes immediate contact with the cable. Easy Installation. Exclusive powergrip. Provides a grip that’s high up on the cable — not on the first convolution — so strip length and cutting of cable are not critical. Overlapping range of sizes.
Jacketed Metal Clad Cable Termination Fittings Overlapping range of sizes accommodates a broad range of cables! STAR TECK® Jacketed Metal-Clad Cable Fittings for Ordinary Locations HUB SIZE NPT CAT. NO. C Retaining ring (stainless steel) Bushing (neoprene) Gland nut (aluminum) B Grounding ring (stainless steel) Body (aluminum) A • Overlapping sizes minimize possibility of mismatched cables and fittings in the field • Available in hub sizes from 1⁄2" to 4", handling outer jacket diameters from 0.
Jacketed Metal Clad Cable Termination Fittings Easy installation saves time, money! STAR TECK XP® Jacketed Metal-Clad Cable Fittings for Hazardous Locations Application • Provide means for passing armored, metal clad, jacketed cables through a bulkhead or enclosure in hazardous areas (these fittings are suitable for hazardous areas when used with T&B sealing compound) 1. Prepare cable 2.
Jacketed Metal Clad Cable Termination Fittings STAR TECK XP® Jacketed Metal Clad Cable Fittings for Hazardous Locations CAT. NO. STX050-462 STX050-464 STX075-465 STX075-466 STX100-467 STX100-468 STX125-469 STX150-470 STX150-550 STX150-471 STX200-472 STX200-473 STX200-474 STX250-475 STX250-476 STX300-478 STX300-479 STX350-480 STX350-481 STX400-482 STX400-483 STX400-484 STX400-485 HUB SIZE NPT ⁄2 ⁄2 3 ⁄4 3 ⁄4 1 1 11⁄4 11⁄2 11⁄2 11⁄2 2 2 2 21⁄2 21⁄2 3 3 31⁄2 31⁄2 4 4 4 4 1 1 CABLE RANGE OVER JACKET (IN.
Jacketed Metal Clad Cable Termination Fittings Spin-On® Series II Connectors and Accessories CAT. NO. 2-050-008 2-050-010 2-050-020 2-050-030 2-075-040 2-075-050 2-075-060 2-100-070 2-100-080 2-100-090 2-100-100 2-125-110 2-125-120 2-125-130 2-150-140 2-150-150 2-150-160 2-200-170 2-200-180 2-200-190 2-200-200 2-250-210 2-250-220 2-250-230 2-250-240 2-300-250 2-300-260 2-300-270 2-300-280 2-350-300 2-350-310 2-350-320 2-400-330 2-400-340 HUB SIZE NPT CABLE RANGE OVER ARMOR (IN.
Jacketed Metal Clad Cable Termination Fittings Install a complete gas-blocked connector in a hazardous location! Spin-On® X Connectors for Hazardous Locations CAT. NO. 4-075-008 4-075-010 4-075-020 4-075-030 4-075-040 4-100-050 4-100-060 4-100-070 4-100-080 4-125-090 4-125-100 4-125-110 4-125-120 4-150-130 4-150-140 4-150-150 4-200-160 4-200-170 4-200-180 4-200-190 4-250-200 4-250-220 4-300-240 4-300-260 4-300-270 4-400-350 HUB SIZE NPT CABLE RANGE OVER ARMOR (IN.
Tray Cable Fittings Now A va in Sta ilable inl up to ess 1" Increase safety for hazardous locations. Applications Silver Grip® TCF® Series — Tray Cable: Complies with IEC requirements for Class I, Zone 2 Tray/Cord Fitting locations when used with enclosures containing no arcing or sparking Introducing the Silver Grip® Tray/Cord Fitting — the safe, yet cost-efficient choice for increased safety when terminating portable cord and tray cable in hazardous locations.
Tray Cable Fittings The T&B TC Series Tray Cable Connector The Thomas & Betts TC Series of connectors are designed specifically for transitioning tray cable from horizontal cable tray to terminations in enclosures. The precision machined aluminum interiors are ideally suited for use with sunlight-oil resistant cable.
Electrical Metallic Tubing (EMT) Fittings Suggested Specifications for Electrical Metallic Tubing (EMT) Fittings Series 5123 Insulated EMT Connector (Raintight) (Compression Type) Series 5120 EMT Coupling (Raintight) (Compression Type) Series 1350 Pipe Spacers Series 4176 Pipe Straps A-100 www.tnb.com • Ferrous Electrical Metallic Tubing (EMT) shall be of the hot dipped galvanized type conforming to applicable specifications WW-563/ANSI C33.98/ANSI C80.3/UL 797/ CSA C22.2 No. 83. E.M.T.
