EDM SYSCREW 300 1400 AIR

|
SYSCREW 300-1400 AIR
13
Operating Limits and Correction Factors
EVAPORATOR CONDENSER
Fouling factor
(m
2
.°C/kW)
Cooling capacity
factor
Power input
factor
Fouling factor
(m
2
.°C/kW)
Cooling capacity
factor
Power input
factor
0.044 1.000 1.000 0.044 1.000 1.000
0.088 0.987 0.995 0.088 0.987 1.023
0.176 0.964 0.985 0.176 0.955 1.068
0.352 0.915 0.962 0.352 0.910 1.135
Fouling factors
Altitude (m) Cooling capacity factor Power input factor
0 1.000 1.000
600 0.987 1.010
1.200 0.973 1.020
1.800 0.958 1.029
2.400 0.943 1.038
Altitude factors
STD Version
14 21
43
16 15
T AirC)
LWT C)
50
40
30
20
10
0
-10
-20
-10-50 51
01
5
1 Water.
2 Water + Glycol.
3 Water + FSC.
4 Water + Glycol + FSC.
14 Brine Version.
15 Polar Version.
16 Polar + Glycol.
1 + 2 Standard unit.
S Version
14 21
16 15
T AirC)
LWT C)
50
40
30
20
10
0
-10
-20
-10 -5 0510 15
1 Water.
2 Water + Glycol.
14 Brine Version.
15 Polar Version.
16 Polar + Glycol.
1 + 2 Standard unit.
HT Version
14 21
16 15
T AirC)
LWT C)
50
40
30
20
10
0
-10
-20
-10-50 51
01
5
1 Water.
2 Water + Glycol.
14 Brine Version.
15 Polar Version.
16 Polar + Glycol.