IOM SYSCREW 440 1550 WATER EVO
Table Of Contents
33
English
8 - Technical Data (continued)
Desuperheater pressure drop
(*) Capacity referred to only one circuit.
Model
Nom. Capacity Qnom. Qmax. Qmin. K Dp nom DP max DP min
kW l/h l/h l/h kPa/(l/h)^2 kPa kPa kPa
440 34 5927 9878 3704 2.285E-08 0.8 2.2 0.3
490 38 6596 10993 4122 2.285E-08 1.0 2.8 0.4
570 44 7603 12672 4752 1.380E-08 0.8 2.2 0.3
630 49 8492 14154 5308 1.380E-08 1.0 2.8 0.4
700 not available
770 not available
860 34 5841 9734 3650 2.285E-08 0.8 2.2 0.3
920
36 6245 10409 3903 2.285E-08 0.9 2.5 0.3
990 39 6663 11105 4164 2.285E-08 1.0 2.8 0.4
1070
42 7146 11911 4466 1.380E-08 0.7 2.0 0.3
1130 44 7556 12594 4723 1.380E-08 0.8 2.2 0.3
1220
47 8160 13599 5100 1.380E-08 0.9 2.6 0.4
1280 50 8573 14288 5358 1.380E-08 1.0 2.8 0.4
1400 not available
1550 not available