Electrical Metallic Tubing (EMT) Fittings Fittings for Electrical Metallic Tubing (EMT) Compression Type, Raintight 5123 Series 5120 Series Application • To connect and effectively bond electrical metallic tubing to a box or an enclosure Standard Material • To provide a rain tight connection between tubing and the connector Rated 105° C All Steel except Insulator. Insulator . . . . . . . . . . . . . . . . . . . .Thermoplastic, UL Standard Finish • To couple ends of tubing All Steel Parts . . . . .
Electrical Metallic Tubing (EMT) Fittings Materials, Specifications Material: Steel Body, Steel Locknut EMT Raintight Fittings UL Standard: 514B Liner: Nylon (for insulated fittings) NEMA: FB-1 Threads: Male hub threads NPS • Distinctive fitting design and gland nut color enable inspectors to visually inspect conformance from a distance — no close-up inspection required Across Peaks A Raintight EMT Compression Fittings feature a distinctive design and vibrant gland nut color, enabling inspectors to
Electrical Metallic Tubing (EMT) Fittings Insulated for safe, simple installation in cramped locations or tight corners! Short Elbows — Insulated* • Ideal for applications where large radius conduit elbows won’t fit or would appear unworkmanlike • Shoulders on body of 1⁄2" size are hex-shaped to provide positive holding for standard installation tools CAT. NO. HUB SIZE A DIMENSION (IN.
Electrical Metallic Tubing (EMT) Fittings Snap-on design holds strap in place! Pipe Straps — Steel Oval Hole for Screw Size (C) • Elongated bolt hole makes alignment easy, even when holes in mounting surface are out of alignment CAT. NO. HUB SIZE A 4159 4160 4161 4162 4163 4164 ⁄2" ⁄4" 1" 11⁄4" 11⁄2" 2" 1 ⁄32 21⁄32 211⁄32 27⁄8 311⁄16 41⁄16 1 DIMENSIONS (IN.) B ⁄4 ⁄4 3 ⁄4 3 ⁄4 11⁄4 11⁄8 27 3 3 3 C (BOLT HOLE) ⁄4 ⁄4 1 ⁄4 1 ⁄4 11 ⁄32 13 ⁄32 1 1 Not UL Listed. CSA File No.
Liquidtight Flexible Metal Conduit Fittings Our Liquidtight Line Is the End-All for Liquidtight Dust-Tight Connections. All our high-performance products are designed to deliver excellent reliability as well as ease of installation in virtually any application. And you benefit from our expertise through our liquidtight and dust-tight connections available for a variety of conduits as well as portable cord.
Liquidtight Flexible Metal Conduit Fittings T&B makes liquidtight fittings for demanding situations. Liquidtight Flexible Metal Conduit Fittings Gland deflects water away from connector and prevents “pooling” of moisture. Look for the distinctive “Pumpkin” appearance of the gland nut. Revolver® Grounding Fitting Saves time and money using our infinitely adjustable rotating ground lug. Simply align the lug in your preferred position and tighten the gland.
Liquidtight Flexible Metal Conduit Connectors Liquidtight Connectors Features of Thomas & Betts Liquidtight Fittings include: Liquidtight Flexible Metal Conduit Fittings • Safe Edge® ground cone design that accepts variations in raceway convolutions and provides a positive bond Thomas & Betts Liquidtight fittings for flexible metal conduits are suitable for a wide range of installations, including heavy industrial applications.
Liquidtight Flexible Metal Conduit Fittings 5331 Series* 5231 AL Series Application • Used where flexible metal raceway is installed in outdoor or indoor locations where exposed to continuous or intermittent moisture Standard Material • To positively bond conduit to box or enclosure Sealing Ring and Insulator: All thermoplastic • Ground cone design offers the following advantages: * 5341 Series… same as 5331, except 45° Connectors 5351 Series… same as 5331, except 90° Connectors 304 Stainless Steel
Liquidtight Flexible Metal Conduit Fittings 52® and 53™ Series Liquidtight Straight Connectors* CAT. NO. INSULATED STEEL Steel/malleable iron or aluminum tapered hub threads. With safe-edge ground through 4" cone and double bevel seating ring (through 2").
Liquidtight Flexible Metal Conduit Fittings 52® Series High-Temperature Flexible Metal Liquidtight Fittings Where liquidtight flexible metal fittings are required in high-temperature environments up to 150° C: T&B HT-Series Liquidtight Fittings are available straight, 45° and 90°.
