Datasheet

THEORY OF OPERATION
Serial Interface Description
F/S-Mode Protocol
H/S-Mode Protocol
TPS62350, TPS62351
TPS62352, TPS62353
TPS62354, TPS62355, TPS62356
www.ti.com
.............................................................................................................................................................. SLVS540E MAY 2006 REVISED APRIL 2008
I
2
C is a 2-wire serial interface developed by Philips Semiconductor (see I
2
C-Bus Specification, Version 2.1,
January 2000). The bus consists of a data line (SDA) and a clock line (SCL) with pull-up structures. When the
bus is idle, both SDA and SCL lines are pulled high. All the I
2
C compatible devices connect to the I
2
C bus
through open drain I/O pins, SDA and SCL. A master device, usually a microcontroller or a digital signal
processor, controls the bus. The master is responsible for generating the SCL signal and device addresses. The
master also generates specific conditions that indicate the START and STOP of data transfer. A slave device
receives and/or transmits data on the bus under control of the master device.
The TPS6235x device works as a slave and supports the following data transfer modes, as defined in the
I
2
C-Bus Specification: standard mode (100 kbps), fast mode (400 kbps), and high-speed mode (up to 3.4 Mbps
in write mode). The interface adds flexibility to the power supply solution, enabling most functions to be
programmed to new values depending on the instantaneous application requirements. Register contents remain
intact as long as supply voltage remains above 2.2 V (typical).
The data transfer protocol for standard and fast modes is exactly the same, therefore, they are referred to as
F/S-mode in this document. The protocol for high-speed mode is different from the F/S-mode, and it is referred to
as HS-mode. The TPS6235x device supports 7-bit addressing; 10-bit addressing and general call address are
not supported.
The TPS6235x device has a 7-bit address with the 2 LSB bits factory programmable allowing up to four dc/dc
converters to be connected to the same bus. The 5 MSBs are 10010.
The master initiates data transfer by generating a start condition. The start condition is when a high-to-low
transition occurs on the SDA line while SCL is high, see Figure 45 . All I
2
C-compatible devices should recognize a
start condition.
The master then generates the SCL pulses, and transmits the 7-bit address and the read/write direction bit R/W
on the SDA line. During all transmissions, the master ensures that data is valid. A valid data condition requires
the SDA line to be stable during the entire high period of the clock pulse, see Figure 46 . All devices recognize
the address sent by the master and compare it to their internal fixed addresses. Only the slave device with a
matching address generates an acknowledge, see Figure 47 , by pulling the SDA line low during the entire high
period of the ninth SCL cycle. Upon detecting this acknowledge, the master knows that the communication link
with a slave has been established.
The master generates further SCL cycles to either transmit data to the slave (R/W bit 1) or receive data from the
slave (R/W bit 0). In either case, the receiver needs to acknowledge the data sent by the transmitter. An
acknowledge signal can either be generated by the master or by the slave, depending on which one is the
receiver. 9-bit valid data sequences consisting of 8-bit data and 1-bit acknowledge can continue as long as
necessary.
To signal the end of the data transfer, the master generates a stop condition by pulling the SDA line from low to
high while the SCL line is high, see Figure 45 . This releases the bus and stops the communication link with the
addressed slave. All I
2
C compatible devices must recognize the stop condition. Upon the receipt of a stop
condition, all devices know that the bus is released, and they wait for a start condition followed by a matching
address
Attempting to read data from register addresses not listed in this section results in FFh being read out.
When the bus is idle, both SDA and SCL lines are pulled high by the pull-up devices.
The master generates a start condition followed by a valid serial byte containing HS master code 00001XXX.
This transmission is made in F/S-mode at no more than 400 Kbps. No device is allowed to acknowledge the HS
master code, but all devices must recognize it and switch their internal setting to support 3.4-Mbps operation.
Copyright © 2006 2008, Texas Instruments Incorporated Submit Documentation Feedback 25
Product Folder Link(s): TPS62350, TPS62351 TPS62352, TPS62353 TPS62354, TPS62355, TPS62356