IOM SYSCREW AIR EVO HSE

31
English
6 - Control (continued)
List of parameters - IN/OUT MENU
Notes:
n° circuits : 2
compressor circuit 1: fixed speed step screw
compressor circuit 2: variable speed (inverter driven) screw
ANALOG INPUTS - control board
Variable Name Type Description
U1
Ntc
Leaving / Outlet water temperature
U2
4-20mA
Pressure from high pressure transducer 1
U3
4-20mA
Pressure from high pressure transducer 2
U4
Ntc
Entering / Inlet water temperature
U5
Ntc
Outdoor air temperature
U6
-
Not used
U7
-
Not used
U8
-
Not used
U9
Ntc-HT
Discharge probe temperature circuit 1
U10
Ntc-HT
Discharge probe temperature circuit 2
DIGITAL INPUTS - control board
Variable Name Type Description
ID1
24Vdc
Remote On/Off Status
ID2
24Vdc
Low pressure switch circuit 1 Status
ID3
24Vdc
Low pressure switch circuit 2 Status
ID4
24Vdc
Not used
ID5
24Vdc
Serious Alarm (phase monitor) Status
ID6
24Vdc
Thermal protection compressor 1 Status
ID7
24Vdc
Oil level switch compressor 1 Status
ID8
24Vdc
Not used
ID9
24Vdc
Not used
ID10
24Vdc
Not used
ID11
24Vdc
Not used
ID12
24Vdc
Water flow switch / Interlock Status
ID13H
230Vdc
High pressure switch comrpessor 1
ID14H
230Vdc
Not used
ID15
24Vdc
Thermal protection fan circuit 1 step 2 Status
ID16
24Vdc
Thermal protection fan circuit 1 step 1 Status
ID17
24Vdc
Thermal protection fan circuit 2 step 2 Status
ID18
24Vdc
Thermal protection fan circuit 2 step 1 Status
INPUTS / OUTPUTS - expansion card
Variable Name Type Description
U1
-
Remote double set point
U2
-
Part load / switch off Circuit 1
U3
-
Part load / switch off Circuit 2
U4
-
Thermal shared fan deck
U5
-
Not used
U6
-
Not used
U7
-
Shared fan deck (control signal)
U8
-
Analog remote set point
U9
-
Not used
U10
-
Not used