Liquidtight Flexible Metal Conduit Fittings High-quality, corrosion-resistant, liquidtight termination for LTA flexible aluminum conduit. NEW! B 52® Series Liquidtight Aluminum Connectors — Straight and 90˚ Liquidtight Aluminum Fitting — Straight A C B A C Liquidtight Aluminum Fitting — 90˚ Angle . . . . . . . . . . . . . . . . . Specifications . . . . . . . . . . . . . . . . . . . Standard Material • Body, Gland, Locknut . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Liquidtight Flexible Metal Conduit Fittings The strength of steel — with superior corrosion-resistance! Stainless Steel Liquidtight Conduit Connectors • Ideal for industrial MRO and OEM applications in food and beverage, pharmaceutical, petrochemical, wastewater, salt water and other corrosive environments • Available in straight, 45° and 90° angled configurations to fit conduit from 3⁄8" to 2" • Connects metallic-cored liquidtight conduit to a box or enclosure • Standard version (SST Series) rated for
Liquidtight Flexible Metal Conduit Fittings Sealing material resists oil, coolants and hydraulic fluids as well as water! Liquidtight Sealing Gasket The 5262 Series Sealing Gasket includes a stainless steel retaining ring to prevent elongation of the Santoprene® gasket, ensuring a superior seal.
Liquidtight Flexible Metal Conduit Fittings Nylon Insulated CHASE® Connectors B A C Steel or malleable iron with O-Ring Seal CAT. NO. CONDUIT SIZE A DIMENSIONS (IN.
Liquidtight Flexible Metal Conduit Fittings External Bonding Liquidtight Flexible Metal Conduit Connectors Application • Used where external bonding jumper is required around liquidtight flexible metal conduit • To positively bond conduit to box or enclosure • Used where flexible raceway is installed in outdoor or indoors location where exposed to continuous or intermittent moisture Features • Designed with provision to install bonding jumper in several positions • Designed to accept mechanical or compressi
Liquidtight Flexible Metal Conduit Fittings Malleable iron with tapered hub threads! Grounding Fittings — Straight*, 45° Angle and 90° Angle Revolver® Ground Ring CAT. NO. STEEL INSULATED A C B Straight Ground Fittings Malleable iron, tapered hub threads. Ground Wire Max. over Ribs 90º Angle Ground Fittings Malleable iron tapered hub threads.
Liquidtight Flexible Metal Conduit Fittings Liquidtight Union for Threaded Hub 41 Series (B) Controlled Deformation of Resilient Seal (E) Gland Resilient Seal (A) (C) Application • To couple threaded end of a fitting or a pipe to a tapped opening in a box or enclosure where rotation of fitting or pipe is limited or restricted Standard Material/Finish Features • Design provides high quality bond between fitting or pipe to the union Range • Provided with resilient seal (A) Listings/Compliances • Res
Liquidtight Flexible Metal Conduit Fittings Fittings for liquidtight flexible metal conduit with metric threads of PG form (DIN 40430). PG Metric Thread Liquidtight Fittings* CAT. NO. FLEXIBLE CONDUIT SIZE Fittings for Liquidtight flexible metal conduit with metric threads of PG Form (DIN 40430). METRIC PG THREAD Nylon insulated straight connectors 1 7330 ⁄4" 9 5 7360 ⁄16" 9 3 † 7361 ⁄8" 11 3 † 7362 ⁄8" 13.
Liquidtight Flexible Metal Conduit Fittings Provides a positive seal against water, oil and dust! Steel Liquidtight Connectors for Type A Non-Metallic Flexible Conduit • Steel or malleable iron construction with nylon-insulated throat • Santoprene® sealing gasket with Type 316 stainless steel retaining ring • NPT hub threads seal in female threads • Offers high mechanical pull-out strength • Supplied with sealing ring and steel locknut • Available in straight, 45º and 90º in hub sizes from 3⁄8" to 2" Strai
Liquidtight Flexible Metal Conduit Fittings Fittings for Liquidtight Flexible Non-Metallic Conduit Type A Series 6302 Series 6322 Series 6302SST Connectors for Liquidtight Flexible Non-Metallic Conduit — Straight Thermoplastic Connectors for Liquidtight Flexible Non-Metallic Conduit — 90˚ Thermoplastic Connectors for Liquidtight Flexible Non-Metallic Conduit — Straight Stainless Steel Standard Material Application • To provide a liquidtight, dust-tight connection between flexible, non-metallic condui
Liquidtight Flexible Metal Conduit Fittings Stainless steel construction for unbeatable strength and corrosion resistance! Stainless Steel Fittings for Liquidtight Flexible Non-Metallic Conduit Type A • Type 304 stainless steel body, gland and locknut • Supplied with Series 5262 Sealing Gasket (see p. A-113) • UL Listed and CSA Certified for use with Type A conduit only Length NPT Thread Dia. NEW! CAT. NO. Straight Connector 6302SST 6303SST 6304SST 6305SST CONDUIT SIZE DIA. (IN.) LENGTH (IN.
