Design Guide

CATEGORY | INSTALLATION
1.800.735.4328 | THERMADOR.COM
61
PRO GRAND
®
RANGES | INSTALLATION
1.800.735.4328 | THERMADOR.COM
PRO GRAND
®
RANGES
INSTALLATION
61
36-INCH, 48-INCH AND 60-INCH PRO GRAND
RANGE DIMENSIONS AND CLEARANCE
REQUIREMENTS WITH “FLUSH ISLAND TRIM”
36-INCH, 48-INCH AND 60-INCH PRO GRAND
RANGE DIMENSIONS AND CLEARANCE
REQUIREMENTS WITH “LOW BACK”
Note: A 36-inch minimum clearance is required between
the top of the cooking surface and the bottom of an
unprotected cabinet. A 30-inch clearance can be used
when the bottom of the wood or metal cabinet is
protected by not less than
1
/
4
inch of a ame retardant
material covered with not less than No. 28 MSG sheet
steel, 0.015 inch (0.4 mm) thick stainless steel, 0.024 inch
(0.6 mm) aluminum, or 0.020 inch (0.5 mm) thick copper.
Combustible
Materials
31¼" (794 mm)
29
1
/
8
" (740 mm)
36" (914 mm) min.
to combustible
materials
25
1
/
8
" (638 mm)
max. recess depth
Combustible
Back Wall
35
7
/
8
" (911 mm) Min.
36¾" (933 mm) Max.
26
7
/
8
" (683 mm)
48¾" (1238 mm)
Installation Clearances with Flush Island Trim
12” (305 mm) min. to
combustible surface
with Flush Island Trim
12" (305 mm) min. to
combustible surface
with Flush Island Trim
If an inner wall
is used under the
cantilever counter
top, there should be a
1
/
8
" (3 mm) gap from
the rear of the range
to the inner wall.
For Flush Island Trim
For Flush Island Trim
installations, counterinstallations, counter
surface should havesurface should have
a cantilever edgea cantilever edge
meeting the back meeting the back
section of the Flush
section of the Flush
Island Trim accessory.Island Trim accessory.
Shaded area behind
range indicates
minimum clearance
to combustible surfaces,
combustible materials
cannot be located within
this area.
Shaded area behind
range indicates
minimum clearance
to combustible surfaces,
combustible materials
cannot be located within
this area.
As defined in the “National Fuel Gas Code” (ANSI Z223.1, Current Edition).
Clearances from non-combustible materials are not part of the ANSI Z21.1
scope and are not certified by CSA. Clearances of less than 12" (305 mm)
must be approved by the local codes and/or by the local authority having jurisdiction.
Combustible
Materials
31¼" (794 mm)
29
1
/8
" (740 mm)
36" (914 mm) min.
to combustible
materials
25
1
/8
" (638 mm)
max. recess depth
Combustible
Back Wall
35
7
/8
" (911 mm) Min.
36¾" (933 mm) Max.
26
7
/8
" (683 mm)
48¾" (1238 mm)
Installation Clearances with Flush Island Trim
12” (305 mm) min. to
combustible surface
with Flush Island Trim
12" (305 mm) min. to
combustible surface
with Flush Island Trim
If an inner wall
is used under the
cantilever counter
top, there should be a
1
/8
" (3 mm) gap from
the rear of the range
to the inner wall.
For Flush Island Trim
For Flush Island Trim
installations, counter
installations, counter
surface should have
surface should have
a cantilever edge
a cantilever edge
meeting the back
meeting the back
section of the Flush
section of the Flush
Island Trim accessory.
Island Trim accessory.
Shaded area behind
range indicates
minimum clearance
to combustible surfaces,
combustible materials
cannot be located within
this area.
Shaded area behind
range indicates
minimum clearance
to combustible surfaces,
combustible materials
cannot be located within
this area.
As defined in the “National Fuel Gas Code” (ANSI Z223.1, Current Edition).
Clearances from non-combustible materials are not part of the ANSI Z21.1
scope and are not certified by CSA. Clearances of less than 12" (305 mm)
must be approved by the local codes and/or by the local authority having jurisdiction.
9" (229 mm)
Lowback
Combustible
Materials
31¼" (794 mm)
29
1
/8
" (740 mm)
36" (914 mm) min.
to combustible
materials
25
1
/8
" (638 mm)
max. recess depth
Combustible
Back Wall
35
7
/8
" (911 mm) Min.
36¾" (933 mm) Max.
26
7
/8
" (683 mm)
48¾" (1238 mm)
Installation Clearances with Low Backguard
As defined in the “National Fuel Gas Code” (ANSI Z223.1, Current Edition).
Clearances from non-combustible materials are not part of the ANSI Z21.1
scope and are not certified by CSA. Clearances of less than 12" (305 mm)
must be approved by the local codes and/or by the local authority having jurisdiction.
9" (229 mm)
Lowback
Combustible
Materials
31¼" (794 mm)
29
1
/
8
" (740 mm)
36" (914 mm) min.
to combustible
materials
25
1
/
8
" (638 mm)
max. recess depth
Combustible
Back Wall
35
7
/
8
" (911 mm) Min.
36¾" (933 mm) Max.
26
7
/
8
" (683 mm)
48¾" (1238 mm)
Installation Clearances with Low Backguard
As defined in the “National Fuel Gas Code” (ANSI Z223.1, Current Edition).
Clearances from non-combustible materials are not part of the ANSI Z21.1
scope and are not certified by CSA. Clearances of less than 12" (305 mm)
must be approved by the local codes and/or by the local authority having jurisdiction.