IOM SYSCREW 300 1400 AIR CO

33
English
8 - Technical Data (continued)
Standard 1070 1130 1170 1200 1300 1400
Power supply V/Ph/Hz 400V/3/50Hz
Number of refrigerant circuits 2 2 2 2 2 2
Start-up Type SD SD SD SD SD SD
Total capacity steps % 25-50-62-75-87-100
COMPRESSOR
Number 2 2 2 2 2 2
Type Screw
INTERNAL HEAT EXCHANGER (EVAPORATOR)
Number 1 1 1 1 1 1
Type Shall & tube (Pure counterflow)
Water connections inch 6 6 8 8 10 10
EXTERNAL HEAT EXCHANGER (COILS)
Number 17 18 19 20 22 24
Type MCHX - Al/Alloy
FAN
Number 17 18 19 20 22 24
Air flow m³/h 108.6 115.0 121.4 127.8 140.6 153.4
Total input power kW 35.7 37.8 39.9 42.0 46.2 50.4
REFRIGERANT
Type / GWP R134a / 1430
Charge 1 / 2 (1)
kg
73 / 83 83 / 83 79 / 92 89 / 89 96 / 104 102 / 102
tCO
2
eq
104,4 / 118,7 118,7 / 118,7 113,0 / 131,6 127,3 / 127,3 137,3 / 148,7 145,9 / 145,9
DESUPERHEATER
Number 2 2 2 2 2 2
Type PHE
Water flow Rate l/s 6.63 7.00 7.27 7.57 8.18 8.66
Water Pressure Drop kPa 8.9 7.7 8.3 7.0 8.2 9.2
WEIGHT
Shipping kg 7.490 7.760 7.970 8.180 8.570 8.890
Operating kg 7.880 8.150 8.350 8.560 8.940 9.245
DIMENSIONS
Length mm 9.900 10.900 10.900 10.900 12.000 13.000
Width mm 2.200 2.200 2.200 2.200 2.200 2.200
Height mm 2.510 2.510 2.510 2.510 2.510 2.510
(1) The refrigerant value are indicative values for standard units. The actual data are indicated on the unit label.