Shureflex™ Nylon Conduit System A fast, flexible and watertight system of protection for electrical cables! Shureflex™ Nylon Conduit • Made from Polyamide 6 (PA6) or Polyamide 12 (PA12) Available Spring 2009! • Halogen, phosphor and cadmium free • Available in Standard Grade (PA6), Medium Grade (PA6) and Extra Flexible Grade (PA12) Standard Grade (PA6) Conduit ® • Very flexible and light • Typical applications include general wiring, machine tools, industrial equipment and automotive • UL94V-2 flammabi
Shureflex™ Nylon Conduit System High-performance fittings with a unique self-locking mechanism! Shureflex™ Nylon Conduit Fittings • Quick and secure installation — one-piece assembly with no tools required • Made from Polyamide 6 (PA6) — halogen, phosphor and cadmium free • Watertight protection (IP66 rating standard) and outstanding pull-out strength • UL94V-2 flammability rated • Temperature range of –40˚ C to 105˚ C (–40˚ F to 221˚ F) • Recommended for connecting Shureflex™ nylon conduit in electrica
Shureflex™ Nylon Conduit System Available Spring 2009! T Fittings Y Fittings CAT. NO. CONDUIT NOM. SIZE (IN.) CONDUIT NOM. SIZE (MM) STD. PKG. QTY. NY-T10 NY-T12 NY-T17 NY-T23 NY-T29 NY-T36 ⁄8 ⁄2 3 ⁄4 1 11⁄4 11⁄2 10 12 17–18 23 29 36 20 20 20 10 5 5 3 1 CAT. NO. NY-Y17-12-BK NY-Y23-17-BK NY-Y29-23-BK NY-Y36-29-BK NY-Y48-36-BK CONDUIT NOM. SIZE (IN.) CONDUIT NOM. SIZE (MM) STD. PKG. QTY.
Shureflex™ Nylon Conduit System Use on Shureflex™ fittings to achieve IP68 and IP69K ratings. Use on Shureflex™ conduit to achieve IP68 and IP69K ratings.
XTRA FLEX® System — Conduit, Tubing, Fittings for Non-Metallic Liquidtight Conduit Specification Sheet — Bullet Liquidtight Fittings or Liquidtight Flexible Non-Metallic Conduit and Tubing ® Application A series of nonmetallic connectors designed to provide a liquidtight seal when terminating liquidtight nonmetallic conduit (UL Type B) or liquidtight nonmetallic tubing to a box or enclosure with knockout opening or a threaded hub.
XTRA FLEX® System — Conduit, Tubing, Fittings for Non-Metallic Liquidtight Conduit The BULLET® non-metallic liquidtight fitting — easy to use, built to take it! Plastic Bullet® Liquidtight Fittings for T&B LTC Non-Metallic Liquidtight Conduit Type B and T&B EFC Flexible Tubing This engineering breakthrough meets the demand for a tough, reusable, non-metallic liquidtight fitting for use with XTRA FLEX® Type B conduit or flexible tubing.
XTRA FLEX® System — Conduit, Tubing, Fittings for Non-Metallic Liquidtight Conduit Table 1 — Behavior of EMS20-1B.1 IN: Aqueous Solutions of Inorganic Salts at Room Temperature SALT SOLUTIONS 10% Ammonium Chloride 10% Aluminum Chloride 10% Sodium Hypochlorite (0.
XTRA FLEX® System — Conduit, Tubing, Fittings for Non-Metallic Liquidtight Conduit Metallic Bullet® Liquidtight Connectors for T&B LTC Non-Metallic Liquidtight Conduit Type B and T&B EFC Flexible Tubing A B C Figure Figure 1 A CAT. NO. FIG. TRADE SIZE (IN.
XTRA FLEX® System — Conduit, Tubing, Fittings for Non-Metallic Liquidtight Conduit Material — PVC When you have a conduit application in a liquidtight environment, it’s time to load up the T&B Bullet®. Thomas & Betts introduces the ISO Metric Bullet® liquidtight fittings for use with the 3⁄8", 1⁄2" and 3⁄4" XTRA FLEX® EFC and LTC non-metallic liquidtight conduit series.
