S - Super Low Noise Version 650 720 800 850 910 970 1000
Power supply V/Ph/Hz 400V/3/50Hz
Number of refrigerant circuits 2 2 2 2 2 2 2
Start-up Type SD SD SD SD SD SD SD
Total capacity steps % 25-50-62-75-87-100
COMPRESSOR
Number 2 2 2 2 2 2 2
Type Screw
INTERNAL HEAT EXCHANGER (EVAPORATOR)
Number 1 1 1 1 1 1 1
Type Shall & tube (Pure counterflow)
Water connections inch 6 6 8 8 8 8 8
EXTERNAL HEAT EXCHANGER (COILS)
Number 12 12 12 14 14 15 16
Type MCHX - Al/Alloy
FAN
Number 12 12 12 14 14 15 16
Air flow m³/h 51.7 51.7 51.7 60.3 60.3 64.6 68.9
Total input power kW 13.8 13.8 13.8 16.1 16.1 17.3 18.4
REFRIGERANT
Type / GWP R134a / 1430
Charge 1 / 2 (1)
kg
48 / 48 49 / 55 57 / 57 57 / 67 66 / 66 66 / 76 74 / 74
tCO
2
eq
68,6 / 68,6 70,1 / 78,7 81,5 / 81,5 81,5 / 95,8 94,4 / 94,4 94,4 / 108,7 105,8 / 105,8
DESUPERHEATER
Number 2 2 2 2 2 2 2
Type PHE
WEIGHT
Shipping kg 5.180 5.600 6.090 6.620 6.700 6.920 7.010
Operating kg 5.430 5.860 6.320 6.850 6.930 7.190 7.280
DIMENSIONS
Length mm 6.700 6.700 6.700 8.800 8.800 8.800 8.800
Width mm 2.200 2.200 2.200 2.200 2.200 2.200 2.200
Height mm 2.510 2.510 2.510 2.510 2.510 2.510 2.510