Datasheet

108-2043
3.3. Ratings
! Voltage: 600 volts AC m axim um
! Operating Tem perature: 105°C maxim um
3.4. Perform ance and Test Description
Product is designed to m eet the electrical, m echanical and environm ental perform ance requirem ents
specified in Figure 1.
3.5. Test Requirem ents and Procedures Sum mary
Test Description Requirem ent Procedure
Exam ination of Product. Meets requirem ents of product
drawing and Application Spec 114-
2123.
TE Spec 109-1.
Visual, dim ensional and functional
per applicable inspection plan.
ELECTRICAL
Dielectric W ithstanding Voltage,
Test Condition A.
No breakdown or flashover when
3400 volts AC are applied for 1
minute.
UL 310, 600 Volt Rating.
Test wired terminals in Num ber 12
lead shot.
Dielectric W ithstanding Voltage,
Test Condition C.
No breakdown or flashover at rear
of term inal when 3000 volts AC are
applied for 1 m inute.
UL 310, 600 Volt Rating.
Test on flat m etal plate.
See Figure 4.
Dielectric W ithstanding Voltage,
Receptacle, Tab Entry Position.
Terminal Applied
Size Voltage (volts AC)
250 1000
187 1000
110 600
No breakdown or flashover, 1
minute hold.
TE Spec 109-29-1.
Test wired terminals on a flat m etal
plate.
See Figure 5.
Heating (Tem perature Rise). W ire Size Current (am peres)
(AW G) .110 Others
26 1 1
24 2 2
22 2 3
20 3 4
18 4 7
16 5 10
14 8 15
12 20
10 24
20°C m axim um tem perature rise.
UL 310.
Stabilize at specified current and
measure temperature rise.
Figure 1 (continued)
Rev D 2 of 5