XTRA FLEX® System — Conduit, Tubing, Fittings for Non-Metallic Liquidtight Conduit Material — PVC Maximum flexibility for tight applications! Corrugated Flexible Non-Metallic Tubing • OEM grade — UL Recognized • PVC material Recommended industrial applications • Protection of fiber optic cable • Black color standard • Installation of instrumentation and control cable • Extremely fast installation • Indoor/outdoor lighting • Liquidtight with specified fittings • Packaging equipment • Good tensile s
XTRA FLEX® System — Conduit, Tubing, Fittings for Non-Metallic Liquidtight Conduit Material — PVC NEW! Now available in reels. XTRA FLEX® Conduit The XTRA FLEX® system offers a lightweight, liquidtight flexible conduit solution for demanding applications. The XTRA FLEX® system ensures fast, easy installations and long-lasting, high performance in a variety of environments. Now, XTRA FLEX® Conduit is available on reels.
XTRA FLEX® System — Conduit, Tubing, Fittings for Non-Metallic Liquidtight Conduit Material — PVC Smooth, sunlight- and oil-resistant outer jacket, approved for outdoor use! Smooth Liquidtight Non-Metallic Conduit Type B Industrial Grade • Industrial grade — UL Listed/CSA Certified • PVC material • Liquidtight non-metallic conduit Type B • Black color standard • Fast installation — even in tight, cramped spaces • Smooth inner diameter enables easy wire pulling CAT. NO. CONDUIT SIZE MIN.
XTRA FLEX® System — Conduit, Tubing, Fittings for Non-Metallic Liquidtight Conduit Material — PVC XTRA FLEX® Non-Metallic Conduit Type B and Flexible Tubing A = SATISFACTORY CHEMICAL B = BE EXPECTED TO CHANGE CHEMICAL C = NOT RECOMMENDED CHEMICAL Acetate Solvents . . . . . . . . . . . . . . . . . . . C Acetic Acid (10%). . . . . . . . . . . . . . . . . . A Acetic Acid (Glacial) . . . . . . . . . . . . . . . . B Acetone. . . . . . . . . . . . . . . . . . . . . . . . . . C Acrylonitrile. . . . . . . . . .
Flexible Cord and Cable Fittings Flexible Cord Connectors The Ranger® Series Cord Connector Fittings Our Ranger® Liquidtight fittings are the only connectors able to take a .250 inch cable range.
Flexible Cord and Cable Fittings Whatever the application. Whatever the size. Thomas & Betts is your connection to tough, versatile cord and cable fittings. Thomas & Betts offers a complete line of rugged, reliable cord and cable fittings. All fittings are produced to the highest standards, combining innovative design and precision manufacturing methods to provide the products you need for your specific applications.
Flexible Cord and Cable Fittings 2920 Ranger® Series 2516 Series 2920AL Ranger® Series 2920SST Ranger® Series Ranger® Series of Liquidtight Flexible Cord and Cable Connectors Application • A liquidtight connector to connect flexible cord or cable to an enclosure and provide adequate strain relief Standard Material Features • Liquidtight connection with enclosure is ensured by: Retaining RingThermoplastic/Stainless Steel (A)Taper threaded hub on 2520 series for female hub application (B)Using sealin
Flexible Cord and Cable Fittings The Ranger® Series of Steel Liquidtight Cord Connectors The Ranger® Series Steel Liquidtight Connector takes twice the cable range of most ordinary strain relief connectors. T&B’s Ranger Connectors enable you to reduce your inventory and save time with one connector that can do the work of two.
Flexible Cord and Cable Fittings The Ranger® Series of Non-Metallic Liquidtight Cord Connectors Application • Provide means for passing a cord into an enclosure or through a bulkhead or into a rigid conduit The Ranger® Series Non-Metallic Liquidtight Cord Connector takes twice the cable range of most ordinary strain relief connectors. T&B’s Ranger Connectors enable you to reduce your inventory and save time with one connector that can do the work of two.
Flexible Cord and Cable Fittings Type 304 stainless construction for your harshest environments! The Ranger® Series of Stainless Steel Liquidtight Cord Connectors Until now, there’s been no ideal solution for liquidtight connections of portable cord to a box or enclosure in corrosive environments. Steel connectors rust, and non-metallic connectors can’t withstand high temperatures or ultraviolet exposure.
