IOM SYSCREW AIR EVO HSE

47
English
8 - Technical Data (continued)
SYSCREW AIR EVO HSE S 380 440 510 590 660 730
Power supply* V/Ph/Hz 400 (± 10%) / 3 / 50
Number of refrigerant circuits 2
Start-up Type PW+FI PW+FI PW+FI PW+FI SD+FI SD+FI
Min÷Max capacity steps % 22% ÷ 100% 18% ÷ 100% 16% ÷ 100% 14% ÷ 100% 13% ÷ 100% 15% ÷ 100%
COMPRESSOR
Number 2
Type 1 STEP SCREW + 1 INVERTER SCREW
INTERNAL HEAT EXCHANGER (EVAPORATOR)
Number 1
Type Shell & tube (Pure counterflow)
Water connections inch 6 6 8 8 8 8
EXTERNAL HEAT EXCHANGER (COILS)
Number 8 10 10 10 12 12
Type MCHX - Al/Alloy
FAN
Number 8 10 10 10 12 12
Air flow m³/h 152.640 191.160 191.160 191.160 229.320 229.320
Total input power kW 9.2 11.5 11.5 11.5 13.8 13.8
REFRIGERANT
Type / GWP R134a / 1430
Charge 1 / 2 (1)
kg
33 / 33 41 / 41 46 / 46 51 / 51 65 / 65 68 / 68
tCO
2
eq
47,2 / 47,2 58,6 / 58,6 65,8 / 65,8 72,9 / 72,9 93,0 / 93,0 97,2 / 97,2
Type / GWP R513A / 631
Charge 1 / 2 (1)
kg
33 / 33 41 / 41 46 / 46 51 / 51 65 / 65 68 / 68
tCO
2
eq
20,8 / 20,8 25,9 / 25,9 29,0 / 29,0 32,2 / 32,2 41,0 / 41,0 42,9 / 42,9
DESUPERHEATER
Number 2
Type PHE
WEIGHT
Shipping kg 3832 4210 4744 5077 5474 6017
Operating kg 3981 4352 4990 5323 5702 6293
DIMENSIONS
Length mm 4660 5712 5712 6764 7816 7816
Width mm 2192 2192 2192 2192 2192 2192
Height mm 2590 2590 2590 2590 2590 2590
(1) The refrigerant value are indicative values for standard units. The actual data are indicated on the unit label.
* Voltage supply tolerances: +/- 10% of the nominal Voltage (400V) for short term application; +/-5% of the nominal Voltage (400V) for continuous application
** High Temperature Units (HT), data with fans at max speed (1100 Rpm)