52
MODE 3 – ∆T CONTROL [VC]:
Thismodeprovidesvariableowsystem,consistingoftheprimarycircuit/primary+secondarycircuit.
VCmodeincludesthefollowingcomponents:
Twopressuretransducersinstalledattheendsoftheheatexchanger(ΔP
EVAPORATOR
) factory installed.
A dedicated system control, factory installed.
A bypass valve with actuator supplied loose (installation by the customer).
Theoptionoffersacompleteandpredenedpackage,guaranteeingsimpleselection,supplyandcommissioning.Inpar-
ticular, the unit includes an additional control system, equipped with an evolved algorithm, which interacts with the main
control of the unit.
VCmodeprovidesfollowingadvantages:
Anidealsolutionforsystemsworkingonxed∆T.
Acompletevariableowsystemwithmaximumenergysavings.
The system provides complete and reliable control of the system.
Itreducestheoperatingcostoftheplant[OPEX].
The pump speed will reduce automatically to save energy during low occupancy periods.
Abypass,whichensurestheminimumowacrosstheheatexchangerthereforepreventingtheheatexchangerfrom
freezing.
TheoperatingprincipleofVCsummarizedasfollows:
VCmodeperformsanintelligentcontroloftheowbasedontheuser-denedconstant∆T.
Theuserdenesthe∆Tsetpointfromthechillercontroller.
Theuserhasaexibilitytoxtherequiredoperatingheadfromthechillercontroller.
Thepumpspeedcanreduceuntilitreachestheminimumallowableowrateontheheatexchangeroftheunit.
Uponexceedingtheminimumallowableowthreshold,theby-passvalvewillopentriggeredbythefrequencydrive,
torecirculatetheowthatisnotrequiredbytheplant,butwhichisnecessarytoguaranteetheowrateminimum
to the exchanger.
FIGURE3:GENERALSCHEMATICSFOR∆TCONTROL