Flexible Cord and Cable Fittings The Ranger® Series of Aluminum Liquidtight Cord Connectors Application • A liquidtight connector to connect flexible cord to an enclosure and provide adequate strain relief • Form a mechanical grip and water and liquidtight seal NEW! • Installer can simply use screwdriver to get into the hard-to-reach area and secure the gland nut • Marked with cable ranges and conduit hub sizes C Material • Form a non-slip connection • Body: Copper-free Aluminum or termination for flexib
Flexible Cord and Cable Fittings T&B Liquidtight Strain Relief Cord Connectors C C A A The T&B Steel Liquidtight Strain Relief Cord Connector is suited for most general control and power cable applications. This series features sturdy neoprene bushings and tapered hub threads.
Flexible Cord and Cable Fittings Liquidtight Strain Relief Connectors — 45° C A B For wire mesh grips refer to page A-147. Liquidtight Strain Relief Connectors — 90° B A C * Remove sufficient outer covering of cable to permit conductors to pass through connector body. † UL not applicable. Complies with JIC standards. UL Listed as liquidtight strain relief and outlet bushing. CSA certified watertight. Temperature rating 105°C.
Flexible Cord and Cable Fittings CHASE® Liquidtight Cord Connectors CAT. NO. CABLE SIZE RANGE SIZE (IN.) 2631 2632 2633 2634 2637 2638 2639 2640 2641 2646 2647 2648 (.125-.250) (.250-.375) (.375-.500) (.450-.560) (.125-.250) (.250-.375) (.375-.500) (.500-.625) (.625-.750) (.500-.625) (.625-.750) (.750-.880) THROAT DIA. CORD RANGE ⁄2" ⁄2" 1 ⁄2" 1 ⁄2" 3 ⁄4" 3 ⁄4" 3 ⁄4" 3 ⁄4" 3 ⁄4" 1" 1" 1" ⁄16" ⁄16" 9 ⁄16" 9 ⁄16" 25 ⁄32" 25 ⁄32" 25 ⁄32" 25 ⁄32" 25 ⁄32" 1" 1" 1" 1 1 DIMENSIONS (IN.
Flexible Cord and Cable Fittings — Non-Metallic Non-Metallic Liquidtight Flexible Cord Connectors — Black Beauty® Series Standard Material Application • A liquidtight connector to connect flexible cord to a box or enclosure and provide adequate strain relief 2672 Series Gland Body, Gland & Segmented Chuck . . . . . . . . . . Weather stabilized thermoplastic rated for 34° C (-29° F) to 105° C (221° F) application. Bushing . . . . . . . . . . . . . . . . . . . . . .
Flexible Cord and Cable Fittings Rugged, weather-stabilized nylon construction! Black Beauty® Non-Metallic Liquidtight Strain Relief Connector — Straight CAT. NO. • UL 94-V2 flammability rated • Temperature rating: -34° C to +105° C • Meets Coast Guard CG293 2671 2690 2672 2673* 2691* 2692* 2693 2694* 2674 2675 2696* 2676 2677 2678* 2699 2702 2703 2704 2705-TB 2706 2707 2708 2709 2710* TRADE OR HUB SIZE THROAT DIAM. (IN.) CORD RANGE (IN.) A DIMENSIONS (IN.
Flexible Cord and Cable Fittings The T&B WMG-PC Series Wire Mesh Grips for Portable Cord T&B Wire Mesh grips are ordered separately and fit with your existing inventory of Ranger® connectors and liquidtight strain relief connectors. There’s no need to duplicate inventory.
Non-Metallic Cable and Cord Fittings Low-profile cable gland perfect for tight spots. Non-Metallic Cable Glands T&B Nylon Cable Glands have a sturdy cable sealing mechanism that results in superior strain relief. The compact size ensures quick and easy installation in cramped spaces. The non-metallic construction provides excellent corrosion, chemical and impact resistance. The glands have long threads and locknuts are available.
Non-Metallic Cable and Cord Fittings Non-Metallic Cable/Cord Fitting with Integral Strain-Relief NEW! Thomas & Betts is pleased to announce the new non-metallic spiral cable/cord connector. T&B spiral cable/cord connectors are ideal in environments where maximum protection is needed against conductor fatigue caused by flexing cables.
Service Entrance Cable Fittings Suggested Specifications for Service Entrance Fittings All service fittings shall be approved for the purpose by a nationally recognized testing laboratory, inspection agency or product evaluation organization. Where service raceway consists of a rigid metal conduit, intermediate metal conduit, electrical metallic tubing or where service entrance cable is used as service conductors, a suitable rain tight service head conforming to Federal Standard W-C-586 shall be provided.
