IOM SYSCREW 440 1550 WATER EVO
Table Of Contents
34
8 - Technical Data (continued)
8.2 Technical data
SYSCREW WATER EVO CO STD / S 440 490 570 630 700 770 860
Power supply V/Ph/Hz 400 (± 10%) / 3 / 50
Number of refrigerant circuits 1 2
Start-up Type SD
Total capacity steps % 50-75-100
25-50-62-
75-87-100
COMPRESSOR
Number 1 2
Type Screw
INTERNAL HEAT EXCHANGER (EVAPORATOR)
Number 1
Type Shell & tube (Pure counterflow)
Water connections inch 6 6 6 6 8 8 8
EXTERNAL HEAT EXCHANGER (CONDENSER)
Number 1 2
Type Shell & tube
Water connections inch 4 4 5 5 5 5 4 / 4
REFRIGERANT
Type / GWP R134a / 1430
Charge (1)
kg
54 54 74 92 93 87 114
tCO
2
eq
77,2 77,2 105,8 131,6 133,0 124,4 163,0
Type / GWP R513A / 631
Charge (1)
kg
54 54 74 92 93 87 114
tCO
2
eq
34,1 34,1 46,7 58,1 58,7 54,9 71,9
DESUPERHEATER
Number 1 2
Type PHE
Water connections inch 2”1/2 N.A. 2”1/2
WEIGHT (STD VERSION)
Shipping kg 2475 2485 2658 2770 3134 3176 4636
Operating kg 2690 2700 2875 3003 3472 3521 5000
WEIGHT (S VERSION)
Shipping kg 2669 2679 2852 2964 3328 3370 5024
Operating kg 2884 2894 3069 3197 3666 3715 5388
DIMENSIONS (STD VERSION)
Length mm 4250 4250 4210 4210 4180 4180 4510
Width mm 1350 1350 1350 1350 1350 1350 1520
Height mm 1650 1650 1650 1650 1650 1650 1710
DIMENSIONS (S VERSION)
Length mm 4250 4250 4210 4210 4180 4180 4510
Width mm 1350 1350 1350 1350 1350 1350 1520
Height mm 1750 1750 1750 1750 1750 1750 1780
(1) The refrigerant value are indicative values for standard units. The actual data are indicated on the unit label.