Service Entrance Cable Fittings Suggested Specifications for Service Entrance Fittings (Continued) Where service entrance cable is used as overhead service conductors and code requires use of a service head, entrance caps shall be installed; caps shall be cast metal type of suitable ferrous or non-ferrous metal equipped with thermoset insulators and proper knockout openings; caps when installed with proper drip loop must ensure raintight conditions.
Service Entrance Cable Fittings Service Entrance Cable Connector Range (Type SE/Type Use) C Oval (Flat) Cable Size . . . . . . . . . . . . . . . ….260 x .500 thru 1.062 x 1.765 Type USE Cable Size . . . . . . . . . . . . . …3 #12 thru 3-4/0 AWG Conductors Hub Size. . . . . . . . . . . . . . . . . . . . . .
Service Entrance Cable Fittings Oil- and water-resistant neoprene bushing specially designed for sealing around underground feeder cable! Underground Liquidtight Feeder-Cable Fittings • Stainless steel retaining ring provides bearing surface for glandnut and eliminates cable twist • Ribbed glandnut tightens easily with wrench to form high-strength connection CAT. NO. 2116-TB* 2237 2238 2239 HUB SIZE CABLE OPENING A ⁄2" ⁄4" 3 ⁄4" 3 ⁄4" .235 x .500 .230 x .430 .235 x .465 .240 x .
Service Entrance Cable Fittings Two-taper design — one slow and one fast — enables connectors to accept varied cable sizes for maximum take-up! Watertight Connectors for Oval Cable Watertight Connectors for Oval Cable • Tapered neoprene bushings resist oil, sunlight and water • Hex gland and body take same wrench opening • Stainless-steel slip ring prevents cable from twisting as gland ring is tightened • Threads on body tapered for water-sealing CAT. NO. HUB SIZE MAX. MIN.
Metal Clad Cable, Armored Cable and Flexible Metal Conduit Fittings Metal Clad Cable, Armored Cable and Flexible Metal Conduit Armored Cable (Type AC) — Ref. NEC Article 320 National Electrical Code defines type AC armored cable as, “A fabricated assembly of insulated conductors in a flexible metallic enclosure.” ACT Indicates an armored cable employing conductors having thermoplastic (Type T) insulation. AC Indicates an armored cable employing conductors having rubber insulation of code grade.
Metal Clad Cable, Armored Cable and Flexible Metal Conduit Fittings Metal Clad Cable, Armored Cable and Flexible Metal Conduit — continued Flexible Metal Conduit — Ref. NEC Article 348 Flexible metal conduit can be used for exposed or concealed work in dry locations. It can be used for wet locations provided conductors within are lead covered or other approved type. Flexible metal conduit cannot be used underground or embedded in poured concrete or aggregate.
Metal Clad Cable, Armored Cable and Flexible Metal Conduit Fittings TITE-BITE® Connectors Application • To connect and effectively bond metal clad cables, armored cable or flexible metal conduit to a box or an enclosure Typical Installation Saddle Locknut Features • Provided with an angled saddle designed to: 3110 Series Super-Fast Installation! Up to 2X faster than standard connectors! Very High Cable Pull-Out Resistance! (1) Firmly secure conduit in place without damaging cable armor (Mechanical hol
Metal Clad Cable, Armored Cable and Flexible Metal Conduit Fittings Designed to resist vibration and strain! TITE-BITE® Connectors — Nylon-Insulated • Super-fast installation and extreme pull-out resistance due to angled saddle design • Steel or malleable iron construction • Tough, insulated lining and Tite-Bite® design make these connectors a “must” when conductors are subject to vibration or strain • Look for the unique T&B blue color to ensure the highest quality fitting CAT. NO. CABLE OPENING (IN.
Metal Clad Cable, Armored Cable and Flexible Metal Conduit Fittings The easiest and best connector to install when making sharp bends at the enclosure or equipment! TITE-BITE® Connectors — 90° Angle Nylon-Insulated • Steel or malleable iron construction • Offers all of the advantages of the straight connector with only one screw to tighten, except in the larger sizes, which have two • Peep hole on top provides for easy inspection of ABC bushing • Narrow design makes it easy to install connectors in adjacent
Metal Clad Cable, Armored Cable and Flexible Metal Conduit Fittings Fits every size of armored cable, metal clad cable and flexible metal conduit! Squeeze Connectors — Straight CAT. NO. B C A • Malleable iron or steel construction • Catalog No. 253 is steel INS. CAT. NO. CABLE OPENING (IN.) MAX. MIN. 252*** — .531 253-TB**†† 253-I-TB**†† .585 254-TB 254-I-TB .938 255 255-I 1.094 256 256-I 1.375 257*** 257-I*** 1.656 258*** 258-I*** 1.875 259*** 259-I*** 2.500 249*** 249-I*** 3.
Metal Clad Cable, Armored Cable and Flexible Metal Conduit Fittings Armor-gripping saddle stays open by itself when cable is being inserted! Two-Screw Connectors C • Formed steel body • Carefully round bushing CAT. NO. CABLE OPENING (IN.) MAX. MIN. 3301-TB** 3312-TB .656 .937 TRADE SIZE .250 .500 ** UL Listed for armored cable only. K.O. SIZE A DIMENSIONS (IN.) B C ⁄2" 1 ⁄2" ⁄32 13⁄32 15⁄16 15⁄8 11⁄16 13⁄8 ⁄8" 1 ⁄2" 3 1 31 UL File No. E 1383 A B CSA File No.
Non-Metallic Sheathed Cable Fittings Non-Metallic Sheathed Cable Ref. NEC Article 336 Code defines non-metallic sheathed cable as, “A factory assembly of two or more insulated conductors having an outer sheath of moisture resistant, flame retardant, non-metallic material.” NEC 300-4(b) requires that cable be protected from physical damage when it passes through factory or field punched, cut or drilled holes in metal members. A bushing or grommet firmly secured in place is recommended.
Non-Metallic Sheathed Cable Fittings Suggested Specifications for Non-Metallic Sheathed Cable Fittings • Where non-metallic sheathed cable or flexible cord terminates into a threaded or threadless opening, terminating fittings used shall be approved for the purpose by nationally recognized laboratory, inspection agency or product evaluation organization.
Non-Metallic Sheathed Cable Fittings Non-Metallic Sheathed Cable and Flexible Cord Connectors (All Plastic) Application • To connect non-metallic sheathed cable and flexible cord to a box or an enclosure Standard Material Features • Design provides strain relief by partially deflecting cable (A); therefore: Standard Finish CABLE/ KNOCKOUT CAT. NO.
Non-Metallic Sheathed Cable Fittings Non-Metallic Sheathed Cable & Flexible Cord Connectors (Steel) 3302M Series Non-Metallic Sheathed Cable Connector Typical Installation Application • To connect non-metallic sheathed cable and flexible cord to a box or an enclosure • Insulator firmly secured in place protects conductors and reduces wire pulling effort; protects threads from damaging during handling (D) Features • Rugged all-steel/malleable iron construction (A) • Locknut designed to secure connector
Non-Metallic Sheathed Cable Fittings Steel or malleable iron. Two-Screw Connectors Rounded cable grip and smooth bushing protect the cable sheath and wire insulation. Because saddle is threaded, screws do not travel or extend beyond the connector body as it is clamped to the cable. An extra lip on the saddle closes the unused part of the connector opening.
Conduit Dimensional Data UL Recommended Dimensions and Weights of Rigid Metal Conduit TRADE SIZE (IN.) ⁄4 3 ⁄8 1 ⁄2 3 ⁄4 1 11⁄4 11⁄2 2 21⁄2 3 31⁄2 4 41⁄2 5 6 1 THDS. PER IN. I.D. (IN.) O.D. (IN.) WALL THICKNESS (IN.) MIN. WT. AT 100' LENGTHS WITH ONE COUPLING ATTACHED (LBS.) 18 18 14 14 111⁄2 111⁄2 111⁄2 111⁄2 8 8 8 8 8 8 8 0.364 0.493 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 3.548 4.026 4.506 5.047 6.065 .540 .675 .840 1.050 1.315 1.660 1.900 2.375 2.875 3.500 4.000 4.500 5.000 5.563 6.
Conduit Dimensional Data Knockout (Sliphole) Sizes for Electrical Conduits and Connectors UL Recommended Diameters for Flexible Metal Conduit (Greenfield) TRADE SIZE (IN.) NOM. KNOCKOUT DIAMETER MIN. MAX. TRADE SIZE (IN.) ⁄4 3 ⁄8 1 ⁄2 3 ⁄4 1 11⁄4 11⁄2 2 21⁄2 3 31⁄2 4 41⁄2 5 6 .575 .718 .875 1.109 1.375 1.734 1.984 2.469 2.969 3.594 4.125 4.641 5.109 5.719 6.813 .559 .703 .859 1.094 1.359 1.719 1.958 2.433 2.938 3.563 4.063 4.563 5.063 5.625 6.700 .605 .734 .906 1.141 1.406 1.766 2.000 2.500 3.